Cooper CLPT-DF Pt medium voltage fuses for potential and small power transformer Datasheet

Technical Data 6002
Effective March 2016
Supersedes December 2015
BUSSMANN
SERIES
PT Medium voltage fuses for potential and
small power transformers
Features and benefits
Description:
•
Bussmann® series Indicating and nonindicating E-Rated, current-limiting, medium
voltage fuses for potential, small power and
control transformers.
Contents
Description
•
Low amp, current-limiting E-Rated PT
medium voltage fuses are general purpose
fuses defined by their melting time-current
characteristic that permit their electrical
interchangeability with other fuses of the
same E Rating.
•
E-Rated general purpose fuses must have
a current responsive element that will melt
in 300 seconds at an RMS current within
the range of 200% to 240% of the fuse’s
nameplate current rating, fuse refill, or link
per ANSI C37.46 for fuses rated 100E or less.
•
PT fuses are physically dimensioned for easy
installation in existing hardware.
•
Space saving size eases design
considerations for new installations.
•
Current-limiting fuses provide positive
interruption even on low fault currents.
The fuse limits the magnitude of
electromechanical stresses in the protected
apparatus.
•
These fuses are in a self-contained, nonventing package for installation indoors or
outdoors in an enclosure.
•
Available in indicating and non-indicating
versions.
•
Open fuse indicator speeds troubleshooting
by providing a positive visual indication of
fuse operation.
Page
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.475kV fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
3.6kV fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
5.5kV fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . 10-26
7.2kV fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . 27-29
8.3kV fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . 30-39
12kV fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-42
15.5kV fuses. . . . . . . . . . . . . . . . . . . . . . . . . . 43-52
17.5kV fuses . . . . . . . . . . . . . . . . . . . . . . . . . . 53-54
24kV fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . 55-56
25.5kV fuses. . . . . . . . . . . . . . . . . . . . . . . . . . 57-60
36kV fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . 61-62
38kV fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . 63-69
Fuse mountings. . . . . . . . . . . . . . . . . . . . . . . 70-71
Typical applications:
•
Primary protection of:
• Medium voltage potential transformers
•
Small medium voltage service
transformers
•
Small medium voltage control
transformers.
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
E-Rated PT medium voltage fuses
Catalog symbols (by maximum voltage rating):
•
•
•
•
•
•
2.475kV
• 2NCLPT-_
3.6kV
• 3.6ABCNA_
•
3.6ABWNA_
•
3.6CAV_
•
•
•
5CLPT-_E
•
5NCLPT-_E
•
5NCLPT-_E-A
•
5.5ABWNA_E
•
5.5AMWNA_E
•
5.5CAV_E
•
5.5CAVH_E
7.2kV
• 7.2ABWNA_
•
36kV
•
36ABGNA_
• 36CAV_
•
38kV
• 38CAV_E
•
38CAVH_E
•
38CLPT-_E
Ratings*:
•
Volts
• 2.4kV to 38kV
•
Amps
• 0.25 to 15A
•
Interrupting ratings
•
25 to 80kA RMS Sym
* See catalog number tables for voltages, ampacities and interrupting ratings
by catalog number.
•
7.2ABCNA_
•
7.2AMWNA_E
Agency information:
•
7.2CAV_
•
8.3kV
• 8CLPT-_E-A
•
8CLPT-_E-B
•
8NCLPT-_E
•
8NCLPT-_E-A
•
8NCLPT-_E-B
12kV
• 12ABCNA_
12CAV_
15.5kV
• 15CLPT-_E
•
15NCLPT-_E-A
•
15NCLPT-_E-B
•
15.5CAV_E
•
15.5CAVH_E
17.5kV
•
17.5ABGNA_
•
17.5CAV_
24kV
• 24ABGNA_
•
2
25.5kV
• 25CLPT-_E
5.5kV
• JCW-_
•
•
•
24CAV_
Eaton.com/bussmannseries
Those PT fuses conforming to the requirements for E-Rating
meet the performance characteristics of ANSI C37.46
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
2.475kV maximum system voltage
Dimensions - in (mm)
Amp rating Length A
Diameter B
0.25
0.5
1 4.5 (114)
0.8 (20)
2
5
Clip centers C
3.9 (99)
Catalog No. (Interrupting rating - kA)
Indicating
Non-indicating Recommended fuseclip
—
2NCLPT-.25E (63)
—
2NCLPT-.5E (63)
—
2NCLPT-1E (40) 1A1837
—
2NCLPT-2E (40)
—
2NCLPT-5E (25)
Dimensions (see catalog number tables for values)
C
B
A
Recommended fuseclip and fuse block:
Description
Cat. No.
Open fuseclip for 0.8 (20mm) dia. fuses
1A1837
Single-pole open fuse block with #10-32 phil-slot screw
terminals rated 2500V, 5A maximum and 63kA withstand
rating
PTFB-2500-JCD
Eaton.com/bussmannseries
3
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
2.47kV time-current curves — minimum melting for 2NCLPT-_E
1/4A
1/2A
1A
2A
Time in seconds
5A
Current in apps
2NCLPT-_E
4
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
2.47kV time-current curves — total clearing for 2NCLPT-_E
1/4A
1/2A
1A
2A
Time in seconds
5A
Current in apps
2NCLPT-_E
Eaton.com/bussmannseries
5
Technical Data 6002
Effective March 2016
PT medium voltage fuses for potential and
small power transformers
Peak instantaneous let-through current in kilo-amperes
2.47kV peak let-through curves for 2NCLPT-_E
5A
1A & 2A
1/2A
1/4A
Available current in apps
2NCLPT-_E
6
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
3.6kV maximum system voltage
Amp rating
2
3.15
3.15
6.3
6.3
10
Dimensions - in (mm)
Length A
Diameter B
8.7 (221)
1.6 (41)
5.6 (142)
1 (25)
7.7 (195)
1 (25)
5.6 (142)
1 (25)
Clip centers C
7.6 (193)
4.4 (112)
6.5 (165)
4.4 (112)
7.7 (195)
6.5 (165)
1 (25)
Catalog No. (Interrupting
Indicating
—
—
—
—
—
—
rating - kA)
Non-indicating
3.6CAV2 (50)
3.6ABWNA3.15 (50)
3.6ABCNA3.15 (50)
3.6ABWNA6.3 (50)
3.6ABCNA6.3 (50)
3.6ABCNA10 (50)
Recommended fuseclip
1A1837
A3354705
Dimensions (see catalog number tables for values)
C
B
A
Recommended fuseclips:
Description
Cat. No.
Open fuseclip for 1.0 (25.4mm) dia. fuses
A3354705
Open fuseclip for 1.56 (39.7mm) / 1.6 (40.6mm) dia. fuses
1A0835
Eaton.com/bussmannseries
7
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
3.6kV Time-current curves — minimum melting for 3.6CAV_, 3.6ABC_ and 3.6ABW_
2A (CAV)
Time in seconds
3.15A (ABC/ABW)
6.3A (ABC/ABW)
10A (ABC/ABW)
RMS symmetrical prospective current in amperes
3.6ABC_, 3.6ABW_, 3.6CAV_
8
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
3.6kV Peak let-through curves for 3.6ABC_ and 3.6ABW_
Eaton.com/bussmannseries
9
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
5.5kV maximum system voltage
Amp rating
0.5
0.5
0.5
0.5
1
1
1
1
1.5
2
2
2
3
3
Dimensions - in (mm)
Length A
5.6 (142)
5.6 (142)
7.4 (188)
9.5 (241)
5.6 (142)
5.6 (142)
7.4 (188)
9.5 (241)
9.5 (241)
5.6 (142)
5.6 (142)
7.4 (188)
5.6 (142)
5.6 (142)
Diameter B
0.8 (20)
1 (25)
1.6 (41)
1.6 (41)
1 (25)
0.8 (20)
1.6 (41)
1.6 (41)
1.6 (41)
1 (25)
0.8 (20)
1.6 (41)
1 (25)
0.8 (20)
3 9.5 (241)
3
4
4
5
5
5
5
10
15
Clip centers C
4.8 (122)
4.4 (112)
6.2 (157)
8.1 (206)
4.4 (112)
4.8 (122)
6.2 (157)
8.1 (206)
8.1 (206)
4.4 (112)
4.8 (122)
6.2 (157)
4.4 (112)
4.8 (122)
1.6 (41) 8.1 (206)
7.4 (188)
5.6 (142)
7.3 (185)
9.5 (241)
5.6 (142)
5.6 (142)
7.3 (185)
9.5 (241)
7.4 (188)
1.6
0.8
1.6
1.6
1
0.8
1.6
1.6
1.6
(41)
(20)
(41)
(41)
(25)
(20)
(41)
(41)
(41)
6.2
4.8
5.9
8.1
4.4
4.8
5.9
8.1
6.2
(157)
(122)
(150)
(206)
(112)
(122)
(150)
(206)
(157)
Catalog No. (Interrupting rating - kA)
Indicating
Non-indicating
— 5.5AMWNA0.5E (50)
—
5.5ABWNA0.5E (50)
5.5CAVH0.5E (63)
JCW-1/2E (40)
5CLPT-.5E (80)†
5NCLPT-.5E-A (63)
—
5.5ABWNA1E (50)
— 5.5AMWNA1.0E (50)
5.5CAVH1E (63)
JCW-1E (40)
5CLPT-1E (80)†
5NCLPT-1E-A (63)
5CLPT-1.5E (80)†
—
—
5.5ABWNA2E (50)
— 5.5AMWNA2.0E (50)
5.5CAVH2E (63)
JCW-2E (40)
—
5.5ABWNA3E (50)
— 5.5AMWNA3.0E (50)
Recommended fuseclip
1A1837
A3354705
1A0835
A3354705
1A1837
1A0835
1A0835
A3354705
1A1837
1A0835
A3354705
1A1837
5CLPT-3E (80)
—
1A0835
—
—
5CLPT-5E (80)
—
—
—
5CLPT-10E (80)
—
JCW-3E (40)
5.5AMWNA4.0E (50)
JCW-4E (40)
—
5.5ABWNA5E (50)
5.5AMWNA5.0E (50)
JCW-5E (40)
—
5.5CAV15E (63)
1A0835
1A1837
1A0835
1A0835
A3354705
1A1837
1A0835
1A0835
† Does not comply with ANSI C37.46 for “E” rating.
CLPT Type mountings and hardware 5.5kV maximum (4.8kV nominal)*
Fuse mounting
Amp rating
type**
CLPT and NCLPT-A Mounting
Non-disconnect
0.5–10
Disconnect†
BIL
(kV)
60
60
*
Catalog number
Mounting (including live parts, end fittings)***
Live parts (including
Porcelain insulator
Glass-polyester insulator
end fittings)***
End fittings
(disconnect only)
5CLPT-PNM-A
5CLPT-PDM-A
—
CLPT-DF
5CLPT-GNM-A
5CLPT-GDM-A
CLPT-NL
CLPT-DL
Refers to 5CLPT and 5NCLPT-A fuses only.
** See page 70 for dimensions and diagrams of typical mounting.
*** End fittings supplied only when required.
†
Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
10
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
Dimensions (see catalog number tables for values)
C
B
Recommended fuseclips:
Indicator
Description
Cat. No.
Open fuseclip for 0.8 (20mm) dia. fuses
1A1837
Open fuseclip for 1.0 (25.4mm) dia. fuses
A3354705
Open fuseclip for 1.56 (39.7mm) / 1.6 (40.6mm) dia. fuses
1A0835
A
Eaton.com/bussmannseries
11
Technical Data 6002
Effective March 2016
5.5kV time-current curves — minimum melting for 5NCLPT-_-A
5NCLPT-_E-A
12
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
5.5kV time-current curves — total clearing for 5NCLPT-_-A
5NCLPT-_E-A
Eaton.com/bussmannseries
13
Technical Data 6002
Effective March 2016
5.5kV peak let-through curves for 5NCLPT-_-A
5NCLPT-_E-A
14
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
5.5kV time-current curves — minimum melting for 5NCLPT_
0.5A
1A
2A
3A
4A
5A
5NCLPT-_E
Eaton.com/bussmannseries
15
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
5.5kV time-current curves — total clearing for 5NCLPT_
0.5A
1A
2A
3A
4A
5A
5NCLPT-_E
16
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
5.5kV peak let-through curves for 5NCLPT_
5A
4A
3A
2A
1A
0.5A
5NCLPT-_E
Eaton.com/bussmannseries
17
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
5.5kV time-current curves — minimum melting for 5CLPT_
0.5A
1A
1.5A
3A
5A
10A
5CLPT-_E
18
Eaton.com/bussmannseries
0.5, 1 and 1.5 A fuse melt times in the dotted line region
may not be assured due to manufacturing variations.
The dotted lines show nominal operation. Some individual
fuses may not open until current at 10-second mark is applied.
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
5.5kV Time-current curves — total clearing for 5CLPT_
Times in seconds
0.5A
1A
1.5A
3A
5A
10A
5CLPT-_E
Eaton.com/bussmannseries
19
Technical Data 6002
Effective March 2016
PT medium voltage fuses for potential and
small power transformers
5.5kV peak let-through curves for 5CLPT_
10A
5A
1A & 1.5A
3A
0.5A
5CLPT-_E
20
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
2A (CAVH)
1A (CAVH)
0.5A (CAVH)
5.5kV time-current curves — minimum melting for 5.5CAV_ and 5.5CAVH_
15A (CAV)
5.5CAV_, 5.5CAVH_
Eaton.com/bussmannseries
21
Technical Data 6002
Effective March 2016
PT medium voltage fuses for potential and
small power transformers
5.5kV time-current curves — total clearing for 5.5CAV_
15A (CAV)
5.5CAV_
22
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
5.5kV peak let-through curves for 5.5CAVH_
2A (CAVH)
1A (CAVH)
0.5A (CAVH)
5.5CAVH_
Eaton.com/bussmannseries
23
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
5A (ABW)
2A (ABW)
3A (ABW)
1A (ABW)
0.5A (ABW)
5.5kV time-current curves — minimum melting for 5.5ABW_ and 5.5AMW_
0.5A (AMW)
1A (AMW)
2A (AMW)
3A (AMW)
4A (AMW)
5A (AMW)
5.5ABW_, 5.5AMW_
24
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
5A (ABW)
2A (ABW)
3A (ABW)
1A (ABW)
0.5A (ABW)
5.5kV time-current curves — total clearing for 5.5ABW_ and 5.5AMW_
0.5A (AMW)
1A (AMW)
2A (AMW)
3A (AMW)
4A (AMW)
5A (AMW)
5.5ABW_, 5.5AMW_
Eaton.com/bussmannseries
25
Technical Data 6002
Effective March 2016
PT medium voltage fuses for potential and
small power transformers
5.5kV peak let-through curves for 5.5ABW_ and 5.5AMW_
5A (ABW)
3A (ABW)
2A (ABW)
1A (ABW)
5A (AMW)
4A (AMW)
0.5A (ABW)
3A (AMW)
2A (AMW)
1A (AMW)
0.5A (AMW)
5.5ABW_, 5.5AMW_
26
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
7.2kV maximum system voltage
Amp rating
0.5
1
2
2
3
3.15
3.15
4
4
5
6
6.3
6.3
10
Dimensions - in (mm)
Length A
5.6 (142)
5.6 (142)
5.6 (142)
8.7 (221)
5.6 (142)
5.6 (142)
7.7 (195)
5.6 (142)
8.7 (221)
5.6 (142)
8.7 (221)
5.6 (142)
7.7 (195)
8.7 (221)
Diameter B
0.8 (20)
0.8 (20)
0.8 (20)
1.6 (41)
0.8 (20)
1 (25.4)
1 (25.4)
0.8 (20)
1.6 (41)
0.8 (20)
1.6 (41)
1 (25.4)
1 (25.4)
1.6 (41)
Clip centers C
4.8 (122)
4.8 (122)
4.8 (122)
7.5 (190)
4.8 (122)
4.4 (112)
6.5 (165)
4.8 (122)
7.5 (190)
4.8 (122)
7.5 (190)
4.4 (112)
6.5 (165)
7.5 (190)
Catalog No. (Interrupting rating - kA)
Indicating
Non-indicating
—
7.2AMWNA0.5E (50)
—
7.2AMWNA1.0E (50)
—
7.2AMWNA2.0E (50)
—
7.2CAV2 (63)
—
7.2AMWNA3.0E (50)
—
7.2ABWNA3.15 (45)
—
7.2ABCNA3.15 (45)
—
7.2AMWNA4.0E (50)
—
7.2CAV4 (63)
—
7.2AMWNA5E (50)
—
7.2CAV6 (63)
—
7.2ABWNA6.3 (45)
—
7.2ABCNA6.3 (45)
—
7.2CAV10 (63)
Recommended fuseclip
1A1837
1A0835
1A1837
A3354705
1A1837
1A0835
1A1837
1A0835
A3354705
1A0835
Dimensions (see catalog number tables for values)
C
B
A
Recommended fuseclips
Description
Cat. No.
Open fuseclip for 0.8 (20mm) dia. fuses
1A1837
Open fuseclip for 1.0 (25.4mm) dia. fuses
A3354705
Open fuseclip for 1.56 (39.7mm) / 1.6 (40.6mm) dia. fuses
1A0835
Eaton.com/bussmannseries
27
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
7.2kV time-current curves — minimum melting for 7.2ABW_ and 7.2CAV_
2A (CAV)
4A (CAV)
6A (CAV)
10A (CAV)
6.3A (ABW)
3.15A (ABW)
7.2ABW_, 7.2CAV_
28
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
7.2kV peak let-through curves for 7.2ABW_
Eaton.com/bussmannseries
29
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
8.3kV maximum system voltage
Amp rating
0.5
1
1
2
2
3
4
5
5
10
Dimensions - in (mm)
Length A
Diameter B
9.5 (241)
1.6 (41)
5 (127)
1.1 (28)
9.5 (241)
1.6 (41)
8 (203)
0.8 (20)
9.5 (241)
1.6 (41)
12.9 (328)
1.6 (41)
8 (203)
0.8 (20)
5 (127)
1.1 (28)
12.9 (328)
1.6 (41)
12.9 (328)
1.6 (41)
Clip centers C
8.1 (206)
4 (102)
8.1 (206)
7.2 (183)
8.1 (206)
11.5 (292)
7.2 (183)
4 (102)
11.5 (292)
11.5 (292)
Catalog No. (interrupting rating - kA)
Indicating
Non-indicating
8CLPT-.5E-A (80)†
8NCLPT-.5E-A (50)
—
8NCLPT-1E (50)
—
8NCLPT-1E-A (50)
—
8NCLPT-2E (25)
—
8NCLPT-2E-A (50)
8CLPT-3E-B (80)
8NCLPT-3E-B (50)
—
8NCLPT-4E (25)
—
8NCLPT-5E (50)
8CLPT-5E-B (50)
8NCLPT-5E-B (50)
8CLPT-10E-B (50)
8NCLPT-10E-B (50)
Recommended fuseclip
1A0835
A3354705
1A0835
1A1837
1A0835
1A1837
A3354705
1A0835
† Does not comply with ANSI C37.46 for “E” rating.
CLPT type mountings and hardware 8.3kV maximum (7.2kV nominal)*
Catalog number
Amp rating
0.5–2
3–10
*
**
***
†
Fuse mounting
type**
Non-disconnect
Disconnect†
Non-disconnect
Disconnect†
BIL
(kV)
75
75
75
75
Mounting (including live parts, end fittings)***
Porcelain insulator
Glass-polyester insulator
Live parts (including End fittings
end fittings)***
(disconnect only)
8CLPT-PNM-A
8CLPT-PDM-A
8CLPT-PNM-B
8CLPT-PDM-B
CLPT-NL
CLPT-DL
CLPT-NL
CLPT-DL
8CLPT-GNM-A
8CLPT-GDM-A
8CLPT-GNM-B
8CLPT-GDM-B
Refers to 8CLPT and 8NCLPT-A or -B fuses only.
See page 70 for dimensions and diagrams of typical mounting.
End fittings supplied only when required.
Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
Dimensions (see catalog number tables for values)
C
Indicator
B
A
Recommended fuseclips:
Description
Cat. No.
Open fuseclip for 0.8 (20mm) dia. fuses
1A1837
Open fuseclip for 1.0 (25.4mm) dia. fuses
A3354705
Open fuseclip for 1.56 (39.7mm) / 1.6 (40.6mm) dia. fuses
1A0835
30
—
CLPT-DF
—
CLPT-DF
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
8.3kV time-current curves — minimum melting for 8NCLPT_
1A
5A
2A
4A
8NCLPT-_E
Curve 59887102
July 2002
Reference # 628852, 598871
Curve 56357206
July 2002
Eaton.com/bussmannseries
31
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
8.3kV time-current curves — total clearing for 8NCLPT_
1A
5A
2A
4A
8NCLPT-_E
32
Eaton.com/bussmannseries
Curve 59887104
July 2002
Reference # 598871
Curve 59883706
July 2002
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
8.3kV peak let-through curves for 8NCLPT_
5A
4A
8NCLPT-_E
Curve 63933703
July 2001
Reference # 639337
2A
1A
Curve 63933704
July 2001
Reference # 639337
Eaton.com/bussmannseries
33
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
8.3kV time-current curves — minimum melting for 8CLPT_
0.5A
3A
5A
10A
8CLPT-_E
34
Eaton.com/bussmannseries
0.5 A fuse melt time in the dotted line region may not be
assured due to manufacturing variations. The dotted lines
show nominal operation. Some individual fuses may not
open until current at 10-second mark is applied.
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
8.3kV time-current curves — total clearing for 8CLPT_
0.5A
3A
5A
10A
8CLPT-_E
Eaton.com/bussmannseries
35
Technical Data 6002
Effective March 2016
PT medium voltage fuses for potential and
small power transformers
8.3kV peak let-through curves for 8CLPT_
10A
5A
3A
0.5A
8CLPT-_E
36
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
8.3kV time-current curves — minimum melting for 8NCLPT-_E-A/B
0.5A
1A
2A
3A
5A
10A
8NCLPT-_E-A/B
Eaton.com/bussmannseries
37
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
8.3kV time-current curves — total clearing for 8NCLPT-_E--A/B
0.5A
1A
2A
3A
5A
10A
8NCLPT-_E-A/B
38
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
8.3kV peak let-through curves for 8NCLPT-_E-A/B
10A
5A
3A
1A & 2A
0.5A
8NCLPT-_E-A/B
Eaton.com/bussmannseries
39
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
12kV maximum system voltage
Dimensions - in (mm)
Catalog No. (Interrupting rating - kA)
Length A
Diameter B Clip centers C
Indicating
Non-indicating
2
8.7 (221)
1.6 (41)
7.5 (190) —
12CAV2 (40)
3.15
7.7 (195)
1 (25)
6.5 (165) —
12ABCNA3.15 (45)
Amp rating
Dimensions (see catalog number tables for values)
C
B
A
Recommended fuseclips:
Description
Cat. No.
Open fuseclip for 1.0 (25.4mm) dia. fuses
A3354705
Open fuseclip for 1.56 (39.7mm) / 1.6 (40.6mm) dia. fuses
1A0835
40
Eaton.com/bussmannseries
Recommended fuseclip
1A0835
A3354705
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
12kV time-current curves — minimum melting for 12ABC_ and 12CAV_
2A (CAV)
3.15A (ABC)
12ABC_, 12CAV_
Eaton.com/bussmannseries
41
Technical Data 6002
Effective March 2016
12kV peak let-through curves for 12ABC_
42
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
15.5kV maximum system voltage
Amp rating
0.5
1
2
3
3
3
5
5
7
10
Dimensions - in (mm)
Catalog No. (Interrupting rating - kA)
Length A
Diameter B Clip centers C
Indicating
Non-indicating Recommended fuseclip
12.9 (328)
1.6 (41)
11.5 (292)
15.5CAVH0.5E (80)
15NCLPT-.5E-A (63)
12.9 (328)
1.6 (41)
11.5 (292)
15.5CAVH1E (80)
15NCLPT-1E-A (63)
12.9 (328)
1.6 (41)
11.5 (292)
15.5CAVH2E (80)
15NCLPT-2E-A (63)
12.9 (328)
1.6 (41)
11.5 (292)
—
15.5CAV3E (80)
17.6 (447)
1.6 (41)
16.1 (409)
—
15NCLPT-3E-B (63)
1A0835
17.6 (447)
1.6 (41)
16.1 (409)
15CLPT-3E-B (63)
—
12.9 (328)
1.6 (41)
11.5 (292)
—
15.5CAV5E (80)
17.6 (447)
1.6 (41)
16.1 (409)
15CLPT-5E-B (80)
15NCLPT-5E-B (63)
12.9 (328)
1.6 (41)
11.5 (292)
—
15.5CAV7E (80)
17.6 (447)
1.6 (41)
16.1 (409)
15CLPT-10E-B (50)
15NCLPT-10E-B (63)
CLPT Type mountings and hardware 15.5kV maximum (14.4kV nominal)
Amp rating
0.5–2
3–10
*
**
†
Fuse mounting
type*
Nondisconnect
Disconnect†
Nondisconnect
Disconnect†
BIL
(kV)
Catalog number
Mounting (Including live parts, end fittings)**
Porcelain insulator
Glass-polyester insulator
Live parts (including End fittings
end fittings)**
(disconnect only)
95
15CLPT-PNM-A
15CLPT-GNM-A
CLPT-NL
—
95
15CLPT-PDM-A
15CLPT-GDM-A
CLPT-DL
CLPT-DF
95
15CLPT-PNM-B
15CLPT-GNM-B
CLPT-NL
CLPT-DF
95
15CLPT-PDM-B
15CLPT-GDM-B
CLPT-DL
—
See page 70 for dimensions and diagrams of typical mounting.
End fittings supplied only when required.
Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
Dimensions (see catalog number tables for values)
C
Indicator
B
A
Recommended fuseclips:
Description
Cat. No.
Open fuseclip for 1.56 (39.7mm) / 1.6 (40.6mm) dia. fuses
1A0835
Eaton.com/bussmannseries
43
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
15.5kV time-current curves — minimum melting for 15CLPT_
0.5A
1A
1.5A
3A
5A
10A
15CLPT-_E
44
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
15.5kV time-current curves — total clearing for 15CLPT_
0.5A
1A
1.5A
3A
5A
10A
15CLPT-_E
Eaton.com/bussmannseries
45
Technical Data 6002
Effective March 2016
PT medium voltage fuses for potential and
small power transformers
15.5kV peak let-through curves for 15CLPT_
10A
5A
1A & 1.5A
3A
0.5A
15CLPT-_E
46
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
15.5kV time-current curves — minimum melting for 15NCLPT_
0.5A
1A
2A
3A
5A
10A
15NCLPT-_E
Eaton.com/bussmannseries
47
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
15.5kV Time-current curves — total clearing for 15NCLPT_
0.5A
1A
2A
3A
5A
10A
15NCLPT-_E
48
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
15.5kV Peak let-through curves for 15NCLPT_
10A
5A
3A
1A & 2A
0.5A
15NCLPT-_E
Eaton.com/bussmannseries
49
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
2A (CAVH)
1A (CAVH)
0.5A (CAVH)
15.5kV time-current curves — minimum melting for 15.5CAV_ and 15.5CAVH_
7A (CAV)
3A (CAV)
15.5CAV_, 15.5CAVH_
50
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
2A (CAVH)
1A (CAVH)
0.5A (CAVH)
15.5kV time-current curves — total clearing for 15.5CAVH_
7A (CAV)
3A (CAV)
15.5CAV_, 15.5CAVH_
Eaton.com/bussmannseries
51
Technical Data 6002
Effective March 2016
PT medium voltage fuses for potential and
small power transformers
15.5kV peak let-through curves for 15.5CAVH_
2A (CAVH)
1A (CAVH)
0.5A (CAVH)
15.5CAVH_
52
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
17.5kV maximum system voltage
Dimensions - in (mm)
Amp rating Length A
Diameter B
2
4
8.7 (221)
1.6 (41)
6
Clip centers C
7.5 (190)
10
Catalog No. (Interrupting rating - kA)
Indicating
Non-indicating Recommended fuseclip
—
17.5CAV2 (40)
—
17.5CAV4 (40)
1A0835
—
17.5CAV6 (40)
—
17.5CAV10 (40)
Dimensions (see catalog number tables for values)
C
B
A
Recommended fuseclips:
Description
Cat. No.
Open fuseclip for 1.56 (39.7mm) / 1.6 (40.6mm) dia. fuses
1A0835
Eaton.com/bussmannseries
53
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
17.5kV time-current curves — minimum melting for 17.5CAV_
2A (CAV)
4A (CAV)
6A (CAV)
10A (CAV)
7.5CAV_
54
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
24kV maximum system voltage
Dimensions - in (mm)
Amp rating Length A
Diameter B
2
3 13.49 (340)
1.6 (41)
4
Clip centers C
12.2 (310)
Catalog No. (Interrupting rating - kA)
Indicating
Non-indicating
—
24CAV2 (40)
—
24CAV3 (40)
—
24CAV4 (40)
Recommended fuseclip
1A0835
Dimensions (see catalog number tables for values)
C
B
A
Recommended fuseclips:
Description
Cat. No.
Open fuseclip for 1.56 (39.7mm) / 1.6 (40.6mm) dia. fuses
1A0835
Eaton.com/bussmannseries
55
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
24kV time-current curves — minimum melting for 24CAV_
2A (CAV)
3A (CAV)
4A (CAV)
24CAV_
56
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
25.5kV maximum system voltage
Amp rating
0.5
1
Length A
17.6 (447)
17.6 (447)
Dimensions - in (mm)
Diameter B
Clip centers C
1.6 (41)
16.1 (410)
1.6 (41)
16.1 (410)
Catalog No. (interrupting rating - kA)
Indicating
Non-indicating
25CLPT-.5E (44)†
—
25CLPT-1E (44)†
—
Recommended
fuseclip
1A0835
† Does not comply with ANSI C37.46 for “E” rating.
CLPT Type Mountings and Hardware 25.5kV Maximum (23kV Nominal)
Amp rating
0.5–1
*
**
†
Fuse mounting
type*
Non-disconnect
Disconnect
BIL
(kV)
150
150
Catalog number
Mounting (including live parts, end fittings)**
Porcelain insulator
Glass-polyester insulator
25CLPT-PNM-A
—
25CLPT-PDM-A
—
Live parts (including
end fittings)**
25CLPT-NL
25CLPT-DL
End fittings
(disconnect only)
—
CLPT-DF
See page 70 for dimensions and diagrams of typical mounting.
End fittings supplied only when required.
Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
Dimensions (see catalog number tables for values)
C
Indicator
B
A
Recommended fuseclips:
Description
Cat. No.
Open fuseclip for 1.56 (39.7mm) / 1.6 (40.6mm) dia. fuses
1A0835
Eaton.com/bussmannseries
57
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
25.5kV time-current curves — minimum melting for 25CLPT_
0.5A
1A
25CLPT-_E
58
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
25.5kV time-current curves — total clearing for 25CLPT_
0.5A
1A
25CLPT-_E
Eaton.com/bussmannseries
59
Technical Data 6002
Effective March 2016
PT medium voltage fuses for potential and
small power transformers
25.5kV Peak let-through curves for 25CLPT_
1A
0.5A
25CLPT-_E
60
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
36kV maximum system voltage
Amp rating
2
4
Length A
17.3 (439)
Dimensions - in (mm)
Diameter B
Clip centers C
1.6 (41)
16.1 (410)
Catalog No. (Interrupting rating - kA)
Indicating
Non-indicating
—
36CAV2 (40)
—
36CAV4 (40)
Recommended
fuseclip
1A0835
Dimensions (see catalog number tables for values)
C
B
A
Recommended fuseclips:
Description
Cat. No.
Open fuseclip for 1.56 (39.7mm) / 1.6 (40.6mm) dia. fuses
1A0835
Eaton.com/bussmannseries
61
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
36kV Time-current curves — minimum melting for 36CAV_
2A (CAV)
4A (CAV)
36CAV_
62
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
38kV maximum system voltage
Amp rating
0.5
0.5
1
2
4
Dimensions - in (mm)
Length A
Diameter B
17.3 (439)
1.6 (41)
18.6 (472)
1.6 (41)
17.3 (439)
1.6 (41)
17.3 (439)
1.6 (41)
17.3 (439)
1.6 (41)
Clip centers C
16.1 (409)
17.1 (434)
16.1 (409)
16.1 (409)
16.1 (409)
Catalog No. (interrupting rating - kA)
Indicating
Non-indicating Recommended fuseclip
38CAVH0.5E (38)
—
38CLPT-0.5E (44)†
—
38CAVH1E (38)
— 1A0835
38CAVH2E (38)
—
—
38CAV4E (38)
† Does not comply with ANSI C37.46 for “E” rating.
CLPT Type Mountings and Hardware 38kV Maximum (34.5kV Nominal)
Amp rating
0.5
Catalog number
Fuse mounting Mounting (including Live Parts, End Fittings)*
type
Porcelain insulator
Glass-polyester insulator
Disconnect†
Not applicable
Not applicable
Non-disconnect Not applicable
Not applicable
Live Parts
(including end fittings)*
25CLPT-NL
25CLPT-DL
End fittings
(disconnect only)
CLPT-DF
—
* End fittings supplied only when required.
† Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
Dimensions (see catalog number tables for values)
C
Indicator
B
A
Recommended fuseclip:
Description
Cat. No.
Open fuseclip for 1.56 (39.7mm) / 1.6 (40.6mm) dia. fuses
1A0835
Eaton.com/bussmannseries
63
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
2A (CAVH)
1A (CAVH)
0.5A (CAVH)
38kV time-current curves — minimum melting for 38CAV_ and 38CAVH
4A (CAV)
38CAV_, 38CAVH_
64
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
2A (CAVH)
1A (CAVH)
0.5A (CAVH)
38kV time-current curves — total clearing for 38CAV_ and 38CAVH
4A (CAV)
38CAV_, 38CAVH_
Eaton.com/bussmannseries
65
Technical Data 6002
Effective March 2016
PT medium voltage fuses for potential and
small power transformers
38kV peak let-through curves for 38CAVH
2A (CAVH)
1A (CAVH)
0.5A (CAVH)
38CAVH_
66
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
38kV time-current curves — minimum melting for 38CLPT_
0.5A
38CLPT_
Eaton.com/bussmannseries
67
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
38kV time-current curves — total clearing for 38CLPT_
0.5A
38CLPT_
68
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
38kV peak let-through curves for 38CLPT_
0.5A
38CLPT_
Eaton.com/bussmannseries
69
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
PT fuse mountings - in (mm)
Catalog number
Hole centers A Hole centers B
5.5kV Disconnect†
5CLPT-GDM-A
9.37 (238) 6 (152.4)
5CLPT-PDM-A
9.37 (238) 6 (152.4)
5.5kV Non-disconnect
5CLPT-GNM-A
9.37 (238)
5CLPT-PNM-A
9.37 (238)
8.3kV Disconnect†
8CLPT-GDM-A
9.37 (238)
8CLPT-GDM-B
9.37 (238)
8CLPT-PDM-A
9.37 (238)
8CLPT-PDM-B
12.74 (323.6)
8.3kV Non-disconnect
8CLPT-GNM-A
9.37 (238)
8CLPT-PNM-A
9.37 (238)
8CLPT-GNM-B
12.75 (323.8)
8CLPT-PNM-B
12.75 (323.8)
15.5kV Disconnect†
15CLPT-GDM-A
12.74 (323.6)
15CLPT-PDM-A
12.74 (323.6)
15CLPT-GDM-B
17.46 (443.5)
15CLPT-PDM-B
17.46 (443.5)
15.5kV Non-disconnect
15CLPT-GNM-A
12.74 (323.6)
15CLPT-PNM-A
12.74 (323.6)
15CLPT-GNM-B
17.46 (443.5)
15CLPT-PNM-B
17.46 (443.5)
25.5kV Disconnect†
25CLPT-PDM-A
19.12 (485.6)
25.5kV Non-disconnect
25CLPT-PNM-A
26.63 (676.4)
Overall length C Hole Inset D
Hole centers E
Contact height F Overall height G
18.63 (473.2) 0.75 (19)
18.63 (473.2) 0.75 (19)
1.75 (44.4)
1.75 (44.4)
4.5 (114.3)
4.5 (114.3)
9.56 (242.8)
9.56 (242.8)
60
60
6 (152.4)
6 (152.4)
18.63 (473.2) 0.75 (19)
18.63 (473.2) 0.75 (19)
1.75 (44.4)
1.75 (44.4)
4.5 (114.3)
4.5 (114.3)
6.94 (176.2)
6.94 (176.2)
60
60
6
6
6
6
(152.4)
(152.4)
(152.4)
(152.4)
18.63
18.63
18.63
22
(473.2)
(473.2)
(473.2)
(558.8)
0.75
0.75
0.75
0.75
(19)
(19)
(19)
(19)
1.75
1.75
1.75
1.75
(44.4)
(44.4)
(44.4)
(44.4)
7
7
7
7
(177.8)
(177.8)
(177.8)
(177.8)
12.06
12.06
12.06
12.06
(306.3)
(306.3)
(306.3)
(306.3)
75
75
75
75
6
6
6
6
(152.4)
(152.4)
(152.4)
(152.4)
18.63
18.63
22
22
(473.2)
(473.2)
(558.8)
(558.8)
0.75
0.75
0.75
0.75
(19)
(19)
(19)
(19)
1.75
1.75
1.75
1.75
(44.4)
(44.4)
(44.4)
(44.4)
7
7
7
7
(177.8)
(177.8)
(177.8)
(177.8)
9.44
9.44
9.44
9.44
(239.8)
(239.8)
(239.8)
(239.8)
75
75
75
75
6
6
6
6
(152.4)
(152.4)
(152.4)
(152.4)
22 (558.8)
22 (558.8)
26.63 (676.4)
26.63 (676.4)
0.75
0.75
0.75
0.75
(19)
(19)
(19)
(19)
1.75
1.75
1.75
1.75
(44.4)
(44.4)
(44.4)
(44.4)
7
7
7
7
(177.8)
(177.8)
(177.8)
(177.8)
12.06
12.06
12.06
12.06
(306.3)
(306.3)
(306.3)
(306.3)
95
95
95
95
6
6
6
6
(152.4)
(152.4)
(152.4)
(152.4)
22 (558.8)
22 (558.8)
26.63 (676.4)
26.63 (676.4)
0.75
0.75
0.75
0.75
(19)
(19)
(19)
(19)
1.75
1.75
1.75
1.75
(44.4)
(44.4)
(44.4)
(44.4)
7
7
7
7
(177.8)
(177.8)
(177.8)
(177.8)
9.44
9.44
9.44
9.44
(239.8)
(239.8)
(239.8)
(239.8)
95
95
95
95
7 (177.8)
26.63 (676.4) 0.75 (19)
1.75 (44.4)
12 (304.8)
17.06 (433.3)
150
7 (177.8)
26.63 (676.4) 0.75 (19)
1.75 (44.4)
12 (304.8)
14.75 (374.6)
150
† Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
70
BIL
kV
Eaton.com/bussmannseries
PT medium voltage fuses for potential and
small power transformers
Technical Data 6002
Effective March 2016
Disconnect mountings†
Non-disconnect mountings
G
G
F
D
F
D
E
E
C
A
A
C
E
E
D
B
D
B
† Disconnect mountings provide a means for fuse extraction only. Do not use
a disconnect mounting for load switching or fuse removal while energized.
Eaton.com/bussmannseries
71
Technical Data 6002
PT medium voltage fuses for potential and
small power transformers
Effective March 2016
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this
document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical
information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction
of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice,
any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible
applications.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
For Eaton’s Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2016 Eaton
All Rights Reserved
Printed in USA
Publication No. 6002 – BU-SB15149
March 2016
72
Eaton and Bussmann are valuable
trademarks of Eaton in the US and other
countries. You are not permitted to use the
Eaton trademarks without prior written
consent of Eaton.
Follow us on social media to get the
latest product and support information.
Similar pages