60W Single Output Industrial DIN Rail Power Supply DR-60 series Features : Universal AC input/Full range Protections: Short circuit / Overload / Over voltage Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 UL 508(industrial control equipment)approved Isolation class LED indicator for power on 100% full load burn-in test 3 years warranty SPECIFICATION MODEL DR-60-5 DR-60-12 DR-60-15 DR-60-24 DC VOLTAGE 5V 12V 15V 24V RATED CURRENT 6.5A 4.5A 4A 2.5A CURRENT RANGE 0 ~ 6.5A 0 ~ 4.5A 0 ~ 4A 0 ~ 2.5A RATED POWER 32.5W 54W 60W 60W 120mVp-p 120mVp-p 150mVp-p 11.1 ~ 13.2V 13.5 ~ 16.5V 21.6 ~ 26.4V RIPPLE & NOISE (max.) Note.2 80mVp-p OUTPUT INPUT VOLTAGE ADJ. RANGE VOLTAGE TOLERANCE Note.3 2.0% 1.0% 1.0% 1.0% LINE REGULATION 1.0% 1.0% 1.0% 1.0% LOAD REGULATION 1.0% 1.0% 1.0% 1.0% SETUP, RISE TIME 100ms, 30ms/230VAC HOLD UP TIME (Typ.) 100ms/230VAC VOLTAGE RANGE 88 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz 76% 1.2A/115VAC 0.8A/230VAC COLD START 18A/115VAC 36A/230VAC OVERLOAD 105 ~ 160% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 5.75 ~ 6.9V 13.8 ~ 16.2V 17.25 ~ 20.25V 27.6 ~ 32.4V WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE (Note 4) OTHERS 82% 83% 84% Protection type : Shut down o/p voltage, re-power on to recover -20 ~ +60 (Refer to output load derating curve) 20 ~ 90% RH non-condensing -40 ~ +85 , 10 ~ 95% RH 0.03%/ (0 ~ 50 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL60950-1, TUV EN60950-1 approved, Design refer to EN50178 I/P-O/P:3KVAC ISOLATION RESISTANCE I/P-O/P:100M Ohms / 500VDC / 25 / 70% RH EMI CONDUCTION & RADIATION Compliance to EN55011,EN55022 (CISPR22) Class B Compliance to EN61000-3-2,-3 HARMONIC CURRENT EMS IMMUNITY Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A MTBF 216.2K hrs min. MIL-HDBK-217F (25 78*93*56mm (W*H*D) 0.3Kg; 48pcs/15.4Kg/1.02CUFT DIMENSION PACKING NOTE 23ms/115VAC at full load 124 ~ 370VDC AC CURRENT (Typ.) INRUSH CURRENT (Typ.) OVER VOLTAGE EMC 200ms, 30ms/115VAC at full load EFFICIENCY (Typ.) PROTECTION SAFETY & 4.75 ~ 5.5V ) 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. File Name:DR-60-SPEC 2010-10-02 DR-60 60W Single Output Industrial DIN Rail Power Supply Mechanical Specification series Case No.918B Unit:mm 68 45 47 56 27.4 Terminal Pin No. Assignment Pin No. 5,6 7 8 Assignment AC/N AC/L +V Assignment -V LED +V ADJ. 3 Pin No. 1 2 3,4 46.5 46.5 93 12.2 5 5 5 8 6 5 4 3 7 37.75 78 35 5 ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 2 1 Block Diagram RECTIFIERS & FILTER EMI FILTER I/P POWER SWITCHING O.L.P. PWM CONTROL RECTIFIERS & FILTER +V -V DETECTION CIRCUIT O.V.P. Derating Curve 100 80 LOAD (%) 60 40 20 -20 0 10 20 30 40 50 60 70 (VERTICAL) AMBIENT TEMPERATURE ( ) File Name:DR-60-SPEC 2010-10-02