Lineage Power CAR1248FPBYO-1A 1200 watt 48v front end power supply Datasheet

CAR1248FP Series
1200 Watt 48V Front End Power Supply
Features:
∎ 1200 Watts in 1U
∎ Ultra High Power Density of 19W/in3
∎Active Current Sharing (Single Wire)
∎Remote on/off, Remote Sense, Voltage Program &
Current Share Control Circuits
∎Constant Current
∎Current, Voltage, AC OK, DC OK & Temperature OK
∎ Microprocessor based design allows for I2C communication
∎ Optional Universal / 5-Bay 19” Rack Delivers 6kW of Total Power
∎ International Safety Approvals - UL, CSA, CE Mark (LVD), TUV
FEATURES
BENEFITS
KEY MARKETS & APPLICATIONS
High Power Density 19W/in3
System Scalability up to 6000W
1U x 2U High Form Factor
Load Sharing & Fault Tolerant
5VSB Standby Voltage
I 2C Digital Control & Monitoring
Leaves plenty of room for your applications
Allows flexibility with minimum investment
Minimize space required for power needs
Excellent reliability in N+1 operation
Voltage for external housekeeping and monitoring circuitry
Ideal for monitoring, housekeeping and control
∎ Distributed Power ∎ Blade Servers
∎ Mid-end servers ∎ Network Equipment
∎Network Attached Storage
∎ Automatic Test Equipment
∎ Storage Area Networks
SPECIFICATIONS
1200 Watt +48V Front End Power Supply
Input Voltage Range
Input Current Maximum
Inrush Current
Input Protection
Power Factor
Efficiency
Output Power
Output Voltage Range
Output Current
Voltage Programming
Standby Bias Voltage
Voltage Regulation
Ouput Ripple & Noise
Transient Response
Switching Frequency
Hold-Up Time
Remote On/Off
Current Limit Protection
Short Circuit Protection
Over Voltage Protection
Operating Temperature
Over Temperature Protection
EMI
LED Indicators
Analog Status & Control
85-264 VAC, 47-63 Hz
12.75A @ 100VAC, 7.9A @ 180 VAC, full load
40A max. cold start (per ETS 300 132-1 and bellcore specifications)
Dual Fused (Line & Neutral) 20 Amp / 250 VAC Type 3AB Axial
0.99 typical complies with IEC555, EN60555-2, EN61000-3-2
91% typical at 230 VAC Full Load Operation, 85% Typical @ 90 VAC Full Load Operation
1200W at High Line Operation (230 VAC), Derate to 1000 W at Low Line Operation (90 VAC)
+48 VDC (±10%)
25A @ +48 VDC for High Line Operation (230 VAC), reduced to 20.8A at Low Line Operation (90VAC)
Vout = 43.2V + 3.3x (Vprog - 0.364)V where 0.364 < Vprog < 3.27V
5VSB@500mA, reference to +48VDC Return
±2% of Vnom for any combination of line, load and temperature
ETS300 132-2, 32dBnrc. Bandwidth: 25Hz - 20kHz. 2mVrms pk-pk with 0.1µF ceramic and 10µF electrolytics caps
5% max deviation Recovery time 300µs @ 50% load step and di/dt < 1A/µs
200kHz (input) / 400kHz (output)
20ms at 1KW (typical) @ 90VAC
ON if >3V or open; OFF if <1V (max. sink 1mA) Open collector type
110-130% of Iout Nominal
Self protected with auto recovery
+60 VDC max, latched. Reset condition by recycling AC Input or toggling remote on/off
-10°C to +70°C. power derating above 55°C at 2.5% per °C
Non latching; protection active at 110°C internal temperature, restart at 95°C (typical)
FCC-B & EN55022-B with specified filter or at rack level, GR-1089-CORE
Green = AC OK & DC OK, Red = Fault
Voltage Programming (V Prog), Load sharing (I Share), Remote ON/OFF, Current Monitor (I Monitor), Over temperature (Temp Warning), Fault, PS Present, Module Enable
I 2C Option, see detailed specification for details
IEC68-2-27, MIL-STD-810E, Telcordia GR-63-CORE
11.02 x 3.44 x 1.65” / 284.5 x 87.4 x 41.9mm
2.8 lbs
IEC 950 per EN60950, UL60950, CSA 22.2-950, CE Mark (LVD), TUV
I 2C Signals, Bezel
Digital Status & Control
Shock & Vibration
Dimensions
Weight
Safety Approvals
Options
rev 100506
www.lineagepower.com/oem
Lineage Power
Lineage Power
Lineage Power (China)
3000 Skyline Dr.
Mesquite, TX 75149 Phone: (972) 284-2000
2841 Dow Avenue
Tustin, CA 92780 USA Phone: (714) 544-6665
1353 Chenqiao Road, Shanghai Sengpu Industrial Park
Shanghai, 201401 China
Phone: 021 6710 8910
CAR1248FP Series
1200 Watt 48V Front End Power Supply
OUTLINE DRAWING
PART NUMBER DEFINITION GUIDE
CAR 12 48 F P x xx -1A
Series
12=1200W
Output Current
48=48V
Output Voltage
Rev.
Blank=Non-compliant
YO=5 of 6 Compliant
ZO=6 of 6 Compliant
RoHS
B=Bezel Option
Blank=None
Options
F=Front End
Type
P=Positive
Examples:
Polarity
CAR1248FPZO-1A
1200W/48V Front End, 6 of 6 RoHS
CAR1248FPBYO-1A
1200W/48V Front End, Bezel, 5 of 6 RoHS
CAR1248FPB-1A
1200W/48V Front End, Bezel
PIN OUT INFORMATION
A1
VSB 5V
B4
PS Present
D1
V Prog
P4
Vout
A2
VSB 5V Return
B5
Serial Data Line
D2
OVP Test Point
P5
Vout Return
A3
Signal RTN
B6
Serial Data Clock
D3
Remote On/Off
A4
Write Protect
C1
I Share
D4
DC OK
A5
Remote Sense (+)
C2
N/C
D5
AC OK
A6
Remote Sense (-)
C3
Temp Warning
D6
Interrupt
B1
Fault
C4
I2C Address (A0)
P1
Line
B2
I Monitor
C5
I2C Address (A1)
P2
Neutral
B3
Module Enable
C6
I2C Address (A2)
P3
Chassis
D1 D2 D3 D4 D5 D6
P1
P2
P3
C1 C2 C3 C4 C5 C6
B1 B2 B3 B4 B5 B6
P4
A1 A2 A3 A4 A5 A6
rev 100506
P5
Connector is FCI / Berg
Part # 51939-070
Mates with FCI / Berg
Part # 51915-050
www.lineagepower.com/oem
Lineage Power
Lineage Power
Lineage Power (China)
3000 Skyline Dr.
Mesquite, TX 75149 Phone: (972) 284-2000
2841 Dow Avenue
Tustin, CA 92780 USA Phone: (714) 544-6665
1353 Chenqiao Road, Shanghai Sengpu Industrial Park
Shanghai, 201401 China
Phone: 021 6710 8910
Similar pages