PULS does it again: practical, versatile and reliable like the SilverLine – yet small like no other. Data Sheet MiniLine (Dual Output) with DC ±12V / ±15V (36W) • Mounted and connected in record time, no tools required • World-wide approvals (UL, EN, CSA, CB Scheme) for industry and office/ home • Tiny: WxHxD = 45 x 75 x 91mm • Output voltage adjustable to DC ±12V (without jumper) or DC ±15V (with jumper) • 100-240V Wide Range Input • PULS Overload Design™ (high output overload capability) • NEC Class 2 Power Supply PULS GmbH, Arabellastrasse 15, 81925 Munich Tel. +49.(0)89.9278-244, Fax: +49.(0)89.9278-199 [email protected], http://www.puls-power.com Mini is more. ML30e106/040504 Technical Data ML30.106 S X Input s amp l C g prin X Output Input voltage AC100-240V (Wide Range), 47...63 Hz Admiss. limits: AC 85...264V (DC 85...375V) Output voltage Input current <0.65A (@ AC 100Vin, 36W Pout) <0.4A (@ AC 196Vin, 36W Pout) • preset External fusing not required, unit provides internal fuse (T3A15H, not accessible) Output current Transient immunity Transient resistance acc. to VDE 0160 / W2 (750V/ 1.3ms), over entire load range 0...2.8A (+12V) / 0...1.4A (-12V) 0...2.4A (+15V) / 0...1.4A (-15V) Rated total output power: 36W Voltage regulation stat. ±4% Vout dyn. ±2% Vout over all 0.1...2.8A (+12V) / 0.1...1.4A (-12V) 0.1...2.4A (+15V) / 0.1...1.4A (-15V) Rated total output power: 36W Hold-up time (see diagram below): >180ms @ AC 230V (+12V / 2A, -12V / 1A; +15V / 1,6A, -15V / 0,8A) >100ms @ AC 196V (+12V / 2A, -12V / 1A; +15V /1,6A, -15V / 0,8A) >18ms @ AC 100V (+12V / 2A, -12V / 1A; +15V /1,6A, -15V / 0,8A) • range Ripple/Noise 86% (AC 230V, 36W) (see also diagram below) typ. 6W (AC 230V, 36W) Losses MTBF (Reliability) <50mVPP (20MHz bandw., 50Ω measurem.) Overvoltage prot. (OVP) <50V X Efficiency, Reliability Efficiency DC ±12V (without jumper) DC ±15V (with jumper); ±15V ± 0.5% with symetric load and 36W (with jumper) Rated continuous loading (see output current above); depending on builtin orientation, Vin and Tamb (convection cooling); for details see derating diagram below Overload behaviour PULS Overload Design™: No switch-off at overload/short-circuit. Thus, you need no oversizing to start awkward loads. Protection Unit is protected against (also permanent) short-circuit, overload and open-circuit. Derating depending on built-in orientation; see diagram below Power back immunity max. ±20V Operating indicator Green LED (DC ON) 600.000 h acc. to Siemensnorm SN29500 (symetric load / 36W, AC 230V, Tamb = 40°C) Prior to shipment, every unit undergoes the following tests in order to isolate any defective units which might suffer an early failure: • Run-in / burn-in (Full load, Tamb = +60°C, on/off cycle) • Functional test (100 %) X Construction, Mechanics, Installation Robust plastic housing (US Patent No. D442, 923S), fine ventilation grid on three housing sides to keep out small parts (e.g. screws), IP20 X Environmental Data, EMC, Safety Dimensions and weight • WxHxD 45mm x 75mm x 91mm (+ DIN rail) Depth incl. terminals: 98 mm (+ DIN rail) 240 g • Weight Ambient temperature range (measured 25mm below unit) • storage/transport -25°C ... +85°C • operation -10°C ... +70°C (for derating see diagram below) Humidity max. 95% (without condensation) Electromagnetic emissions (EME) EN 61000-6-3 (includes EN 61000-6-4) Class B (EN 55011, EN 55022) Easy snap-on mounting onto the DIN-Rail (TS35/7,5 or TS35/15). Unit sits safely and firmly on the rail; no tools required even to remove Electromagnetic immunity (EMI) EN 61000-6-2 (includes EN 61000-6-1) Connection Safe low voltage.: Prot. class/degree: SELV (EN60950, VDE0100/T.410), PELV (EN50178) Class I (EN60950) / IP20 (EN60529) Mounting orientation , or (cf. ’Output’) Ventilation/Cooling Normal convection, no fan required • Free space for coolingrecom’d.: 25mm on sides with ventilation grid by Spring Clamp terminals; uniformly firm hold, vibration-resistant and maintenance-free. Connector size range • flexible cable • solid cable • Wire strip length The PSU complies with all major safety approvals for EU (EN 60 950, EN 60204-1, EN 50178), USA (UL 60950, E137006, UL508 LISTED, E198865), Canada (CAN/CSA-C22.2 No 60950 [CUR], CAN/CSA-C22.2 No. 14 [CUL]), CB Scheme (IEC 60950). 0.3-2.5mm2 (28-12 AWG) 0.3-4mm2 (28-12 AWG) Ferrules admissible 6mm (0.24in) recommended Design details – for your advantage: • All terminals are easy to reach as mounted on the front panel. • Input and output are strictly apart from each other (input below, output above) and so cannot be mixed up • Mounting and connection do not require any screwdriver → Easy, quick, durable and reliable installation X Diagrams ± 18 90 ± 12 ±9 ±12V/±15V @ 230VAC ±6 ±12V/±15V @ 100VAC ±3 ±0 ±0,0 Output power [W] 86 Wirkungsgrad [%] Output voltage Vout [V] 40 88 ± 15 84 82 100 VACin 120 VACin 230 VACin 80 78 76 500 A a 30 B 20 b Mounting 10 ±2,5 ±3,0 0,3 0,6 0,9 1,2 1,5 Output current Iout [A] 1,8 -10 0 10 20 30 40 50 Ambient temperature [°C] Pout=36W (12V/15V) 400 Pout=18W (12V/15V) 350 300 250 200 150 50 0 72 ±1,0 ±1,5 ±2,0 Output current Iout [A] 450 100 85-264 V ACin A-a A-a A-b 85-370 V DCin B-a B-a B-b 74 ±0,5 Hold-up time with ACin (at Vout = ±12V / ±15V, typ.) Derating of output power Efficiency (@ Vout = ±15V, typ.) Hold-up time [ms] Output characteristic Vout/Iout (@ Vout = ±12V / ±15V, min.) 60 70 0 90 125 160 195 Input voltage V ACin [V] 230 Product information (ML30e106), Stand: 4. May 2004. Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They are subject to change without prior notice. PULS GmbH, Arabellastraße 15, D-81925 München X Tel: +49.(0)89.9278-244, Fax: +49.(0)89.9278-199, E-Mail: [email protected] X www.puls-power.com