Panasonic FP0-E16YTA Programmable controller Datasheet

FPS (Sigma) Series
Programmable Controllers
09/2008
FPS (Sigma)
The next generation compact PLC
Highlights
State-of-the-art PLC technology in the most compact size plus the ability to communicate via all important modern media
characterize the FPS (Sigma). With its two 100kHz pulse outputs, four high speed counters that function at up to 50kHz for
positioning applications, a programming memory capable of storing 32,000 steps, a real-time clock, and communication interfaces
for RS232C and RS485, FPS (Sigma) is one of the most flexible PLCs on the market. Remarkably, it is also one of the smallest!
Communication
Four quick and easy snap-on cassettes are available to add
different serial ports to the FPS (Sigma). All ports are capable of
communicating at speeds of up to 115.2kbps.
1-channel RS232C type
2-channel RS232C type
1-channel RS485 type
1-channel RS232C + 1-channel RS485 type
Positioning
In addition to a host of handy Panasonic functions, the FPS (Sigma)
also offers circular and linear interpolation. Circular interpolation can
be used for applications that apply glue, linear interpolation for pick &
place applications, for example. By combining the FPS (Sigma) with
servo motors, you can perform real 2-axis motion control.
Temperature control
Minas A4 Servo Drives
FPS (Sigma)
With the thermocouple input units and our accurate unique PID
and IPD algorithms, temperature can be controlled more easily and
accurately than ever.
Fast PID but
it overshoots
No overshoots
but slow
Other highlights
High
expansion capability with up to 384 I/Os
Short circuit protected transistor outputs
Fastest
processing time, 0.32µsec/basic command
Built-in
analog volume with two points
Compact
design [30 x 90 x 60mm (WxHxD)]
Backup battery
Large data memory of up to 2MByte
2
09/2008
FPS (Sigma) example
fast and no overshoot
FPS (Sigma) CPUs
Outstanding performance in a compact design
FPS (Sigma) – Transistor output type
28 points
Input
Output (PNP)
16 points
12 points
FPS (Sigma)
Relay output type
32 points
24 points
Input
Output (NPN)
16 points
16 points
Input
16 points
Output
8 points
Connector type
Connector type
Terminal type
FPG-C28P2H-A
FPG-C32T2H-A
FPG-C24R2H-A
FPS (Sigma) – Transistor output type with thermistor input
FPS (Sigma) –
Relay output type
with thermistor input
Temperature
control
80
70
60
50
40
30
10
0
28 points
Input
16 points
Output
12 points
32 points
Input
16 points
24 points
Output
16 points
Input
16 points
Output
8 points
2 Thermistor inputs
2 Thermistor inputs
2 Thermistor inputs
FPG-C28P2HTM
FPG-C32T2HTM
FPG-C24R2HTM
High expansion capability
FPS (Sigma) can use the expansion units of the FP0 on the right-hand side.
New FPS (Sigma) units can be added to the left-hand side.
Max. 4 expansion units
each 64 I/Os = 256 I/Os
…up to
384 I/O
!
CPU
max. 32 I/O s
Parallel
expansion
BUS
09/2008
Max. 3 expansion units
each 32 I/O s = 96 I/Os
Serial
expansion
BUS
3
FPS (Sigma) expansion units – left side
Wide variety of expansion units
FPS (Sigma)
I/O expansion unit
FPS (Sigma)
I/O expansion unit
FPS (Sigma)
Memory expansion unit
64 points
Input
Output (PNP)
32 points
32 points
MIL connector type
FPG-XY64D2P-A
64 points
Input
Output (NPN)
32 points
32 points
MIL connector type
FPG-XY64D2T-A
Memory: 256k words
FPG-EM1
FPG-EM1
FPS (Sigma) positioning expansion units RTEX
Real-time Ethernet system for Minas A4N servo drives
2-axis
4-axis
8-axis
FPG-PN2AN
FPG-PN4AN
FPG-PN8AN
FPS (Sigma) positioning expansion units
4
1-axis
1-axis
2-axis
2-axis
Transistor output
FPG-PP11
Line driver output
FPG-PP12
Transistor output
FPG-PP21
Line driver output
FPG-PP22
09/2008
FPS (Sigma) expansion units – left side
Wide variety of expansion units
FPS (Sigma)
PROFIBUS expansion unit
FPS (Sigma)
CANopen expansion unit
FPS (Sigma)
DeviceNet expansion unit
FPS (Sigma)
S-Link expansion unit
PROFIBUS Master
CANopen Master
DeviceNet Master
S-Link Master
FPG-DPV1-M
FPG-CAN-M
FPG-DEV-M
FPG-SL
Network plug-in modules for
FPS (Sigma) FNS unit
FPS (Sigma)
FNS (Flexible Network Slave) unit
Flexible Network Slave
PROFIBUS
Plug-in module
AFPN-AB6200
FPG-FNS
DeviceNet
Plug-in module
AFPN-AB6201
FPS (Sigma)
CC-Link slave expansion unit
CC-Link Slave
CANopen
Plug-in module
AFPN-AB6218
FPG-CCLS
FP memory loader
Communication cassettes
• Read or write
programs from or
into a PLC
• Personal computer is
not required
• Applicable with FP0,
FPS (Sigma), FP-X ,
FP2 and FP2SH
1-channel RS232C type
2-channel RS232C type
1-channel RS485 type
FPG-COM1
5-wire
FPG-COM2
3-wire
FPG-COM3
2-wire
1-channel RS232C type
+ 1-channel RS485 type
FPG-COM4
2-wire
09/2008
AFP8670
Data clear type
AFP8671
Data hold type
5
FPS (Sigma) expansion units – right side
Wide variety of expansion units
A maximum of 3 FP0 expansion units can be added to the FPS (Sigma) CPU unit.
Digital I/O units
Relay output type
8 points
Input Output
4 points 4 points
FP0-E8RSA
Input only type
16 points
Input Output
8 points 8 points
FP0-E16RSA
32 points
Input Output
16 points16 points
FP0-E32RS
8 points
Input
8 points
FP0-E8XA
Transistor output type
16 points
Input
16 points
FP0-E16XA
Option:
8 points
Output
8 points
FP0-E8YPA (PNP)
FP0-E8YTA (NPN)
16 points
16 points
32 points
Input Output
Output
Input Output
8 points 8 points
16 points
16 points16 points
FP0-E16PA (PNP) FP0-E16YPA (PNP) FP0-E32PA (PNP)
FP0-E16TA (NPN) FP0-E16YTA (NPN) FP0-E32TA (NPN)
Output 8 points
FP0-E8YRSA
Analog I/O units
Temperature control units
3 points
Input Output
2 points 1 point
4 points
Output
4 points
4 points
Output
4 points
8 points
Input
8 points
4 points
Input
4 points
8 points
Input
8 points
6 points
Input
6 points
FP0-A21A
FP0-A04I
FP0-A04V
FP0-A80A
FP0-TC4
FP0-TC8
FP0-RTD6
–
–
–
–
± 10V, ± 100mV
0–5V, 0–20mA
• K, J, T, R type thermocouples can be used
• Input (12bit):
±10V, 0–5V,
0–20mA
• Output (12bit):
±10V, 0–20mA
4–20mA
• Resolution: 0.1°C
• Accuracy: 0.8°C (R type: 3°C)
• Temperature range: -100 to 1500°C
±10V
AC power supply
Input
85 to 265VAC
Output
24V DC/0,7A
Terminal type
FP0PSA2
6
• P
t100, Pt1000,
Ni1000
• T
emperature range:
-200 to 500°C
Networking units
Input
85 to 265V AC
Output
24V DC/2,1A
MEWNET-F
FP0-IOL
Terminal type
FPPS24050ED
(MEWNET-F Slave)
09/2008
PROFIBUS
FP0-DPS2
(DP Slave) or
Remote I/O
Ethernet
FPWEB2
(Web-Server unit)
FPS (Sigma)
Optimized communication function
Four types of communication
cassettes enable:
Efficient connection to serial
devices.
Transmission speeds of up to
115.2kbits/s.
Long transmission distance of
up to 1200m.
In addition, the green screw
terminal is removable for easy
wiring.
1-channel RS232C type FPG-COM1
2-channel RS232C type FPG-COM2
1-channel RS485 type FPG-COM3
1-channel RS232C + 1-channel RS485 type FPG-COM4
With the RS232C type communications cassette:
Image
processing device
FPS
Efficient connection with other control devices helps to save space!
Enables connection to devices with RS232C interface, such as a programmable
display panel, image processing device and other devices.
When used as a tool port, up to 3 external devices can be connected.
A 2-channel type communication cassette is used.
GT
touch terminal
RS232C
RS232C
With the RS485 type communication cassette:
More links than you imagined a compact PLC could achieve
(2048 link relays / 256-word link data registers)
Can be used to share product type data between different machines.
Can be used for interlocking between different machines.
Easy wiring between PLCs with twin-core cabling.
Link data register
Link data register
Link data register
Product type data
Product type data
Product type data
Process machine
Assembly machine
Inspection machine
RS485
Masterless communication using the FPS (Sigma)
Even if a station goes into a power-off state, communications between
the other stations continue. The failed station can be integrated quickly
and smoothly into the network in the event of recurrence.
Link
station
Link
station
Link
station
Link
station
Connection to external devices using RS485 interface
Enables connection to external devices, such as temperature controllers
or Eco Power Meter, that are equipped with RS485 interface.
Transmission speed: Max. 115.2kbits/s.
Transmission distance: Max. 1200m.
Control is possible using commercially available RS485 devices.
GT Touch Terminals
RS232C
RS485
RS232C
Temperature controller, Eco Power Meter
KT4H
KW4M
09/2008
7
FPS (Sigma) positioning
Specially designed for positioning applications
Max. 100kHz pulse output performance is now standard.
Powerful device capable of linear interpolation and circular interpolation.
Pulse output max. 100kHz
Because command processing at speeds up to 100kHz is available,
high-speed, high-precision positioning is enabled. Along with stepping
motor control, the specs also ensure plenty of scope for controlling
servo motors.
FP∑ (Sigma)
Stepping motor
Servo motor
Pulse output CW
Y0
Pulse output CCW
Y1
Motor
driver
1
Pulse output CW
Y3
Possible to combine with pulse-train input drivers
Single unit enables two-axis control
5
Pulse output CCW
Y4
Motor
driver
2
Rapid 0.02ms start (when JOG operation controls are executed)
The time taken to execute the JOG operation, from the instant the trigger (execution condition) goes on to the time of pulse output,
is 0.02ms and 0.2ms even with trapezoidal control. Control time is reduced even for machines that quickly and repeatedly restart.
Linear interpolation and circular interpolation are built in
(FPG-C32T2H-A and FPG-C28P2H-A)
Interpolation functions enable simultaneous control of two axes.
Applications that a compact PLC couldn‘t previously cope with are
no longer a challenge.
Linear Interpolation
Circular Interpolation
Adhesive
And there’s more:
Support for CW/CCW method
You can choose to set either 30 or 60 steps of acceleration/
deceleration. This feature means you can achieve smoother
movement during long acceleration/ deceleration periods of
stepping motors.
The settings are there for a maximum 60 accelaration/
deceleration steps.
Reduce overall costs by designing systems that combine with
servo motors and small stepping motors without support for
Pulse and Sign method.
Pulse / Sign
method
CW / CCW
method
Smooth acceleration/deceleration
8
09/2008
Motor
driver
Motor
driver
(X 9396, Y -3420)
Target position E
(X 8660, Y -5000)
Home sensor
ON
XA ON
2000Hz
FPS (Sigma) positioning
100Hz
0Hz
High-speed, high precision positioning
150ms
Y-axis
Programming with convenient and
easy-to-understand instructions
(CH2)
Selectable home
return mode
2000
The home return method may be specified even in
situations such as when only a single sensor is being
used, depending on the design.
When the home position return is completed, a deviation
counter clear signal can also be output.
5000 X-axis
Uses a preset value table for starting speed, target speed,
acceleration/deceleration time, and other factors. Easy-tounderstand programming is possible since numbers can be
specified intuitively.
Current position S
Comes with dedicated instructions for each mode:
(X 5000, Y 8660)
trapezoidal control, home return, JOG operation,
free table
operation, linear interpolation, and circular interpolation.
(CH0)
θ
Center position O
(Xo,Yo)
Pass position P
(X 9396, Y -3420)
Target position E
(X 8660, Y -5000)
Home position return
JOG operation
Current position S
(X 5000, Y 8660)
Pulse output diagram
(when the home position proximity input is not used).
Pulse output diagram.
Home sensor
ON
XA ON
θ
Center position O
2000Hz
(Xo,Yo)
XB (JOG command) ON
OFF
Pass position P
(X 9396, Y -3420)
100Hz
0Hz
300Hz
Target position E
(X 8660, Y -5000)
Y0 (Pulse)
0Hz
150ms
Home search automatically reverses the motor rotation when
Over limit input(+) or Over
limit input (-) is input and their
Y-axis
sensor in order
(CH2) XA
searches for the home position
or ON
near homeHome
position
ON
to return to it automatically.
2000
This refers to an operation in which the motor is rotated only
while operation commands are being input. This is used to
forcibly rotate the motor using input from an external switch,
for instance when making adjustments. Depending on the
circumstances, unlimited feeding can be accomplished with
the JOG operation in some cases.
2000Hz
100Hz
0Hz
Linear interpolation
Positioning Iocus.
5000
150ms
X-axis
(CH0)
Circular interpolation
Positioning Iocus.
Center-radial
setting methods are
also available.
Y-axis
(CH2)
2000
Current position S
(X 5000, Y 8660)
θ
Center position O
(Xo,Yo)
5000
X-axis
(CH0)
A control function that automatically defines the continuum of
points in a straight line based
on only two coordinate positions.
XB (JOG command) ON
OFF
Target position E
(X 8660, Y -5000)
Allows points to be smoothly traversed by arced paths for which
the user specifies the orientation plane, the radius of curvature,
motion path profile and direction of motion.
XA ON
300Hz
Y0 (Pulse)
0Hz
Pass position P
(X 9396, Y -3420)
2000Hz
09/2008
100Hz
Home sensor
ON
9
FPS (Sigma) positioning expansion units
Precise positioning
Features
Fast startup of 0.02 or 0.005ms makes cycle time reduction possible.
Feedback pulse count function makes output pulse counting from external encoders possible.
JOG positioning control supports a wide range of applications.
4 types of S-curve acceleration/deceleration control makes smooth startup and stopping possible:
Sine curve, quadratic curve, cycloid curve and cubic curve.
FPG-PP11
FPG-PP12
FPG-PP21
FPG-PP22
K The FPS (Sigma) positioning unit can handle simultaneous startup of multiple axes, enabling simultaneous control of linear
interpolation and other elements through user programs.
K Transistor output type (open collector) and line driver output type are available.
Unit type and product number
Type
Output type
Part number
1-axis type
Transistor output type
FPG-PP11
2-axis type
Transistor output type
FPG-PP21
1-axis type
Line driver output type
FPG-PP12
2-axis type
Line driver output type
FPG-PP22
10
09/2008
FPS (Sigma) RTEX expansion units
RTEX multi-axis network servo system
The RTEX positioning units support Minas A4N network servo drives. A mutually optimized system consisting of PLC and servo
drive greatly simplifies installation.
Configuration example: 16 axes + I/O (256)
FP3 positioning unit RTEX
Monitor LEDs
Status display
Link status
Error display
Pulser input status
Pulser input
terminal
Network port
(Transmit)
Network port
(Receive)
FP dedicated expansion unit
(Max. of 4 units in combination
with positioning unit)
Positioning unit
RTEX
(Max. 2 units)
Control unit
FP /FP0 common
expansion unit
(Max. 3 units)
System configuration:
Maximum number of control axes: 16 axes. Realization of highly accurate 2-axis circular interpolation, 3-axis linear
interpolation and 3-axis spiral interpolation with high-speed 100Mbps communication.
With 3 types in the product range, for 2 axes, 4 axes and 8 axes, provides flexible support even for control of small
numbers of axes.
By using loop wiring Realtime Express* provides high reliability by creating smooth communication conditions with
the data flow always in the same direction.
* Matsushita Electric Industrial network servo systems
FP2/FP2SH Positioning unit RTEX
Specifications:
Configuration example: 8 axes x 14 modules = 112 axes
Master backplane
Pulser input
Part number FP∑ (Sigma)
/ FP2
Monitor LEDs
Status display
Link status
Error display
Pulser input status
terminal
Control method
Interpolation control
Network port
(Transmit)
2-axis type
4-axis type
8-axis type
FPG-PN2AN
FPG-PN4AN
FPG-PN8AN
Expansion backplane
Control units
Pulse/µm/inch/degree
Unit specifications
Network port
(Receive)
Positioning control
functions
Position data
Backup
600 points for each axis
Parameters and data file can be saved to FROM
Acceleration/deceleration
method
Linear acceleration/deceleration/S-curve acceleration/deceleration
Acceleration/deceleration
time
0 to 10,000ms (1ms units) different settings for acceleration and deceleration
are possible
Positioning area
(-1,073,741,823 to 1,073,741,823 pulse) increment and absolute specification
Speed control functions
Origin functions
PTP Control, Cursor Path (CP) Control
2-axis/3-axis linear interpolation, 2-axis circular interpolation,
3-axis spiral interpolation
Supported with JOG operation (free run operation)
Search method
Origin proximity (DOG) search
Creep speed
Free settings possible
Pulser input operation support
Other functions
Auxiliary output code, auxiliary output contact support
Communication
specifications
Dwell time support
Communication speed
Cable
100Mbps
Commercially available LAN straight cable (shielded category 5e)
Connection method
Communication cycle/no. of terminals
Ring method
0.5ms; max. 8 axes/system (command cycle: 1ms)
Transmission distance
Between terminals: 60m; total length: 200m
09/2008
11
Optimized temperature control
Functions convenient for temperature control are built in
The control unit with thermistor inputs enables temperature control
at low cost
Two thermistor inputs, which cost less than thermocouples,
can be connected to the FPS (Sigma) unit via thermistor inputs
(FPG-C28P2HTM, FPG-C32T2HTM and FPG-C24R2HTM).
FPS (Sigma) control unit that
FP¤
control
unit that
accepts
thermistors
accepts thermistors
Thermistor
Using a simple linearization command, measuring
the temperature by the thermistor can be programmed easily.
Analog I/O Unit
A/D
sensor
sor
nerator
D/A
Inverter
Motor
Four- and eight-channel type thermocouple input expansion unit
Up to three units can be added to each control unit, enabling temperature
Analog input type
control of up to 24 channels.
servodriver
Servo motor
Advantages over multiple temperature controllers:
Information collection and computer-based storage.
On-site error monitoring using programmable display.
Significant reduction in total costs.
Power supply stabilisation by protecting synchronisation
between heater ON and OFF states.
Temperature settings can be easily changed using batch function.
Optimized temperature control with PID and PWM instruction
You can easily set multi-stage temperature control and time
control usually available only in high performance type
temperature controllers.
Various FPWIN Pro libraries simplify the programming of closed loop
controlled electrical installations and consequently save valuable human
resurce costs. The process and temperature control Library NCL-PTC-LIB,
for example, includes linear and non-linear controller types such as the
P/I/PI/PID controller and two-point / three-point controllers with and without
hysteresis. Functions for dead band, interpolation, ramp limiting, dead time
and averaging are also included.
12
09/2008
Example of temperature control
with the auto-tuning function only
FP∑ (Sigma) data memory expansion unit
Data capacity expandable up to 256k words
Features
Able to store 256k words, this memory unit is well-suited for storing remote monitoring logs.
Take advantage of FPS’s (Sigma) memory for manufacturing systems that produce more than one model. With FPS’s (Sigma)
memory, you no longer need to download new production data every time you switch manufacturing process.
Up to 4 units can be connected to the FPS (Sigma), allowing up to 1024k words to be stored.
General specifications
Item
Ambient temperature/
humidity
Storage temperature/
humidity
Vibration resistance
Shock resistance
Noise immunity
Basic unit mass
The amount of increase in
control unit consumption
current
FPG-EM1
Description
0 to 55°C, 30 to 85% RH (no condensation)
-20 to +70°C, 30 to 85% RH (no condensation)
10 to 55Hz, 1 sweep/min.,
double amplitude of 0.75mm, 10min. on 3 axes
98m/s 2 or more, 4 times on 3 axes
1000V (P-P) with pulse width 50ns,
1µs (using a noise simulator)
Approx. 80g
35mA or less (24VDC)
(100mA or less (internal 5VDC)
Performance specifications
Item
Memory capacity
Battery life
5V Power consumption
Number of I/O points
Description
256k words (1k words x 256 banks)
5 years or more
10 to 55Hz, 1 sweep/min.,
double amplitude of 100mA or less
Input 16 points
Programming tool FPWIN Pro
Instructions F150 and F151 are necessary for reading from
and writing to memory expansion units.
Data is read with the
F150 instruction.
X0-7
X8-F
0
RUN
1
2
PROG.
3
Data is written with
the F151 instruction.
4
5
6
ERROR
7
ALARM
8
9
A
B
RUN
C
D
E
F
PROG.
Y0-7
Y8-F
0
1
2
3
4
COM.1
S
R
COM.2
S
R
5
6
7
8
9
A
B
C
D
E
F
max.
V0
min.
V1
09/2008
13
FPS (Sigma) Flexible Network Slave units
Powerful, modular network units
The Flexible Network Slave (FNS) units are powerful, modular network units used together with the programmable controllers
FPS (Sigma). By exchanging compact network blocks, you can connect to various networking systems without having to modify
your entire hardware platform. The blocks are available for three bus systems: PROFIBUS, DeviceNet and CANopen. Others are
planned for the future.
Flexible Plug-In Network modules
The world’s first in a PLC
FPG-FNS
PROFIBUS
Plug-in module
AFPN-AB6200
DeviceNet
Plug-in module
AFPN-AB6201
CANopen
Plug-in module
AFPN-AB6218
No special tools are required for mounting. You can mount the blocks in the device at any phase between manufacturer and end
customer without having to worry about special protective provisions.
Advantages:
Wide range of connectivity solutions for FPS (Sigma) and FP2/FP2SH.
One PLC hardware platform for several bus systems.
Fast reaction on new market trends possible with existing units.
No additional hardware development needed. You need only to exchange
the network block.
Very small and compact size.
For each network type ready-made function libraries are available for the programming software
FPWIN Pro, which can be downloaded from Panasonic Electric Works’ internet homepage. These libraries will drastically shorten
the time needed to develop your applications and consequently save valuable human resource costs. They also include a complete
online help file and programming examples. In addition, you need the GSD or EDS files which describe how the slave modules
communicate with the master module. Also these can be downloaded from the same internet homepage.
FNS (Flexible Network Slave) specifications:
Item
Baud rate
Isolation
Connection
types
Maximum
inputs/
outputs
Additional
features
Interface
PROFIBUS
DeviceNet
CANopen
Automatic baud rate detection
9.6kbaud to 12Mbaud
125kbps to 500kbps
10kbps to 1Mbps
Galvanically isolated bus electronics
PDO (Process Data
• Cyclic connections
Object) exchange via:
DP-V0: process data is
• COS (Change of State)
• Cyclic synchronous
accessed from the
• Bit strobe connections
PROFIBUS network as
• Acyclic synchronous
• Polled connections
cyclical I/O data
• COS
• Explicit connections
• Timer-driven connections
76 words altogether for
E.g. for cyclic connec128 words
inputs and outputs
tions: 128 words in each
(for TPDOs and RPDOs)
(in units of 1.2 or 4 words) direction
• UCMM capable
Diagnostic support
• CIP parameter object
Diagnostic support
• Diagnostic support
DB9F
5-pin terminal block
DB9M (9-pin D-sub male)
(9-pin D-Sub female)
Free download for FNS-related files:
www.panasonic-electric-works.com
14
09/2008
FPS (Sigma) Fieldbus Master Units
The optimal network solution for your facility
The expansion Fieldbus Master Units (FMU) allow you to integrate FPΣ (Sigma) PLCs into your network with a maximum degree of
flexibility. The units are available for three bus systems: PROFIBUS, DeviceNet and CANopen. Others are planned for the future.
FPS FMU PROFIBUS:
FPG-DPV1-M
FPS FMU DeviceNet:
FPG-DEV-M
FPS FMU CANopen:
FPG-CAN-M
Advantages:
Wide range of connectivity solutions for FPΣ (Sigma).
One PLC hardware platform for several bus systems.
Gateway function between Fieldbus types simply by connecting the
corresponding expansion units to the same CPU.
One configuration software for various Fieldbus systems:
one-time cost, several network types,
only one installation necessary,
user must only be trained to use one software.
The configuration software is integrated in the PLC programming
software Control FPWIN Pro:
no additional software required on the PC,
bus-relevant global variables are automatically generated for the
PLC program
Fieldbus Master Units (FMU) Library for PROFIBUS, DeviceNet and
CANopen can be downloaded free of charge from Panasonic Electric
Works’ internet homepage.
Control Configurator FM is an add-on
software for Control FPWIN Pro and is
used to configure and diagnose the FMUs.
Part number: AFPS35510
FMU (Fieldbus Master Unit) specifications:
Technical data
Bustype
Number of slaves
PROFIBUS DP
RS485
Connection types
Internal current consumption
Connector type
CANopen
CAN / ISO 11898
125
Number of process data
Bus length
DeviceNet
63
126
3584 bytes for inputs and 3584 bytes for outputs
100m (12Mbit/s)
200m (1.5Mbit/s)
400m (500kbit/s)
1km (187.5kbit/s)
100m (500kbit/s)
250m (250kbit/s)
500m (100kbit/s)
40m (1Mbit/s)
500m (100kbit/s)
DP-V0: process data is accessed
from the PROFIBUS network
as cyclical I/O data
•
•
•
•
•
PDO (Process Data Object)
Exchange via:
• Cyclic synchronous
• Acyclic synchronous
• COS
• Timer-driven connections
Cyclic connections
COS (Change of State)
Bit strobe connections
Polled connections
Explicit connections
450mA
150mA
450mA
DB9F (9-pin D-Sub female)
5-pin terminal block
DB9M (9-pin D-Sub male)
Weight
95g
09/2008
15
FPS (Sigma) S-Link expansion unit
Flexible wire-saving link system S-Link
Features
Up to four S-Link units can be attached to one FPS (Sigma) CPU.
Each unit supports up to 128 I/O signals over a pair of wires up to a distance of 200m
(400m when a booster is used).
The combination of input and output point quantities (a total of 128 points max.) can be set by the rotary
switch in increments of 32 points.
The transmission line connection is realized via a T-branch multi-drop wiring with hook-up connectors.
Adding devices is rendered easy and maintenance is easy.
FPS (Sigma) + S-Link unit
FPΣ +
S-LINK unit
FPG-SL
Features
24VDC
The four-wire cable (two signal wires and two power wires) enables efficient
wiring, and the T-branch wirinig enables a flexible connection layout.
About 60 types of S-Link input/output devices can be
connected to this unit, enabling it to meet diverse I/O
35 Ms
needs. In addition, the high transmission voltage
(24VDC) and the wide clock width (35µs) provide high
noise immunity. Flexible and reliable wiring is available,
reducing the wiring work.
Features
The control unit automatically recognizes I/O allocation in accordance with the attached S-Link unit
position, making the S-Link unit as easy to use as a common expansion I/O device.
If the main wire is broken and an input/output device cannot be recognized, then the S-Link unit displays
the device number. This function significantly reduces the time required for troubleshooting during an
equipment startup check or recovering from on-site problems.
Specifications
Transmission method
Synchronization
Transmission protocol
Transmission line
Transmission speed
Transmission distance *¹
Connection method
Number of I/O points
Bi-directional time-divided multiple signal transmission
Bit synchronization, frame synchronization
S-Link protocol
Exclusive flat cable or cabtyre cable
28.5kbps
Main signal wires: Extensible up to 200m (400m when a booster is used)
T-branch multi-drop wiring or multi-drop wiring
128 points max. (adjustable in encrements of 32 I/O points)
*1 For boosters, see the S-Link catalog and manual issued by SUNX Limited.
16
09/2008
FPS (Sigma)
Supports the enhancement of your equipment’s performance
Network enhancement
Modbus-compatible
FPS (Sigma) is compatible with the world‘s
de facto standard Modbus* and can serve
as both Modbus RTU master and slave,
making it ideal for air conditioning or
temperature control etc.
FPS (Sigma) can serve as Modbus master or slave
Can be used as a master station [F145 (Write) and F146 (Read) instructions].
Can easily communicate with temperature controllers, inverters, FP-e and
overseas PLCs.
Also serves as
a slave station.
* Protocol developed by Modicon Inc.,
an American company
Other available applications
When 17 or more FPS (Sigma) units need to be
linked, you can use the Modbus function instead
of MEWNET-W0 to link up to 99 units. Since each
FPS (Sigma) unit can be either a master or a slave,
a multi-master link can be created by passing a
token from a user program.
Temperature
controller
Power meter
Inverter
FP2/FP2SH
FP-e
FP-X
Token passing
A multi-master link
of up to 99 units
can be created.
Master/
Slave
Master/
Slave
Master/
Slave
Master/
Slave
New “MEWTOCOL Master” function available
The MEWTOCOL master function automatically creates and transmits commands using the Panasonic open protocol
MEWTOCOL. This function significantly facilitates serial communications with MEWTOCOL-compatible equipment, such as
PD60/65, KT4H and KW4M.
RS232C
2D code reader
PD60/65
RS485
Temperature
controller
KT4H
Eco Power Meter
KW4M
Security enhancement
Programs are copy-protected by the upload restriction setting and an eight-character password.
The setting to inhibit the uploading of PLC programs to PCs protects your programs from unauthorized copying. (If this setting is
released, programs in the PLC are forcibly cleared.)
An eight-character password has been adopted. (The conventional four-character password is also available.)
Approx. 218 trillion passwords can be set by combining eight alphanumeric characters, making it nearly impossible to crack the
password set.
Debugging performance enhancement
Up to 512 steps can be rewritten simultaneously in RUN mode.
This improvement allows efficient program debugging without stopping the operation.
09/2008
17
FP Web-Server
FPS (Sigma) programming and operation with LAN/WAN
Wordwide communications
The FP Web-Server module connects all FP-series con­trollers to the Ethernet. No chan­ges to the
PLC program are necessary. Simply assign an IP address to the FP Web-Server and connect the
PLC to the FP Web-Server via the serial RS232C interface. A standard brow­ser, e.g. MS Internet
Explorer, can be used for access at the PC. Configuration of the unit is easily done with the FP
Web Configurator Tool, which has to be ordered once separately.
FP Web-Server main features:
FP Web-Server advantages:
Uses existing intranet,
saves wiring
Uses standard browser,
saves Scada software
Remote control
Remote monitoring
Remote programming
Alarm information via email
Interface/protocol converter
Web-Server:
PLC data presented as HTML pages
Access via standard internet browser
HTML entry field for PLC data change
Optional password protection
Java applet functions library
Ajax JavaScript examples available
Email:
PLC can send emails, also with PLC data attachments
Email server access via LAN or Internet dial-up
PLC defined or pre-stored mail text
FPWEB2
RS232C device server:
Ethernet ↔ RS232C conversion (MEWTOCOL)
Transparent RS232C data tunnelling via Ethernet
Programming and visualisation access via Ethernet
Modem / Ethernet gateway:
FP Web-Server can be dialled up via modem for local or
network access
One remote gateway for multiple FP Web-Servers in a
local Ethernet network
Remote password handling
IEC60870 communicator
Based on the same hardware as the FP Web-Server safe
and easy telecontrol with FP-series PLCs using the wide
spread IEC60870-5 telecontrol standard is possible. Thus
remote process stations can easily be linked to supervisory
control systems or telecontrol main stations. The IEC60870
communicator supports both IEC60870-5-101 communication
via RS232C or modem and IEC60870-5-104 communication
via Ethernet in one module.
Modbus-TCP communication
Modbus-TCP server or client for a PLC
Modbus-TCP server for multiple PLCs
Modbus-TCP server gateway for Modbus-RTU slave
unit(s)
Modbus-TCP client gateway for any Modbus-RTU master
Modbus-TCP master or slave interface for a PLC
Other functions:
XML file delivery for PLC data exchange
Network time server functions
Specifications
Protocols
Number of
browsers
Number of emails
Number of email
addresses
Number of PLC
per unit
IP address
Security
Operating power
Dimensions
Part number
FP Web-Server
Licence to upgrade an
FP Web-Server to an
IEC60870 communicator
FP Web
Configurator Tool
18
FPWEB2
IEC60870LIS
LEDs
Flash memory
Standards fulfilled
FPWEBTOOL2
09/2008
TCP/IP, UDP/IP, SMTP, PPP, NTP, FTP, TELNET,
HTTP, MEWTOCOL-COM
Up to 64 browsers can be connected to one
FP Web-Server
4 predefined in FP Web Flash memory
1 programmable in PLC DT memory as ASCII
4 predefined in FP Web flash memory,
1000 addresses in PLC DT memory, assuming
an average of 32 characters are used per email
address and that an FP0-T32CP with
16k word memory is used
Two PLCs can be connected
3-pin port (port number: 9094)
DB8 port (port number: 9095)
DHCP or manually set by software
Password and DIP switch
24VDC, 75mA (max.)
25 x 90 x 60mm (W x H x D)
Power, COM Ethernet connection, COM data
exchange
512Kbytes
CE, UL, cUL
Control FPWIN Pro
PLC programming software conforming to IEC 61131-3
FPWIN Pro is the Panasonic programming software developed according to the international standard IEC 61131-3
(for Windows 98, NT V4.0, 2000, ME or XP). This new version is a result of experience gained over many years. We were one
of the first PLC manufacturers to offer an IEC 61131-3 programming software, and we are a leading member of the international
organisation PLCopen.
Multiple address assigment
is caught automatically by
the compiler.
Input and output variables
are defined once in the global
variable list.
Local variables are allocated
automatically by the compiler.
Type safe programming using
simple or complex data types.
Comfortable programming in the graphical
LD editor (ladder diagram).
Functions can be saved in
libraries for future reuse.
One instruction for different data types
(overloaded instructions).
Temporary variables are allocated and
released automatically by the compiler.
Navigator with tree representation of
called functions provides an overview
even for very complex projects.
Long variable names make the program
self-explanatory.
The SFC editor (Sequential Function Chart)
allows you to easily visualize processes.
Additional window for monitoring
and forcing variables.
Special functions for controlling the SFC
program from another program.
Using alliases names for PLC-independent
access on the special data registers, e.g. RTC
The ST editor (Structured
Text) solves complex
programming tasks.
Structuring with
selection statements.
No. C-35
04.04.2003
DS: 10 of 26
No. C-34
ST
April 4, 2003
Using loops for running
through incoming data…
…or arrays.
Easy handling of
formulas and
arithmetic
expressions.
Data types supported: 10 of 26
Using STRING functions
for analyzing incoming
data…
Free demonstration disc
…or for generating
formatted output strings.
The most important highlights at a glance:
One software for all FP-series PLCs.
5 programming languages (instruction list, ladder diagram, function block diagram,
sequential function chart, structured text) available for all PLCs.
Program organisation units, task and project management provide clear structure.
Reuse of ready-made functions and function blocks saves time for programming and
debugging.
Online monitoring and diagnostics.
Forcing – turning off input and output contacts via the PC.
Modem communication for remote programming, service and diagnostics.
Extensive comments – online documentation created hand in hand with the program.
6 languages are supported: English, German, French, Italian, Spanish and Japanese.
09/2008
Part numbers:
FPWINPROF: Full version
supports all FP-series PLCs
FPWINPROS: Small version,
supports FP-e, FP0, FP-X
and FPS (Sigma)
19
FPS (Sigma)
Specification tables
Performance specifications
Description
Item
Type of control unit
Part number
NPN transistor output type
PNP transistor output type
Relay output type
FPG-C32T2H-A
FPG-C32T2HTM
FPG-C28P2H-A
FPG-C28P2HTM
FPG-C24R2H-A
FPG-C24R2HTM
32 (Input: 16 / Output: 16)
28 (Input: 16 / Output:12)
24 (Input: 16 / Output: 8)
Max. 384
Max. 380
Max. 376
Number of I/O points
No expansion
With expansion
Program memory
Program capacity
Operation speed
Built-in Flash ROM (without backup battery)
32,000 steps
0.32 µs/step, basic instructions
Memory for execution
External input (X)
1184 points
External output (Y)
1184 points
Internal relay (R)
Timer/Counter (T/C)
4096 points (R0 to R255F)
1024 points 1, 2 / at reset: timer 1008 points (T0-T1007), counter 16 points (C1008-C1023),
Timer range is selected by instructions from 1ms, 10ms, 100ms, 1s
Counter: 1 to 32,767 counts
Link relay (L)
2048 points ¹
Data register (DT)
32,765 words (DT0-DT32,764) ¹
Link data register (LD)
Index register (I)
Differential points
Master control relay points
Labels (JP+LOOP)
Number of step ladder
Number of subroutine
High-speed counter
Pulse output
PWM output
Pulse catch input
Interrupt program
Self-diagnosis functions
Clock/calendar function
Volume input
Thermistor input
Link functions
Battery life (battery is optional)
Comment storage
Linear/circular interpolution
for positioning
Other functions
256 words ¹
14 words (I0-ID)
Unlimited number of points
256 points
256 labels
1000 stages
100 subroutines
Single-phase: 1ch: 50kHz/2ch: 30kHz/3 or 4ch: 20kHz / Two-phase: 1ch: 20kHz/2ch: 15kHz
1 channel: 100kHz / 2 channel: 60kHz
2 channels, 1.5 to 12.5kHz (at resolution of 1000) / 15.6 to 41.7kHz (at resolution of 100)
8 points (X0-X7)
9 programs (external 8 points, 1 periodical interrupt point 0.5ms–30s)
Watchdog timer, program syntax checking, etc.
Year, month, day, hour, minute, second, and day of week 6
2 points resolving power 10bits (K0-K1000)
2 points, resolution: 10 bits (0 to 1000) (for C32T2HTM, C24R2HTM and C28P2HTM only)
Computer link (1:1, 1:N) 3, 4 General communication (1:1, 1:N) 3, 4 PLC link 5
220 days or more* (actual usage value: approx. 840 days (25°C)
Suggested replacement interval: 1 year
All kinds of comments, including I/O comments, remarks and block comments, can be stored
(without backup battery)
Available
Available
Not available
Program edition during run, constant scan, forced I/O, password, floating point real number operation,
PID processing instruction, comment memory 328kByte
Notes: 1) If a battery is not used, only fixed area is backed up (Counter: C1008-C1023, internal relay: R900-R97F, Data register: DT32710-DT32764). If a battery is used, backup is possible:
Area-setting of hold or no-hold is possible by system register.
2) Points can be increased using auxiliary timer.
3) Optional communication cassette (RS232C type) is necessary for 1:1 communication.
4) Optional communication cassette (RS485 type) is necessary for 1:N communication.
5) Optional communication cassette (RS485 type) is necessary.
6) Optional battery is necessary in order to use Clock/Calendar function. Precision calendar timer: at 25°C = 77°F less than 51-second error per month / at 0°C = 32°F less than
119-second error per month / at 55°C = 131°F less than 148-second error per month.
*Value applies when no power is supplied at all.
20
09/2008
FPS (Sigma)
Specification tables
Input specifications
Insulation method
Optical coupler
Rated input voltage
24VDC
Input voltage range
Rated input current
21.6 to 26.4VDC
3.5mA–8mA depends on input no.
8 points/common (FPG-C24), 16 points/common (FPG-C32/C28), 32 points/­common (FPG-XY64)
Either the positive or negative of input power supply can be connected to terminal
Input points per common
Min. ON voltage /
Max. OFF current
Max. ON voltage /
Min. OFF current
Input impedance
19.2V / 3mA–6mA depending on input no.
2.4V / 1.3mA
3k–6.8k depends on input no.
CPU:
Expansion:
Response time
Operating indicator
1ms or less, 5µs (HSC, pulse catch, interrupt input)
0.2ms (OFF → ON)
0.3ms (ON → OFF)
LED
Output specifications – Transistor output type
Item
FPG-C32 (NPN)
Insulation method
Optical coupler
Output method
Rated voltage range
Operating load voltage range
Max. load current
Max. surge current
Output points per common
Open collector
Response time
FPG-C28 (PNP)
5 to 24VDC
24VDC
4.75 to 26.4VDC
21.6 to 26.4VDC
For Y0, Y1, Y3, Y4: 0.3A – For Y2, Y5 to YF: 0.1A
For Y0, Y1, Y3, Y4: 0.5A – For Y2, Y5 to YB: 0.3A
For Y0, Y1, Y3, Y4: 0.9A – For Y2, Y5 to YF: 0.5A
For Y0, Y1, Y3, Y4: 1.5A – For Y2, Y5 to YB: 0.7A
16 points/common
12 points/common
OFF → ON
For Y0, Y1, Y3, Y4 at 15mA or less: <2µs – For Y2, Y5 and higher: < 0.2ms
ON → OFF
For Y0, Y1, Y3, Y4 at 15mA or less: <8µs – For Y2, Y5 and higher: < 0.5ms
Power supply for driving
internal circuit
Operating indicator
Phase fault protection
21.6 to 26.4VDC (70mA)
LED
Thermal protection for Y2, Y5 and higher
Output specifications – relay output type
Output type
Normally open (1 Form A)
Rated control capacity
2A 250VAC, 2A 30VDC (max. 4.5A/common) (resistive load)
Output points per common
OFF → ON
Response time
ON → OFF
Mechanical life time
Electrical life time
Surge absorber
Operating indicator
8 points/common
10ms or less
8ms or less
20 million operations or more
100,000 operations or more
None
LED
Shock resistance
98m/s2 or more,
4 times on 3 axes
Noise humidity
1000V (p-p) with
pulse widths 50ns and 1µs
Operating condition
Free from corrosive gasses and excessive dust
09/2008
21
FPS (Sigma) product overview
Part numbers
FPS (Sigma) control units
Product name
FPS C28 CPU, 16 inputs, 12 outputs (transistor PNP)
FPS C32 CPU, 16 inputs, 16 outputs (transistor NPN)
FPS C24 CPU, 16 inputs, 8 outputs (relay)
FPS C28 CPU, 16 inputs (+ 2 thermistor inputs) , 12 outputs (transistor PNP)
Part number
FPG-C28P2H-A
FPG-C32T2H-A
FPG-C24R2H-A
FPG-C28P2HTM
FPS C32 CPU, 16 inputs (+ 2 thermistor inputs) , 16 outputs (transistor NPN)
FPG-C32T2HTM
FPS C24 CPU, 16 inputs (+ 2 thermistor inputs), 8 outputs (relay)
FPG-C24R2HTM
FPS (Sigma) expansion units (left side expansion)
FPS 64-points I/O expansion unit, 32 inputs, 32 outputs (transistor PNP)
FPS 64-points I/O expansion unit, 32 inputs, 32 outputs (transistor NPN)
FPS memory expansion unit, 256k words
FPS positioning expansion unit, 1 axis type, transistor output
FPS positioning expansion unit, 1 axis type, line driver output
FPS positioning expansion unit, 2 axes type, transistor output
FPS positioning expansion unit, 2 axes type, line driver output
FPS positioning expansion unit RTEX, 2 axes type
FPS positioning expansion unit RTEX, 4 axes type
FPS positioning expansion unit RTEX, 8 axes type
FPS PROFIBUS master expansion unit
FPS FNS + PROFIBUS DP slave module
FPS CANopen master expansion unit
FPS FNS + CANopen slave module
FPS DeviceNet master expansion unit
FPS FNS + DeviceNet slave module
FPS S-Link master expansion unit
FPS CC-Link slave expansion unit
FPG-XY64D2P-A
FPG-XY64D2T-A
FPG-EM1
FPG-PP11
FPG-PP12
FPG-PP21
FPG-PP22
FPG-PN2AN
FPG-PN4AN
FPG-PN8AN
FPG-DPV1-M
FPGFNS + AFPNAB6200
FPG-CAN-M
FPGFNS + AFPNAB6218
FPG-DEV-M
FPGFNS + AFPNAB6201
FPG-SL
FPG-CCLS
FP0 expansion units (right side expansion)
FP0-E8RS, 4 inputs, 4 outputs (relay)
FP0-E8X, 8 inputs
FP0-E8YP, 8 outputs (transistor PNP)
FP0-E8YT, 8 outputs (transistor NPN)
FP0-E16RS, 8 inputs, 8 outputs (relay)
FP0-E16P, 8 inputs, 8 outputs (transistor, PNP)
FP0-E16T, 8 inputs, 8 outputs (transistor, NPN)
FP0-E16X, 16 inputs
FP0-E16YP, 16 outputs (transistor PNP)
FP0-E16YT, 16 outputs (transistor NPN)
FP0-E32PA, 16 inputs, 16 outputs (PNP)
FP0-E32RS, 16 inputs, 16 outputs (relay)
FP0-E32T 16 inputs, 16 outputs (NPN)
FP0-A21A, 2 analog inputs, 1 analog output
FP0A04V, 4 analog outputs, -10 to 10V
FP0-A04I, 4 analog outputs, 4 to 20mA
FP0-A80A, 8 analog inputs
FP0 thermocouple unit, 4 inputs
FP0 thermocouple unit, 8 inputs
FP0 RTD input unit, 6 inputs
FP Web-Server
22
FP0-E8RSA
FP0-E8XA
FP0-E8YPA
FP0-E8YTA
FP0-E16RSA
FP0-E16PA
FP0-E16TA
FP0-E16XA
FP0-E16YPA
FP0-E16YTA
FP0-E32PA
FP0-E32RS
FP0-E32T
FP0-A21A
FP0-A04V
FP0-A04I
FP0-A80A
FP0-TC4
FP0-TC8
FP0-RTD6
FPWEB2
09/2008
FPS (Sigma) product overview
Part numbers
FPS (Sigma) accessories
Product name
FPS 1 channel, RS232C type communication cassette
FPS 2 channels, RS232C type communication cassette
FPS 1 channel, RS485 type communication cassette
FPS 2 channels, RS232C & RS485 type communication cassette
FPS battery, for memory backup & clock functions
FPS power supply cable, 1m
High capacity battery holder
Part number
FPG-COM1
FPG-COM2
FPG-COM3
FPG-COM4
AFPG804
AFPG805
AFPG807
FP memory loader, for transfer of programs without a PC or memory unit (data clear type)
AFP8670
FP memory loader, for transfer of programs without a PC or memory unit (data hold type)
AFP8671
AC power supply
FP0 AC power supply, 24VDC, 0.7A
FP Power supply, 24VDC, 2.1A
FP0-PSA2
FPPS24050ED
Software
FPWIN Pro PLC programming software, small version for
FP-e, FP0, FPS (Sigma) and FP-X
with English manual
with German manual
with French manual
FPWIN Pro PLC programming software, full version for all FP-series PLCs
with English manual
with German manual
with French manual
FPWINPROSEN5
FPWINPROSDE5
FPWINPROSFR5
FPWINPROFEN5
FPWINPROFDE5
FPWINPROFFR5
FP OPC server software with one license
AFPS03510D
FP OPC Server license
AFPS03517D
FP Data Analyzer software tool to read and display PLC data
AFPS04510D
Control configurator FM, configuration software for FPS (Sigma) FMU
AFPS35510
Configurator PM software tool for FPS (Sigma) positioning units RTEX
AFPS66510
PCWAY data monitoring, logging and setting software based on Microsoft Excel
AFW10031
CommX software with USB port dongle
AFW20031
USB port dongle for CommX and PCWAY
AFW1033
09/2008
23
Global Network
North America
Europe
Asia Pacific
China
Japan
Panasonic Electric Works
Please contact our Global Sales Companies in:
Europe
 Headquarters
 Austria
Panasonic Electric Works Europe AG
Panasonic Electric Works Austria GmbH
 Germany
 Hungary
PEW Electronic Materials Europe GmbH
Panasonic Electric Works
Sales Western Europe B.V.
Panasonic Electric Works Czech s.r.o.
Panasonic Electric Works
Sales Western Europe B.V.
Panasonic Electric Works Deutschland GmbH
Panasonic Electric Works Europe AG
 Ireland
 Italy
Panasonic Electric Works UK Ltd.
Panasonic Electric Works Italia srl
 Benelux
 Czech Republic
 France
Panasonic Electric Works Italia Srl
 Nordic Countries Panasonic Electric Works Nordic AB
PEW Fire & Security Technology Europe AB
 Poland
Panasonic Electric Works Polska sp. z o.o
 Portugal
Panasonic Electric Works España S.A.
 Spain
Panasonic Electric Works España S.A.
 Switzerland
Panasonic Electric Works Schweiz AG
 United Kingdom Panasonic Electric Works UK Ltd.
Rudolf-Diesel-Ring 2, 83607 Holzkirchen, Tel. +49 (0) 8024 648-0, Fax +49 (0) 8024 648-111, www.panasonic-electric-works.com
Rep. of PEWDE, Josef Madersperger Str. 2, 2362 Biedermannsdorf, Tel. +43 (0) 2236-26846, Fax +43 (0) 2236-46133
www.panasonic-electric-works.at
Ennshafenstraße 30, 4470 Enns, Tel. +43 (0) 7223 883, Fax +43 (0) 7223 88333, www.panasonic-electronic-materials.com
De Rijn 4, (Postbus 211), 5684 PJ Best, (5680 AE Best), Netherlands, Tel. +31 (0) 499 372727, Fax +31 (0) 499 372185,
www.panasonic-electric-works.nl
Prumyslová 1, 34815 Planá, Tel. (+420-)374 799 990, Fax (+420-)374 799 999, www.panasonic-electric-works.cz
Succursale française, 10, rue des petits ruisseaux, 91370 Verrières Le Buisson, Tél. +33 (0) 1 6013 5757, Fax +33 (0) 1 6013 5758,
www.panasonic-electric-works.fr
Rudolf-Diesel-Ring 2, 83607 Holzkirchen, Tel. +49 (0) 8024 648-0, Fax +49 (0) 8024 648-555, www.panasonic-electric-works.de
Magyarországi Közvetlen Kereskedelmi Képviselet, 1117 Budapest, Neumann János u. 1., Tel. +36 (0) 1482-9258, Fax +36 (0) 1482-9259,
www.panasonic-electric-works.hu
Dublin, Tel. +353 (0) 14600969, Fax +353 (0) 14601131, www.panasonic-electric-works.co.uk
Via del Commercio 3-5 (Z.I. Ferlina), 37012 Bussolengo (VR), Tel. +39 (0) 456752711, Fax +39 (0) 456700444,
www.panasonic-electric-works.it
Building Materials Division, Piazza della Repubblica 24, 20154 Milano MI, Tel. +39-02-2900-5391, Fax +39-02-2900-3466
Sjöängsvägen 10, 19272 Sollentuna, Sweden, Tel. +46 859476680, Fax +46 859476690, www.panasonic-electric-works.se
Citadellsvägen 23, 21118 Malmö, Tel. +46 40 697 7000, Fax +46 40 697 7099, www.panasonic-fire-security.com
Al. Krakowska 4/6, 02-284 Warszawa, Tel. +48 (0) 22 338-11-33, Fax +48 (0) 22 338-12-00, www.panasonic-electric-works.pl
Portuguese Branch Office, Avda Adelino Amaro da Costa 728 R/C J, 2750-277 Cascais, Tel. +351 214812520, Fax +351 214812529
Barajas Park, San Severo 20, 28042 Madrid, Tel. +34 913293875, Fax +34 913292976, www.panasonic-electric-works.es
Grundstrasse 8, 6343 Rotkreuz, Tel. +41 (0) 41 7997050, Fax +41 (0) 41 7997055, www.panasonic-electric-works.ch
Sunrise Parkway, Linford Wood, Milton Keynes, MK14 6 LF, Tel. +44 (0) 1908 231555, Fax +44 (0) 1908 231599,
www.panasonic-electric-works.co.uk
North & South America
 USA
PEW Corporation of America
629 Central Avenue, New Providence, N.J. 07974, Tel. 1-908-464-3550, Fax 1-908-464-8513, www.pewa.panasonic.com
Asia Pacific / China / Japan
 China
Panasonic Electric Works (China) Co., Ltd.
 Hong Kong
Panasonic Electric Works
(Hong Kong) Co., Ltd.
1048 Kadoma, Kadoma-shi, Osaka 571-8686, Japan, Tel. (06) 6908-1050, Fax (06) 6908-5781, www.mew.co.jp/e-acg/
Matsushita Electric Works, Ltd.
Panasonic Electric Works Asia Pacific Pte. Ltd. 101 Thomson Road, #25-03/05, United Square, Singapore 307591, Tel. (06255) 5473, Fax (06253) 5689
 Japan
 Singapore
Level 2, Tower W3, The Towers Oriental Plaza, No. 2, East Chang An Ave., Dong Cheng District, Beijing 100738, Tel. (010) 8518-5988,
Fax (010) 8518-1297
RM1205-9, 12/F, Tower 2, The Gateway, 25 Canton Road, Tsimshatsui, Kowloon, Hong Kong, Tel. (0852) 2956-3118, Fax (0852) 2956-0398
09/2008
Copyright © 2008 • Printed in Germany
4136 euen 08/08
Similar pages