TDK HWS150-24/HD Single output industrial power supply Datasheet

HWS50-1500/HD Series
Single Output Industrial Power Supplies
Features
u Limited Lifetime Warranty
u -10 to +71°C Operation (-40°C start up)
u Universal Input (85 - 265VAC)
u Conformally coated pcbs
u Class 1 Div 2 option (/RYHD suffix)
u Wide range AC Input
Key Market Segments & Applications
Specifications
Model
Input Voltage range (47-63Hz)
Input Current (Typ)
(1)
Inrush Current
(1)
Power Factor
Temperature Coefficient
Overcurrent Protection
Overvoltage Protection
Hold Up Time (Typ)
Leakage Current (60Hz)
Remote Sense
Indicator
Remote On/Off
Parallel operation
DC Good
Remote Adjust (PV)
Operating Temperature
and Derating (operation to
+74°C - contact factory)
Storage Temperature
Humidity (non condensing)
Cooling
Withstand Voltage
(2)
Isolation Resistance
Vibration (non operating)
Shock (in packaging)
Safety Agency Approvals
Line Dip
Conducted & Radiated EMI
Immunity
Weight (Typ)
Size (WxHxD)
Warranty
A
A
V
ms
mA
°C
°C
g
in
yrs
HWS50
HWS100
HWS150
HWS300
HWS600
HWS1000 HWS1500
85-265VAC or 120-370VDC
85-265VAC or 120-330VDC (No DC input for HWS1500)
0.7 / 0.35
1.3 / 0.65
1.9 / 0.95
4.1 / 2.1
8.1 / 3.9
13.5 / 7
19 / 10
14 / 2
20 / 4
Meets EN61000-3-2
<0.02%/°C
>104%
Yes (See table on page 2)
20
<0.5mA
<0.75mA
<1.2mA
≤1.5mA
No
Yes
Green LED = ON
No
Yes (Isolated from output)
No
Single wire connection (5 units max)
No
Yes
No
Yes (3)
HWS50-150: -10°C to +71°C, (-10 ~+50°C: 100%, +60°C: 60%, +71°C: 20%)
HWS300-1500: -10°C to +71°C, (-10 ~+50°C: 100%, derate linearly to 50% load from +50 to +71°C)
Guaranteed start up at -40°C (see specification sheets on website for details and derating)
-40 to +85°C
Operating: 30 - 90%RH (10 -90% on HWS300-1500), Non operating 10 - 95%RH
Convection
Internal fan
Input to Ground 2kVAC, Input to Output 3kVAC, Output to Ground 500VAC for 1 min.
>100MΩ at 25°C & 70%RH, Output to Ground 500VDC, >10M Output to remote on/off 100VDC
MIL-STD-810F 514.5 Category 4, 10 (HWS1500 Cat 4, figure 514.5C-1)
MIL-STD-810F 516.5 Category I, VI (HWS1500 <196.1m/s2)
UL60950-1, CSA60950-1, EN60950-1, EN50178, CE Mark
Complies with SEMI F47 (200VAC line only)
EN55011 / EN55022-B, FCC-B, VCCI-B (HWS1500 Class A)
IEC61000-4-2 (Level 2,3), -3, -4, -6, (Level 3), -5, -8 (Level 4), -11
280
450
500
1000
1600
3200
3800
1.04x3.23x4.72 1.1x3.23x6.3 1.46x3.23x6.3 2.4x3.23x6.5 3.94x3.23x6.5 5x3.2x9.5
5x3.25x11
Limited lifetime warranty (See TDK-Lambda’s terms & conditions)
(1) 100/200VAC input
(2) HWS300-600 2.5kVAC Input to ground
1-800-526-2324 • www.us.tdk-lambda.com/lp/
(3) 1-6V program voltage input to adjust output 20-120% (typical) of
nominal. See instruction manual for details & models with this feature.
(*) Class 1 Div 2 option (/RYHD suffix
63
Disclaimer: us.tdk-lambda.com/lp/legal.htm
HWS50-1500/HD Series
Output Ratings
Model
Voltage
HWS50-3/HD
3.3V
HWS100-3/HD
3.3V
HWS150-3/HD
3.3V
HWS300-3/HD
3.3V
HWS600-3/HD
3.3V
HWS1000-3/HD 3.3V
HWS1500-3/HD 3.3V
HWS50-5/HD
5V
HWS100-5/HD
5V
HWS150-5/HD
5V
HWS300-5/HD
5V
HWS600-5/HD
5V
HWS1000-5/HD
5V
HWS1500-5/HD
5V
HWS1000-6/HD
6V
HWS1000-7/HD 7.5V
HWS50-12/HD
12V
HWS100-12/HD 12V
HWS150-12/HD 12V
HWS300-12/HD 12V
HWS600-12/HD 12V
HWS1000-12/HD 12V
HWS1500-12/HD 12V
HWS50-15/HD
15V
HWS100-15/HD 15V
HWS150-15/HD 15V
HWS300-15/HD 15V
HWS600-15/HD 15V
HWS1000-15/HD 15V
HWS1500-15/HD 15V
HWS50-24/HD
24V
HWS100-24/HD 24V
HWS150-24/HD 24V
HWS300-24/HD 24V
HWS600-24/HD 24V
HWS1000-24/HD 24V
HWS1500-24/HD 24V
HWS1000-36/HD 36V
HWS1500-36/HD 36V
HWS50-48/HD
48V
HWS100-48/HD 48V
HWS150-48/HD 48V
HWS300-48/HD 48V
HWS600-48/HD 48V
HWS1000-48/HD 48V
HWS1500-48/HD 48V
HWS1000-60/HD 60V
Adjust
Max
Peak
Max
Load
Line
Ripple Overvoltage Efficiency
Range
Curr(A) Curr(A)4 Power(W) Reg(mV) Reg(mV) Noise(mV)
(V)
(typ)%1
2.97 - 3.96
10
33
40
20
120
4.13-4.95
76/78
2.97 - 3.96
20
66
40
20
120
4.13-4.95
78/81
2.97 - 3.96
30
99
40
20
120
4.13-4.95
78/81
2.64 - 3.96
60
198
30
20
120
4.13-4.95
74/77
2.64 - 3.96
120
396
30
20
120
4.13-4.95
75/78
2.64 - 3.96
200
660
40
20
120
4.12-4.62
71/73
2.64 - 3.96
300
990
60
36
150
4.12-4.62
72/75
4.0 - 6.0
10
50
40
20
120
6.25-7.25
82/84
4.0 - 6.0
20
100
40
20
120
6.25-7.25
83/86
4.0 - 6.0
30
150
40
20
120
6.25-7.25
83/86
4.0 - 6.0
60
300
30
20
120
6.25-7.25
79/82
4.0 - 6.0
120
600
30
20
120
6.25-7.25
80/83
4.0 - 6.0
200
1000
40
20
120
6.25-7
76/78
4.0 - 6.0
300
1500
60
36
150
6.25-7
77/81
4.8 - 7.2
167
1002
60
36
150
7.5-8.4
79/81
6.0 - 9.0
134
160
1005
60
36
150
9.37-10.5
80/82
9.6 - 14.4
4.3
51.6
96
48
150
15-17.4
81/83
9.6 - 14.4
8.5
102
96
48
150
15-17.4
83/86
9.6 - 14.4
13
156
96
48
150
15-17.4
83/86
9.6 - 14.4
27
324
72
48
150
15-17.4
80/83
9.6 - 14.4
53
636
72
48
150
15-17.4
80/83
9.6 - 14.4
88
100
1056
100
48
150
15-17.4
82/85
9.6 - 14.4
125
1500
72
48
150
15-17.4
82/85
12.0 - 18.0
3.5
52.5
120
60
150
18.8-21.8
81/83
12.0 - 18.0
7
105
120
60
150
18.8-21.8
83/86
12.0 - 18.0
10
150
120
60
150
18.8-21.8
83/86
12.0 - 18.0
22
330
90
60
150
18.8-21.8
80/83
12.0 - 18.0
43
645
90
60
150
18.8-21.8
81/84
12.0 - 18.0
70
80
1500
120
60
150
18.7-21.8
83/85
12.0 - 18.0
100
1500
90
60
150
18.7-21.8
83/87
19.2 - 28.8
2.2
52.8
192
96
150
30-34.8
82/84
19.2 - 28.8
4.5
108
192
96
150
30-34.8
84/87
19.2 - 28.8
6.5
156
192
96
150
30-34.8
85/88
19.2 - 28.8
14
16.5
336
144
96
150
30-34.8
82/85
19.2 - 28.8
27
31
648
144
96
150
30-34.8
82/85
19.2 - 28.8
46
58.5
1104
150
96
150
30-34.8
85/87
19.2 - 28.8 65/70 (1)
105
1560
144
96
200
30-34.8
84/88
28.8 - 43.2
30.7
39
1104
150
144
200
45-49.7
85/88
28.8 - 43.2 42/46.5(2)
70
1512
150
144
200
45-49.7
84/88
38.4 - 52.8
1.1
52.8
384
192
200
55.2-64.8
83/85
38.4 - 52.8
2.1
100.8
384
192
200
55.2-64.8
84/87
38.4 - 52.8
3.3
158.4
384
192
200
55.2-64.8
85/88
38.4 - 52.8
7
336
288
192
350
55.2-64.8
82/85
38.4 - 52.8
13
624
288
192
350
55.2-64.8
83/86
38.4 - 52.8
28
29.2
1104
300
192
200
55.2-60
86/88
38.4 - 52.8
32
1536
288
192
200
55.2-64.8
86/90
48.0 - 66.0
18.4
23.4
1104
360
240
400
69-75
85/88
(4) 200-265VAC Input, 10s maximum on time, 35% duty cycle
Options
Other Industrial Products
Suffix
Blank
LZSA
DPP, DLP, DSP
PFE
/HDA
/RYHD
Description
No Cover (HWS50-150 Only)
HWS300-1500 the cover is fitted as standard
The cover option for HWS50-150 is special order only
HWS300-1500 the cover is fitted as standard
ISA 12.12.01 (UL1604) - Class 1 Div 2 with dry contact relay
DC Good signal (300W, 600W and 1500W 24V output models
only, no remote on/off function.)
1-800-526-2324 • www.us.tdk-lambda.com/lp/
500W to 1500W Single output
10W to 960W DIN Rail Mount
300 to 1000W AC-DC Power Models
For Additional Information, please visit
us.tdk-lambda.com/lp/products/hws-series.htm
64
Revision B4: Nov 2011
Similar pages