Gamewell-FCI B224BI Advanced multi-criteria detector with four unique sensing element Datasheet

Velociti® Series
MCS-4-Warn
Description
Advanced Multi-Criteria Detector
with Four Unique Sensing Elements
•
The latest addition of the Gamewell-FCI’s Advanced
Detection product line integrates four complementary
technologies into one device to convey accurate fire
sensing information to locations where fire fighter
response-time is critical. The Gamewell-FCI MCS-4Warn is an advanced multi-criteria plug-in detector
that assembles four unique sensing elements into
one unit.
• Electrochemical cell technology that monitors carbon
monoxide (CO) produced by smoldering fires.
• Infrared (IR) sensing that measures ambient light levels
and flame signatures.
• Photo-electric smoke detection.
• Thermal detection for temperature monitoring.
It is designed to be used with the Gamewell-FCI’s E3
Series® and S3 Series fire alarm control panel only.
The integration of continuous monitoring for all four
major elements of a fire allows Gamewell-FCI to create a detector that responds more quickly to an
actual fire with the highest immunity to nuisances.
This advanced multi-criteria detector operates at a
high immunity level. It is designed to detect changing
elements, identify nuisance interference and adjust
the sensor accordingly to reduce false alarms.
Its on-board intelligence runs advanced algorithms
that dynamically adjust detection parameters to
respond to the inputs from the sensors, enabling
instant response as ambient conditions change.
The panel automatically changes sensor thresholds,
sensor gain, time, delays, combinations, sampling
rates, and averaging rates. If any sensor fails, the
detector automatically adjusts the sensitivity of the
remaining sensors and produces a fault condition.
The CO cell has an expected lifetime of approximately six years. It is not a field replaceable component. An internal timer signals the control panel to
signal the approach of the CO cell’s end of life. Upon
expiration, you should contact the system supplier to
arrange for replacement of the unit. Detection is not
compromised when the CO cell expires. The algorithms automatically adjusts to properly weigh the
inputs from the photo-electric, heat, and IR sensors.
•
MCS-4-Warn
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Applies four separate sensing elements.
Has the highest nuisance alarm immunity.
Employs advanced algorithms that interpret and
respond to multiple inputs.
Uses six levels of sensitivity.
Incorporates CO sensing for the fastest
response to slow developing, smoldering fires.
Comprises fully integrated infrared sensing to
support a quick fire alarm response.
Provides the automatic drift compensation of a
smoke sensor and a CO cell.
Offers superior EMI protection.
Includes twin LED indicators that provide 360
visibility.
Programs LEDs to be panel controlled to blink,
latch-on, or latch-off.
Contains a built-in test switch.
SIGNALING
E3 Series® and Velociti® are registered trademarks and CAMWorks™
is a trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
S1195
7272-1703:0173
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60672 Rev. D page 1 of 2
©2013 by Honeywell International Inc. All rights reserved.
Sensitivity Settings &
Suggested Applications (Continued)
Description (Continued)
Note: The CO cell is specifically deployed as a component of smoke detection in this device. This device
is not Listed for applications in which the standalone
CO detection is required for life safety.
The IR light sensor recognizes specific situations
such as welding and makes adjustments rapidly to
further reduce the potential for nuisance alarms. The
thermal detection function uses thermistor technology with a software-corrected linear temperature
response to offer exceptional nuisance alarm immunity and excellent fire detection.
4% per foot (30.48 cm) of
smoke.
Used in equipment rooms,
kitchens, paint shop.
Thermal alarm at 135° F (57° C)
Level 6:
Note: After the CO cell has reached the end of life, any
device set to Level 3 or Level 4 will default to Level 5 and
Level 5 will drop to 3%. The following sensitivities apply to
devices with expired CO cells.
1% per foot (30.48 cm) of smoke.
Level 1:
Very clean environments:
Used in Laboratories.
2% per foot (30.48 cm) of smoke.
Level 2:
Clean environments:
Used in offices.
3% per foot (30.48 cm) of smoke.
Level 5:
Moderately clean environments:
Used in hotel rooms, dorm
rooms.
Thermal alarm at 135° F (57° C)
Level 6:
Level 5:
•
•
•
•
•
Ordering Information
Part Number Description
MCS-4-Warn Advance Multi-Criteria Detector
MCS-4-Warn
Specifications
Accessories
•
Physical Specifications
Base Diameter:
Base Height:
Shipping Weight:
Operating
Temperature Range:
Operating Humidity
Range:
B210LP
B200S
4.0” (10.16 cm)
2.4” (6.1 cm)
4.6 ounces
32° F to 100° F (0° C to 38° C)
10 to 93% relative humidity
(non-condensing)
B200SR
•
Electrical Specifications
External Supply
Voltage:
Standby Current:
Alarm Current
(LED on):
Advanced multi-criteria detector
with four unique sensing elements.
B224BI
15 to 32 VDC
200 µA at 24 VDC
(no communications)
B224RB
Flanged mounting base
Intelligent sounder base, capable
of producing a variety of tone patterns including ANSI Temporal 3.
Compatible with the System Sensor synchronization protocol.
Intelligent sounder base,
Temporal 3 or Continuous tone.
Isolator base, maximum of 25
devices between isolator bases.
Relay base
7 mA at 24 VDC
•
Sensitivity Settings &
Suggested Applications
Level 1:
Level 2:
Level 3:
Level 4:
1% per foot (30.48 cm) of smoke.
Very clean environments:
Used in Laboratories.
2% per foot (30.48 cm) of smoke.
Clean environments:
Used in offices.
3% per foot (30.48 cm) of smoke.
Moderately clean environments:
Used in hotel rooms, dorm
rooms.
3% per foot (30.48 cm) of smoke
with different algorithm processing and weighting of sensor elements. Used in hotel rooms near
a shower or boiler rooms.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60672 Rev. D page 2 of 2
www.gamewell-fci.com