EPCOS B84143B0120R110 Emc filter Datasheet

EMC filters
3-line filters
for converters and power electronics
Rated current 8 to 200 A
Series/Type:
B84143B*R110
Date:
January 2006
 EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the
information contained therein without EPCOS’ prior express consent is prohibited.
3-line filters
B84143B*R110
for converters and power electronics
Power line filters for 3-phase systems
Rated voltage 520/300 V AC, 50/60 Hz
Rated current 8 to 200 A
Construction
■ 3-line filter
■ Metal case
■ Book size
Features
■
■
■
■
■
■
■
Very high insertion loss
Optimized leakage current
Space saving by optimized footprint
Litz wires on the load side reduce mounting time
Low weight
Degree of protection: IP 201)
Optimized for long motor cables and operation
under full load
■ Design complies with
EN 133200, UL 1283, CSA C22.2 No.8
■ UL and cUL approval pending
Applications
■ Frequency converters for motor drives, e.g.
elevators, pumps, traction systems, conveyor systems,
HVAC systems (heating, ventilation and air conditioning)
■ Wind farms
■ Power supplies
Terminals
■ Line side: Finger-safe terminal blocks
■ Load side: Litz wires
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current, rated temperature,
climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
1) To IEC 60529
Please read Cautions and warnings and
Important notes at the end of this document.
2
01/06
3-line filters
B84143B*R110
for converters and power electronics
Typical circuit diagrams
Filters for 8 and 16 A
LINE
LOAD
L1
L1’
L2
L2’
L3
L3’
SSB1526-A
Filters for 25 … 200 A
LINE
LOAD
L1
L1’
L2
L2’
L3
L3’
SSB1527-I
Please read Cautions and warnings and
Important notes at the end of this document.
3
01/06
3-line filters
B84143B*R110
for converters and power electronics
Technical data and measuring conditions
Rated voltage VR
520/300 V AC, 50/60 Hz
Rated current IR
Referred to 40 °C ambient temperature
Test voltage Vtest
1770 V DC, 2 s (line/line)
2700 V DC, 2 s (lines/case)
Overload capability (thermal)
1.5 · IR for 3 min per hour or
2.5 · IR for 30 s per hour
Leakage current Ileak
At 480 V AC, 50 Hz
Climatic category (IEC 60068-1)
25/100/21 (– 25 °C/+ 100 °C/21 days damp heat test)
Approvals
UL 1283 and CSA C22.2 No.8 pending
Characteristics and ordering codes
VR
AC
IR
V
A
520/300
Terminal cross section Ileak
Line side:
Load side:
terminal
litz
blocks
wires
mm2
mA
mm2
8
4
< 14
1.5
Rtyp
Approx.
weight
mΩ
kg
26
1.5
Ordering code
B84143B0008R110
16
4
2.5
< 14
13
1.5
B84143B0016R110
25
6
4
< 14
10
2.7
B84143B0025R110
36
6
6
< 14
6.5
3.2
B84143B0036R110
50
16
10
< 14
4.3
3.7
B84143B0050R110
66
25
16
< 14
2.7
4.3
B84143B0066R110
90
25
25
< 14
2.0
7.7
B84143B0090R110
120
50
35
< 14
1.4
8.3
B84143B0120R110
150
50
35
< 14
0.9
9.7
B84143B0150R110
< 14
0.5
13.5
B84143B0200R110
200
95
70 /
351)
1) PE litz wire
Please read Cautions and warnings and
Important notes at the end of this document.
4
01/06
3-line filters
B84143B*R110
for converters and power electronics
Dimensional drawings
B84143B0008R110, B84143B0016R110 (8 and 16 A)
50
300±10
200
1
0.5
31
15
Wire end ferrule
Litz wire markings
PE M6 x 24
230
215±0.5
6.5
Terminal blocks 4 mm 2
Tightening torque 0.6 ... 0.8 Nm
25±0.3
40
80
Litz wire
46
L1’
L1
L2’
L2
L3 Marking L3’
PE
PE
LINE LOAD
SSB2188-F-E
B84143B0025R110 (25 A)
60
250
400±10
L1
L2
Marking
L3
PE LINE LOAD
L1’
L2’
L3’
PE
56
6.5
280
265±0.5
35±0.3
Wire end ferrule
Litz wire markings
PE M6 x 24
Terminal blocks 4 mm 2
Tightening torque 0.6 ... 0.8 Nm
1
0.5
60
30
75
150
Litz wire
SSB2189-N-E
Please read Cautions and warnings and
Important notes at the end of this document.
5
01/06
3-line filters
B84143B*R110
for converters and power electronics
B84143B0036R110 (36 A)
60
250
400±10
1
0.5
60
30
Wire end ferrule
Litz wire markings
PE M6 x 24
280
265±0.5
6.5
L1
L2
Marking
L3
PE LINE LOAD
L1’
L2’
L3’
PE
56
Terminal blocks 6 mm 2
Tightening torque 1.5 ... 1.8 Nm
35±0.3
75
150
Litz wire
SSB2190-R-E
B84143B0050R110 (50 A)
60
300
500±10
PE M6 x 24
1
0.5
30
Wire end ferrule
Litz wire markings
L1
L2
Marking
L3
PE LINE LOAD
6.5
315±0.5
L1’
L2’
L3’
PE
56
330
Terminal blocks 16 mm 2
Tightening torque 2 ... 2.3 Nm
35±0.3
52
75
150
Litz wire
SSB2191-Z-E
Please read Cautions and warnings and
Important notes at the end of this document.
6
01/06
3-line filters
B84143B*R110
for converters and power electronics
B84143B0066R110 (66 A)
80
300
500±10
60
PE M10 x 39
Wire end ferrule
Litz wire markings
L1’
L2’
L3’
PE
76
55±0.3
L1
L2
Marking
L3
PE LINE LOAD
6.5
330
315±0.5
Terminal blocks 25 mm 2
Tightening torque 4 ... 4.5 Nm
1
0.5
75
52
30
150
Litz wire
SSB2192-8-E
B84143B0090R110 (90 A)
80
300
500±10
Wire end ferrule
1
0.5
30
100
52
200
Litz wire
60
PE M10 x 39
Litz wire markings
L1’
L2’
L3’
PE
76
L1
L2
Marking
L3
PE LINE LOAD
6.5
330
315±0.5
55±0.3
Terminal blocks 25 mm 2
Tightening torque 4 ... 4.5 Nm
SSB2193-G-E
Please read Cautions and warnings and
Important notes at the end of this document.
7
01/06
3-line filters
B84143B*R110
for converters and power electronics
B84143B0120R110, B84143B0150R110 (120 and 150 A)
90
500±10 Wire end ferrule
350
1
40
0.5
78
100
200
Litz wire
65
Litz wire markings
65±0.3
6.5
380
365±0.5
L1
L1’
L2 Marking L2’
L3
L3’
PE LINE LOAD PE
86
PE M10 x 39
Terminal
blocks 50 mm 2
Tightening
torque 6 ... 8 Nm
SSB2194-P-E
B84143B0200R110 (200 A)
110
400
500±10
Wire end ferrule
1
30
0.5
79
80
PE M10 x 39
PE litz wire 35 mm 2
430
415±0.5
L1
L2
Marking
L3
PE LINE LOAD
L1’
L2’
L3’
PE
85±0.3
6.5
Terminal
blocks 95 mm 2
Tightening
torque 15 ... 20 Nm
Litz wire markings
106
110
220
Litz wire
SSB2195-X-E
Please read Cautions and warnings and
Important notes at the end of this document.
8
01/06
3-line filters
B84143B*R110
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 8 and 16 A
α
Filters for 25 and 36 A
120
dB B84143B0008R110
B84143B0016R110
SSB1528-R
α
100
80
60
60
40
40
20
20
10 5
10 6
10 7
0 4
10
Hz 10 8
f
Filters for 50 A
SSB1530-3
10 6
120
dB B84143B0066R110
α
100
10 7
Hz 10 8
f
80
60
60
40
40
20
20
10 6
10 7
0 4
10
Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
9
SSB1531-B
100
80
10 5
10 5
Filters for 66 A
120
dB B84143B0050R110
0 4
10
SSB1529-Z
100
80
0 4
10
α
120
dB B84143B0025 ... B0036R110
01/06
10 5
10 6
10 7
Hz 10 8
f
3-line filters
B84143B*R110
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 90 and 120 A
Filters for 150 and 200 A
120
dB B84143B0090 ... B0120R110
α
SSB1532-J
α
100
120
dB B84143B0150R110
B84143B0200R110
100
80
80
60
60
40
40
20
20
0 4
10
10 5
10 6
10 7
0 4
10
Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
10
SSB1533-S
01/06
10 5
10 6
10 7
Hz 10 8
f
EMC filters
Cautions and warnings
Important information
Please read all safety and warning notes carefully before installing the EMC filter and putting it into
operation (see
). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appro­
priate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in low­
voltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warnings
■ It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
■
■
■
■
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Danger­
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed and
the last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen­
cies that may cause resonances etc. can lead to destruction of the filter housing.
EMC filters must be protected in the application against impermissible exceeding of the rated
currents by suitable overcurrent protective.
11
01/06
EMC filters
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As
a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in which
the malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of
suitable design of the customer application or other action taken by the customer (e.g.
installation of protective circuitry or redundancy) that no injury or damage is sustained by third
parties in the event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as “hazardous”). Useful information on this will be found in our
Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more
detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products.
Consequently, we cannot guarantee that all products named in this publication will always be
available.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap,
PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are
trademarks registered or pending in Europe and in other countries. Further information will be
found on the Internet at www.epcos.com/trademarks.
12
01/06