Gamewell-FCI AM-50-70 Intelligent network transponder Datasheet

INX
Description
Intelligent Network Transponder
The Gamewell-FCI, INX Intelligent Network Transponder
serves as the point of distribution for the system’s audio
and fire fighter telephone risers. It is a component of the
following systems.
• E3 Series® Expandable Emergency Evacuation System
• E3 Series Combined Fire and Mass Notification System
• E3 Series Broadband Audio Evacuation System
The INX occupies a single node on the E3 Broadband network and is connected by a single pair of unshielded,
twisted wires, fiber-optic cable or any combination of the
two. Each E3 Broadband node can be spaced on the network up to a maximum distance of 3,000 feet (914.4 m) or up
to an 8 dB loss using a fiber-optic cable. Built-in isolation at
each node permits Style 4, Style 6, and Style 7 network
configurations.
The E3 Broadband Audio Evacuation System is a peer-topeer, self-regenerating, token ring network comprised of up
to 64 individual nodes. In addition, the Addressable Node
Expander (ANX) board expands the network to 122 nodes.
The E3 Broadband employs proven technology and
extends it to accomplish emergency voice evacuation, 2way fire fighter communications, and building control applications. It is unique in the industry since it requires only a
single pair of wires or fiber-optic cable connections
between nodes to convey all fire alarm, digital voice, fire
fighter communications, paging, and building control signals. This system provides a 16 message capacity with up
to a 3 minute duration per INX. Messages are easily fieldconfigurable with a laptop computer
A typical INX assembly consists of the following:
• an Intelligent Network Interface-Voice Gateway
(INI-VGX) module
• a PM-9/PM-9G power supply
• up to 4 AM-50 Series amplifiers including a minimum of
one backup amplifier
It is enclosed in a compact 19” enclosure capable of
accommodating up to 12 A/H size batteries. The modular
approach of the E3 Broadband greatly simplifies the design
and the installation and allows the complete flexibility in retrofit or add-on situations. This system is ideal for a wide
range of complex system applications including high-rise or
campus installations.
INX
Features
•
•
•
•
IBC Seismic Certified
Listed under UL® Standard 864, 9th Edition.
Listed under UL Standard UL2572 for Mass Notification.
Offers all communication signals and control-by-event
sequences over two wires or fiber-optic cable including:
audio evacuation, voice paging, fire fighter intercom,
and building control signals.
Integrates with INCC command centers and additional
INX transponders to create a complete audio
evacuation system with up to 122 nodes.
Distributed architecture, including Style 7 wiring configurations, allow system components to continue normal
operation with NO loss of function during single line
fault conditions.
Uses state-of-the-art digital signal processor (DSP)
technology for efficient audio compression and filtering.
Software-programmable multi-channel digital audio
applications.
One Style 4 signaling line circuit (SLC) supporting up to
32 addressable speaker circuits (AOM-2SF used for single channel circuits and 16 addressable phones circuits
AOM-TELF).
Up to 150 watts of audio power provided by the AM-50
Series amplifiers with an 50 watts of standby amplifier
enclosed in a single, compact wall-mounted cabinet.
Each AM-50 Series amplifier provides two individually
activated speaker circuits supplying 50 watts total.
•
•
•
•
•
•
•
SIGNALING
FM
®
E3 Series is a registered trademark of Honeywell International Inc.
® is a registered trademark of Underwriters Laboratories Inc.
UL
MEA
City of
City of
Approved
Chicago
FDNY:
Approved DENVER Reference Certificate
Approved
Class
1
7165-1703:0125
COA
#-217-03-E
S1869 3017416
of Compliance
- Class 2
7170-1703:0126 - High Rise
VMA-45894-02C
APPROVED
(Revision 1)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0541 Rev. M page 1 of 4
©2013 by Honeywell International Inc. All rights reserved.
Gamewell-FCI
AM-50 Series
Figure 1 INI-VGX
INI-VGX
The INI-VGX is a multi-function module which incorporates
the following:
• Network interface using twisted, unshielded wire or
fiber-optic cable.
• Fully digital message generator.
• One signaling line circuit for local peripheral devices.
• Local fire fighter phone riser.
It occupies a single DIP switch selectable address on the
network and provides termination points for the network
connection using either a pair of twisted, non-shielded wire
(12 AWG max.) or fiber-optic cable.
The INI-VGX uses advanced Digital Signal Processing
(DSP) technology for audio compression and filtering
allowing E3 Broadband to produce the clearest audio possible. Background noise is automatically filtered during
voice paging and fire fighter communications which
increase audibility and eliminates the need for the Push-toTalk devices.
The INI-VGX can accommodate up to 16 different messages with a total combined duration of three minutes.
Each message can be field installed via a laptop computer
and the messages can be in the form of a voice message
or an evacuation tone. The INI-VGX provides a fire fighter
phone riser that would connect to phone jacks or warden
stations through AOM-TELF modules.
Figure 2 AM-50 Series Amplifiers
AM-50 Series Amplifiers
The AM-50 Series amplifiers offer 2 types of AM-50 Series
amplifiers:
• AM-50-25 amplifier produces a 25VRMS audio output
• AM-50-70 amplifier produces a 70.7VRMS audio output
The AM-50 Series amplifiers are a component of the following systems.
• E3 Series, Expandable Emergency Evacuation System
• E3 Series Combined Fire and Mass Notification System
• E3 Broadband Audio Evacuation System
Both AM-50 Series amplifiers produce 50 watt, digital,
switching power. As many as four AM-50 Series amplifier
modules can be installed in each INX CAB-B cabinet and
are supervised and controlled by an INI-VGX Voice Gateway.
Each AM-50 Series amplifier provides two speaker circuits
that can be wired Style Y (Class “B”) or Style Z (Class “A”).
The terminal connections can accommodate up to 12
AWG, twisted-pair, shielded wire. Both speaker circuits can
produce a combined 50 watt power that can be divided
between the two integral Class A/B speaker circuits. The 2
speaker circuits may be individually activated and supervised by an INI-VGX Voice Gateway.
The AM-50 Series amplifiers may be installed in an INX
CAB-B cabinet or an INCC command center using the
expander plates whenever the E3 control panel is used in
conjunction with the E3 Series®, Expandable Emergency
Evacuation System.
The INI-VGX provides one Signaling Line Circuit (SLC) to
control and supervise Addressable Output Modules (AOM)
serving as speaker circuits and fire fighter telephone circuits. The INI-VGX SLC can support up to 32 speaker circuits using the AOM-2SF for single channel applications. In
addition, each INI-VGX SLC can support up to 16 fire
fighter intercom circuits using the AOM-TELF.
Figure 3 PM-9
PM-9
The PM-9 is a switching power supply that provides 9
amps of filtered and regulated 24 VDC (nominal) to power
the INX transponder. It has an internal battery charging circuit capable of accommodating up to 55 A/H batteries as
well as an auxiliary continuous duty 24 VDC output @ 5
amps max.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0541 Rev. M page 2 of 4
www.gamewell-fci.com
Description (Continued)
Specifications (Continued)
PM-9 (Continued)
Figure 4 PM-9G
PM-9G
The PM-9G is a switching power supply that provides 9
amps of filtered and regulated 24 VDC (nominal) to power
the INX transponder. It has an internal battery charging circuit capable of accommodating up to 55 A/H batteries as
well as an auxiliary continuous duty 24 VDC output @ 5
amps max.
Specifications
Description
PM-9G
Input Voltage:
Input Current:
Output Voltage:
Output Current:
Output Current:
240 VAC @ 50/60 Hz
2.4 amps max. @ 240 VAC, 50/60 Hz
24 VDC FWR
9 amperes Alarm max. continuous
5 amperes max. continuous Standby
(when the PM-9G is used with the ILI-E3
or the ILI95-E3 Series, see Note 1).
Output Current: 4 amperes max. continuous Standby
(when the PM-9G is used with any
AM-50 Series amplifier, see Note 2).
Operating
Temperature:
32° to 120° F (0° to 49° C)
Relative
Humidity:
0 to 93%, non-condensing at 90° F (32° C)
Supervised
Non Power-Limited:
Note 1: Continuous standby loads in excess of .560 Amps
up to 5 Amps may require a Generator Backup or load
shedding during an AC power failure.
Note 2: Continuous standby loads in excess of .560 Amps
up to 4 Amps may require a Generator Backup or load
shedding during an AC power failure.
PM-9
Input Voltage:
Input Current:
Output Voltage:
Output Current:
Output Current:
120 VAC, 60 Hz
4.6 amps max. @ 120 VAC 60 Hz
24 VDC FWR
9 amperes Alarm max. continuous
5 amperes max. continuous Standby
(when the PM-9 is used with the ILI-E3
or the ILI95-E3 Series, see Note 1).
Output Current: 5 amperes max. continuous Standby
(when the PM-9 is used with any
AM-50 Series amplifier) (See Note 2)
Operating
Temperature:
32° to 120° F (0° to 49° C)
Relative
Humidity:
0 to 93%, non-condensing at 90° F (32° C)
Supervised
Non Power-Limited
Note 1: Continuous standby loads in excess of .560 Amps
up to 5 Amps may require a Generator Backup or load
shedding during an AC power failure.
Note 2: Continuous standby loads in excess of .560 Amps
up to 4 Amps may require a Generator Backup or load
shedding during an AC power failure.
Ordering Information
Part Number
Description
INX
Intelligent Network Transponder,
(Distributed Voice Network
Sub-Assembly Enclosure)
Transponder Voice Gateway
INX 9 ampere Power Supply
INX 9 ampere Power Supply
INI-VGX
PM-9
PM-9G
AM-50 Series:
AM-50-25
AM-50-70
INX 50 watt 25 VRMS audio amplifier
INX 50 watt 70.7 VRMS audio amplifier
Cabinets:
INX-CAB
Dimensions:
INX-CABR
Dimensions:
INX-CAB-B
Dimensions:
Backbox with Black Door
INX 19” W x 19” H x 4” D
(48 x 48 x 10 cm)
Backbox with Red Door
INX 19” W x 19” H x 4” D
(48 x 48 x 10 cm)
Backbox with louvered door and
INX-CAB-B Mounting Plate
19 3/8” W x 19 3/8” H x 4.5” D
(49 x 49 x 11 cm)
Seismic Battery Bracket Kits
Part Number Description
90518
NetSOLO NS-INX 7 A/H Seismic Battery
Bracket Kit
90519
E3 CAB-C (INX only) 12 A/H Seismic
Battery Bracket Kit
E3 CAB-D (INX only) 12 A/H Seismic
Battery Bracket Kit
NetSOLO NS-INX 12 A/H Seismic
Battery Bracket Kit
For additional information on the Seismic Battery
Brackets, refer to the following documents:
• Seismic Battery Bracket Installation Guide, P/N: 53839
• E3 Series Cabinets Data Sheet, P/N: 9020-0649
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
9020-0541 Rev. M page 3 of 4
1 11/16"
2. 8 cm
19 3/8"
48 cm
16 "
41 cm
1 3/8"
3. 5 cm
PM-9/
PM-9G
16 11/16"
41 cm
AM-50
SERIES
Gamewell-FCI
AM-50
SERIES
AM-50
SERIES
Gamewell-FCI
AM-50
SERIES
INI-VGX
12 A/H BATTERIES
Figure 5 INX Dimensions
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0541 Rev. M page 4 of 4
www.gamewell-fci.com
19 3/8"
48 cm
Similar pages