Fuji EDS11-130 Graphic program controller (2ch) Datasheet

GRAPHIC PROGRAM CONTROLLER (2CH)
DATA SHEET
PVH
This controller is a multi-function/high-performance program
controller developed on the basis of many years of delivery
records in the field of various industry machines used for
temperature control. It assures program control with high
accuracy, and is capable of using with many types of small
production equipment. Also, it provides PLC (Programmable
Logic Controller) link function for easy application to FA
system, and is ideally used as a component of realizing CIM
system.
FEATURES
1. Complete monitoring operation with full-graphic
display
• Two-channel operating condition can be monitored in
real time. The pattern graph is blackened out with
the lapse of time so the progress of operation can be
checked at a glance.
• The name of process being performed corresponding
to time signal can be displayed (up to 100 names can
be registered with 18 characters/process).
• The horizontal scale (step/time) of temperature pattern
display can be selected and displayed in actual pattern
format.
2. Program pattern (199 patterns (2700 steps, max)
setting function
This function is ideally suited for machines requiring a
large number of patters such as for small production
systems.
3. Adoption of memory card
• Simple and positive program control
Programs can be loaded by changing IC cards
registered with programs of various items, allowing
simple and positive control of program patterns of small
production of many different articles.
• Compact data-base system
Pattern data and PID parameters registered in formerly
used PVH can be saved in IC cards for easy initial
setting to newly purchased articles.
4. Application to control of carbonization furnace and
vacuum furnace
Control of 2-process value, such as temperature/vacuum
degree, temperature/pressure, temperature/humidity,
etc., can be controlled with a single unit. The adoption
of built-in CP (Carbon Potential) calculating function which
is indispensable for control of carbonization furnace,
contributes to cost down and space-saving.
5. Application to FA system
• This controller can be used for FA system when used
in combination with Fuji's FA components.
• Lines between components are integrated by network
(T-link communication), thereby providing system
expansion which allows the user to set up FA system
step by step, from PLC to group control of machines
and to factory FA system.
• RS422A/RS485 communication
SPECIFICATIONS
Size of front panel:
144 × 144 mm
Input:
Full multi-input (see section “Input”)
Control action: Auto-tuning PID operation (normal/reverse
selection possible)
Manual operation function
Program/fixed value control
Control output: • Relay contact output
(2 points)
• Voltage pulse output (To be set
according to
(for SSR drive)
code symbols)
• Current output



IC card function (option):
Used to save program parameters in IC
card
Display system: LCD full-dot graphic display, 320 × 240
dots (with back light)
Program setting unit:
Program memory number:
199 patterns, max.
Max. step number:
2700 steps
Number of steps in 1 pattern:
99 steps, max.
Program setting range:
Time; 0.0 to 999.9 min/step, setting
resolution 0.1 min
Setting range; 0 to 100% of input scale
Setting accuracy: Less than ± 0.5 of full scale
EDS11-130
Date
Dec. 20, 1998
PVH
Fast feed time function:
About 60 times the setting time
Time signal is OFF at fast feed with key
operation.
Operation display:
The states of following operations are
displayed on the front LCD panel.
Program run, program stop, program fast
run, program reset, program end, selected
program No., running step No., measured
value (PV), set value (SV), operation output
value (MV), operation output ON/OFF,
program operation pattern, process name,
time display
Input
(1) Analog input
Input signal, setting scale range:
Kind of input
Temperature
range [°F]
Code Temperature
range [°C]
Resistance
bulb
IEC Pub
751-1983
Pt 100
Pt 100
Pt 100
Pt 100
Pt 100
Pt 100
Pt 100
Pt 100
0
1
2
3
4
5
6
7
0.0 to
0.0 to
0.0 to
0.0 to
–50.0 to
–100.0 to
–199.9 to
–199.9 to
150.0
32.0 to 302.0
300.0
32.0 to 572.0
500.0
32.0 to 932.0
600.0
32.0 to 1112
100.0 –58.0 to 212.0
200.0 –148.0 to 392.0
600.0 –328.0 to 1112
850.0 –328.0 to 1562
Resistance
bulb
JIS C
1604-1981
JPt 100
JPt 100
JPt 100
JPt 100
JPt 100
JPt 100
JPt 100
16
17
18
19
20
21
22
0.0 to
0.0 to
0.0 to
0.0 to
–50.0 to
–100.0 to
–199.9 to
150.0
32.0 to 302.0
300.0
32.0 to 572.0
500.0
32.0 to 932.0
600.0
32.0 to 1112
100.0 –58.0 to 212.0
200.0 –148.0 to 392.0
600.0 –328.0 to 1112
Thermocouple J
J
K
K
K
R
B
T
T
E
E
S
N
U
WRe5-26
PL-II
DC voltage
1 to 5V DC
0 to 5V DC
0 to 10V DC
0 to 1V DC
0 to 100mV DC
0 to 10mV DC
DC current
4 to 20mA DC
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
0.0 to 400.0
0.0 to 800.0
0.0 to 400.0
0.0 to 800.0
0.0 to1200.0
0.0 to1600.0
0.0 to1800.0
–199.9 to 200.0
–150.0 to 400.0
0.0 to 800.0
–199.9 to 800.0
0.0 to1600.0
0.0 to1300.0
–199.9 to 400.0
0.0 to2300.0
0.0 to1300.0
CP input (CH2 only)
80
81
82
83
64
65
66
67
68
69
64*
32.0 to 752.0
32.0 to 1472
32.0 to 752.0
32.0 to 1472
32.0 to 2192
32.0 to 2912
32.0 to 3272
–328.0 to 392.0
–238.0 to 752.0
32.0 to 1472
–328.0 to 1472
32.0 to 2912
32.0 to 2372
–328.0 to 752.0
32.0 to 4172
32.0 to 2372
Scale settable within –999 to
+9999
( )
* To apply the current input, connect 250Ω (option) between
terminal I1C and I1V to convert
it into the voltage of 1 to 5V.
0.00
0.000
0.00
0.000
to
to
to
to
1.50
1.500
2.00
2.000
cp
cp
cp
cp
Note: *Accuracy below –200°C is not guaranteed.
*In the range of R thermocouple 0 to 500°C, accuracy is ± 1% FS.
*In the range of B thermocouple 0 to 400°C, accuracy is ± 5% FS.
*In the range of resistance bulb input –199.9 to 850°C, UNDER is
not displayed even at 0Ω input.
*When B wire is broken at resistance bulb input, UNDER or OVER is
displayed.
2
Input resistance and allowable signal source resistance
Input signal
Input resistance
Allowable signal
source resistance
Thermocouple
1MΩ or more
250Ω or less
Resistance bulb —
Less than 10Ω
per wire
Voltage input
4 to 20mA
External resistor
250Ω
—
Gerconia direct
input
250MΩ or more
20kΩ or less
* Sampling cycle: 0.1sec
(2) Digital input signal
Signal:
No-voltage contact (contact capacity; 12V
DC, 2mA DC or more)
Input points: 16 points
•Start/stop command
•Fast or step run command
•Pattern transfer command
•Monitor panel A/B select command
•Program reset command
•Gerconia sensor impedance check command
•Pattern external select ENT
•Pattern external select 100
(4 points)
(as speci•Pattern external select 101 fied)
(4 points)
•Pattern external select 102
(4 points)



Output
(1) Control output
Control output:
Normal/reverse PID action
Proportional band(P); 0.0 to 999.9%
(2-position action
at P=0)
Integral time(I);
0 to 3200 sec
(integration cut at
I=0)
Derivative time(D);
0.0 to 900.0 sec
(derivation cut at
D=0)
(PID is stored in memory up to 9 kinds;
1 kind of PID can be set on each step of
program pattern).
Time proportional cycle:
1 to 120 sec (setting resolution, 1sec)
(setting is not required at current input)
Relay contact output:
220V AC/30V DC (resistive load)
1c contact
Electric life, 100,000 operations or more
Minimum ON/OFF current, 0.1A (24V DC)
Voltage pulse:
ON; 10 to 18V DC
OFF; 0.5V DC or less
Max. current; about 20mA
Current output:
4 to 20mA DC (allowable load, 600Ω or
less
Accuracy, ± 1.0%FS
Output limiter:
High/low limiter
Setting range, –5 to 105%
Limiter high/low limit set value (pair) is
stored in memory up to 9 kinds; 1 kind
can e set at each step of program pattern.
Control cycle: 0.1sec
(2) Auxiliary analog output (option)
Output points:
2 points
Output data: Any of measured value/set value/
operation value can be set on 2 points
individually.
Output accuracy:
Kinds of output: 1 to 5V DC, 0
DC 1 to 5V
to 5V DC, 0 to 10V DC
DC 0 to 5V
Any one can be set on 2 points
DC 0 to 10V individually by Dip SW (set to 1


 to 5V prior to delivery from factory).
Scaling function:
Provided
(3) Digital output
Status signal (7 points)
•Open-collector output
•Output rating, 24V DC 10mA or less
•ELT ; CPU stop status
•IMP ; Impedance check error status
•RST ; Reset status
•RUN ; Program operation status
•HLD ; Program stop status
•WAIT ; Guarantee soak standby status
•END ; program end status
Time signal (10 points)
•Open-collector output
•Output rating, 24V DC 10mA or less
Setting is made at each step.
Alarm:
4 points
High/low limit alarm, 2 points
High or low limit alarm, 2 points
Setting range, 0 to 100FS
•High/low limit alarm setting can be
made individually up to 9 groups; 1
group can be set at each step.
•High or low limit alarm setting can be
made only on 1 group in common with
high/low limit.
•Besides the above, setting of guarantee soak, maximum standby time alarm,
and main body fault alarm are possible.
Indication function
(1) Set value (SV), measured value (PV) indication
Display system:
LCD display
Indication range:
0 to 100% FS (SV), –5 to 105% FS (PV)
Measured value indication accuracy:
± 0.2% FS ± 1 digit (standard condition)
± 1.0% FS ± 1 digit (CP value indication)
Cold junction temperature compensation
error, ± 1°C
(thermocouple input)
(2) Program No. indication
Display system: LCD display (numeric value display)
Indication range: 1 to 199
(3) Program progress indication
Display system:
LCD graphic display (numeric display and
graphic display)
Indication range:
Step No. 1 to 99, time remained or time
lapse in step, or program progress total
time
(4) Digital input/output and action display
Display system:
LCD display
Display item: Time signal (TS1 to TS10)
Operation status display (reset, start,
stop, fast run, end, control output)
Alarm (1 to 4) output status
IC card battery life alarm display
Other functions:
Cycle operation:
Operation with repeated display of the
same program pattern
Link operation:
Operation with linkage of program pattern
Optional functions:
Communication function:
T-link, RS422A, RS485
Auxiliary analog output:
Refer to "Output" section
General items:
RAS function: With watch-dog timer
Power failure protection:
Momentary power OFF of more than
20ms is regarded as power failure;
automatic start after recovery of power.
Battery backup:
Lithium battery is used.
Battery life; more than 5 years at 0 to 40°C
of ambient temperature at power OFF
Optional accessories
•Comment loader
Comment loader is a software used to register process
names and comments (full size characters) in PVH IC
card for displaying current process names,
corresponding to time signal, on PVH.
Specifications: Japanese full size character;
18 characters/process
Required device (to be prepared by user)
Personal computer; Model FMR (Fujitsu) or PC9801
(NEC) and MS-DOS (Ver. 3.10 or above)
IC card reader/writer; Model MCRJ03 (Towa Electron
Co.)
Towa Electron: FAX 045-471-0071
TEL 045-471-0066
045+471-0061
3
PVH
CODE SYMBOLS
Operating condition:
Power supply:
100V AC
+10%
–15%
200V AC
+10%
–15%



(50/60Hz) (as specified
in code
(50/60Hz) symbols)
Power consumption:
About 30VA
Ambient temperature:
0 to 50°C (storage temperature –10 to
+60°C)
Ambient humidity: 90%RH or less
Mounting angle:
1 2 3 4 5 6 7 8
P VH
9 10 11 12 13
Description
1
Control output 1
Relay contact output
SSR/SSC drive output
4 to 20mA DC output
1
2
3
Control output 2
Relay contact output
SSR/SSC drive output
4 to 20mA DC output
1
2
3
2ch input
Thermocouple input
(2-loop temperature control)
O2 probe connection
(temperature compensation;
1ch temperature input)
O2 probe connection
(temperature compensation;
2ch temperature input)
CP converter connection (1 to 5V DC)
1
∠α=90 to 0°
α
Structure
Enclosure:
Case; steel (dust-proof)
Front door; ABS resin (with packing)
External terminal, cover; ABS resin
Dimensions(HxWxD): 144x144x237mm
Structure:
Embedded type
Mass:
Approx. 3.1kg
Finish color: Case; N1.5 (black)
Front door; N1.5 (black) (colored mold)
2
3
4
Power supply
100V AC 50/60Hz
200V AC 50/60Hz
0
1
Auxiliary analog output
Without
With (Note)
0
1
Transmission function
Without
RS422A
RS485
T-link transmission
Y
R
S
T
DI select function
Fast run + BCD code selection
Step run + BCD code selection
Fast run + pulse input selection
Step run + pulse input selection
Y
A
B
C
IC card
Without
With
0
1
J
E
Display, instruction manual
Japanese
English
(Note) 1-5V DC prior to delivery from factory
4
Process name input method:
1. Process name input with personal computer
2. Saving of process name data in IC card
MS-DOS system
IC card reader/writer (MCRJ03),
Towa Electron Co.
IC
Comment loader
software
IC card (128KB)
Personal computer
(PC9801) or FMR)
Graphic program controller
(PVH)
IC
IC card registered with process
name
3. Loading of process name data from
IC card to PVH
OUTLINE DIAGRAM (Unit:mm)
2≤t≤30
;
;
Panel
174
136.4
Mounting bracket
136.4
215
237
D-SUB connector (15 pins)
;
;
144
26
Screw terminal (M3.5)
Panel cutout size
+1.5
200 or more
200 or more
137
+1.5
–0
137 –0
5
PVH
External connection diagram
External pattern select input (BCD code)
(1's code)
(10°)
D-SUB
l5-pin connector
23
22
21
20
External pattern select input (pulse input)
10's code
(101)
D-SUB 15-pin connector
23
8
15
7
14
6
13
5
12
4
11
3
10
2
9
1
8
15
7
14
6
13
5
12
4
11
3
10
2
9
1
22
21
20
20
ENT
ENT
11A
*2
RCJ
RCJ
A
*1
11B
TC
RCJ
11C
TC +
–
12B
+
–
21+
250Ω
RTD
B
11V
+
1ch input signal PV
mV
–
–
V
+
–
4 to 20mA
+
250Ω
12C
AO1
(Gerconia direct
2ch input signal PV input or 1 to 5V
DC)
RS422
transmission
(T-link
communication
or RS485
communication)
+
O1
21–
AG
SHLD
(SG)
RDA
SDA
(T1)
RDB
SDB
(T2)
AC
AC
SD
T1
T2
Control output 1 (4 to 20mA DC output,
SSR/SSC drive output)
–
+ RS422 com–
munication
+
Auxiliary analog output 1
–
~
100 or 200V AC
Time signal output : T01 to T10
O1C
+
Auxiliary analog output 2
–
AO2
Control output 2 (4 to +
20mA DC, SSR/SSC
drive output)
O1A
O2
O1B
External command input
(start/stop)
T02
T03
AL2
PRO
AL3
output
Status output
CHG
–
IMP
+
–
FLT
+
–
+
–
+
–
+
–
AL4
RST
–
END
CHK
+
PCD
T04
+
AL1
STEP
T05
T06
RST
T07
RUN
T08
HLD
T09
WAIT
T10
PCD
G
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
PCD
PCD
Load
* 1) Resistor (250Ω) is used for 4 to 20mA DC input.
* 2) Equipped with cold junction compensation sensor.
–
O2A
ALC
R/H
•Reset/HOLD command
•Fast run or step run command
•Pattern transfer command
•Monitor panel A/B select command
•Gerconia sensor impedance
check command
Control output 1 (contact output) Alarm
O2B
AG
–
T01
O2C
–
+
DC 24V
External power supply
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
Head Office
6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan
http://www.fesys.co.jp/eng
Sales Div.
International Sales Dept.
No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan
Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187
http: //www.fic-net.jp/eng