Mean Well LRS-150-48 150w single output switching power supply Datasheet

150W Single Output Switching Power Supply
LRS-150
series
Bauar t gepruft
Sicherheit
egel ma ge
od
o s
be wac
g
www. tuv.com
ID 2000000000
■ Features
AC input range selectable by switch
Withstand 300VAC surge input for 5 second
No load power consumption<0.5W
Miniature size and 1U low profile
High operating temperature up to 70℃
Protections: Short circuit / Overload / Over voltage /
■ Applications
Industrial automation machinery
Industrial control system
Mechanical and electrical equipment
Electronic instruments, equipments or
apparatus
Household appliances
Over temperature
Cooling by free air convection
Compliance to IEC/EN 60335-1(PD3) and
IEC/EN61558-1, 2-16 for household appliances
Operating altitude up to 5000 meters
Withstand 5G vibration test
High efficiency, long life and high reliability
LED indicator for power on
100% full load burn-in test
3 years warranty
■ Description
LRS-150 series is a 150W single-output enclosed type power supply with 30mm of low profile design.
Adopting the input of 115VAC or 230VAC(selectable by switch), the entire series provides an output voltage
line of 12V, 15V, 24V, 36V and 48V.
In addition to the high efficiency up to 90%, the design of metallic mesh case enhances the heat dissipation
of LRS-150 that the whole series operates from -30℃ through 70℃ under air convection without a fan.
Delivering an extremely low no load power consumption (less than 0.5W), it allows the end system to
easily meet the worldwide energy requirement. LRS-150 has the complete protection functions and 5G antivibration capability; it is complied with the international safety regulations such as TUV EN60950-1,
EN60335-1,EN61558-1/-2-16, UL60950-1 and GB4943. LRS-150 series serves as a high price-toperformance power supply solution for various industrial applications.
■ Model Encoding
LRS - 150 - 12
Output voltage
Output wattage
Series name
File Name:LRS-150-SPEC 2015-12-31
150W Single Output Switching Power Supply
LRS-150
series
SPECIFICATION
MODEL
OUTPUT
INPUT
LRS-150-12
LRS-150-15
LRS-150-24
LRS-150-36
LRS-150-48
DC VOLTAGE
12V
15V
24V
36V
48V
RATED CURRENT
12.5A
10A
6.5A
4.3A
3.3A
CURRENT RANGE
0 ~ 12.5A
0 ~ 10A
0 ~ 6.5A
0 ~ 4.3A
0 ~ 3.3A
RATED POWER
150W
150W
156W
154.8W
158.4W
RIPPLE & NOISE (max.) Note.2 150mVp-p
150mVp-p
200mVp-p
200mVp-p
200mVp-p
VOLTAGE ADJ. RANGE
13.5 ~ 18V
21.6 ~ 28.8V
32.4 ~ 39.6V
43.2 ~ 52.8V
VOLTAGE TOLERANCE Note.3 ±1.0%
±1.0%
±1.0%
±1.0%
±1.0%
LINE REGULATION Note.4 ±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
LOAD REGULATION Note.5 ±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
SETUP, RISE TIME
500ms, 30ms/230VAC
HOLD UP TIME (Typ.)
40ms/230VAC
VOLTAGE RANGE
85 ~ 132VAC / 170 ~ 264VAC by switch
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
87.5%
AC CURRENT (Typ.)
2.8A/115VAC
INRUSH CURRENT (Typ.)
COLD STAR 60A/230VAC
LEAKAGE CURRENT
<0.75mA / 240VAC
OVER LOAD
PROTECTION
10.2 ~ 13.8V
OVER VOLTAGE
500ms,30ms/115VAC at full load
35ms/115VAC at full load
88.5%
240 ~ 370VDC(switch on 230VAC)
89%
89%
90%
1.6A/230VAC
110 ~ 140% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
13.8 ~ 16.2V
18.75 ~ 21.75V
28.8 ~ 33.6V
41.4 ~ 48.6V
55.2 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE
Shut down o/p voltage, re-power on to recover
WORKING TEMP.
-30 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT
±0.03%/℃ (0 ~ 50℃)
VIBRATION
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL60950-1, TUV EN60950-1, EN60335-1, EN61558-1 /- 2 - 16 ,CCC GB4943 approved
I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:1.25KVAC
SAFETY & WITHSTAND VOLTAGE
ISOLATION
RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC
(Note 7) EMC EMISSION
Compliance to EN55022 (CISPR22), GB9254 Class B, EN55014, EN61000-3-2,Class A(24~48≤80% Load 12,15≤75% Load),EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
601K hrs min.
OTHERS DIMENSION
PACKING
NOTE
MIL-HDBK-217F (25℃)
159*97*30mm (L*W*H)
0.48Kg ; 30pcs/15.4Kg/0.75CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Line regulation is measured from low line to high line at rated load.
5. Load regulation is measured from 0% to 100% rated load.
6. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up
time.
7. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power
supplies.” (as available on http://www.meanwell.com)
8. The ambient temperature derating of 5℃/1000m is needed for operating altitude greater than 2000m (6500ft).
File Name:LRS-150-SPEC 2015-12-31
LRS-150
150W Single Output Switching Power Supply
series
Block Diagram
fosc : 65KHz
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
FG
RECTIFIERS
&
FILTER
POWER
SWITCHING
DETECTION
CIRCUIT
O.L.P.
O.T.P.
+V
-V
CONTROL
O.V.P.
Derating Curve
Static Characteristics
230VAC
100
100
90
75
70
50
LOAD (%)
LOAD (%)
60
40
20
-30 -25
170 ~ 264VAC
85 ~ 132VAC
80
100VAC
Input only
60
50
40
0
10
20
30
40
50
AMBIENT TEMPERATURE (℃)
60
70 (HORIZONTAL)
85
170
100
200
110
220
120
240
130
260
132
264
INPUT VOLTAGE (VAC) 60Hz
File Name:LRS-150-SPEC 2015-12-31
LRS-150
150W Single Output Switching Power Supply
Mechanical Specification
4.5
Case No.241A
series
Unit:mm
3.
5
152.5
ψ
1
9.5
2
=3
85
.0
4
3L
M
2-
8
5
97
3
6
3.5
32
7
6.5
LED
SVR1
78
24
159
6.5
150
Terminal Pin No. Assignment
3.
ψ
117
30
3-
M3
L=
14.5
6
3.5
15
26
18
5
22
Pin No.
1
2
3
Assignment
AC/L
AC/N
FG
Pin No.
4,5
6,7
Assignment
DC OUTPUT -V
DC OUTPUT +V
5
Installation Manual
Please refer to : http://www.meanwell.com/webnet/search/InstallationSearch.html
File Name:LRS-150-SPEC 2015-12-31
Similar pages