NI NICFP-RLY-423 Relay modules for compact fieldpoint Datasheet

Relay Modules for Compact FieldPoint
NEW
NI cFP-RLY-421, NI cFP-RLY-423
• 4 or 8 electromechanical relays
• 8 form A (SPST), RLY-421
• 4 form C (SPDT), RLY-423
• Switch 250 VAC, 120 VDC
• Switch 1.5 A, maximum
• 2,300 Vrms bank isolation for transient
overvoltage protection
• Hot swappable with autoconfiguration
• -40 to 55 °C operating range
(cFP-RLY-421)
• -40 to 60 °C operating range
(cFP-RLY-423)
Module
cFP-RLY-421
cFP-RLY-423
Output Channels
8
4
Maximum
Output Types
120 VDC, 250 VAC
120 VDC, 250 VAC
Output Current Rating
(See Specifications)
1.5 A
1.5 A
Separate Ground
Plane
per Channel
✓
✓
Overview
The National Instruments cFP-RLY-42x devices are versatile relay
modules for Compact FieldPoint that can be used to control digital
signals ranging from low voltage to 120 VDC and to 250 VAC. These
modules are commonly used to control indicator lights, motors, and
power circuits. All the modules include onboard diagnostics to ensure
trouble-free installation and maintenance. Similar relay modules are
available for FieldPoint, see page 572 for more information.
Relay Modules
NI cFP-RLY-42x modules provide built-in module-to-module
isolation to protect your Compact FieldPoint system and controller
from high voltage levels. Each channel on the RLY-42x uses
electrically isolated output relays so that each relay output has a
separate ground plane and each channel can be used with a different
voltage potential. Thus, you can connect one channel to a 24 VDC
and another channel on the same module to a 250 VAC.
All the channels on the relay modules feature LEDs that indicates the
output state of each channel. The modules all feature a maximum
switching frequency of 10 Hz (20 operations). Overall data throughput
depends on software loop speeds and network speeds.
Isolation
The cFP-RLY-42x modules feature optical bank isolation with
2,300 Vrms of breakdown isolation. In addition, the modules provide
double insulation for up to 250 Vrms of operational isolation. Compact
FieldPoint can safely be used in applications where hazardous voltages
are present with the cFP-CB-1 connector block. These Compact
FieldPoint modules do not have channel-to-channel isolation.
Power Requirements
Because the cFP-RLY-42x are high power consumption modules,
they could limit the number of I/O modules that you can connect to
a single network interface module. Controllers and network interface
modules supply up to 9 W to power I/O modules. The RLY-421
requires up to 2.5 W and the RLY-423 requires up to 1.5 W.
Field I/O Connections
Each input channel on the cFP-RLY-421 has two terminals:
1. Relay common terminal (IC)
2. Normally open terminal (NO)
Each channel of the cFP-RLY-423 has three terminals:
1. Normally open terminal (NO)
2. Normally closed terminal (NC)
3. Relay common terminal (IC)
Relay Modules for Compact FieldPoint
V
C
VSUP
NO
Sourcing
Load
Ordering Information
+
or
IC
–
AC
COM
Recommended Compact FieldPoint System Products
To next channel
cFP-RLY-421
V
NI cFP-RLY-421 ..........................................................777318-421
NI cFP-RLY-423 ..........................................................777318-423
C
NO
Load
+
NI cFP-2020 ..............................................................777317-2020
NI cFP-BP-4 ..................................................................778617-04
NI cFP-CB-1 ..................................................................778618-01
NI PS-5 Power Supply ..................................................778805-90
NI Developer Suite Professional Control Edition..........777906-03
IC
–
IC
BUY ONLINE!
NC
Load
Visit ni.com/info and enter cfprly421, and/or cfprly423.
VSUP
COM
cFP-RLY-423
Figure 1. Wiring Schematics for RLY Modules
Specifications
Typical for –40 to 60 °C unless otherwise noted.
Relay Characteristics
Number of channels
cFP-RLY-421 ...............................................
cFP-RLY-423 ...............................................
Relay type
cFP-RLY-421 ...............................................
cFP-RLY-423 ...............................................
Maximum switching capacity (resistive load)
AC ............................................................
DC ............................................................
(cFP-RLY-421) .............................................
(cFP-RLY-423) .............................................
8
4
Indicates on/off state of each contact
10.9 by 10.9 by 9.1 cm (4.3 by 4.3 by 3.6 in.)
136 g (4.8 oz)
156 g (5.5 oz)
Isolation Voltage
SPST, normally open, nonlatching
SPDT, nonlatching
1.5 A at 250 VAC
1.5 A at 0–35 VDC
1.5 A at 40 VDC
1 A at 55 VDC
0.4 A at 120 VDC
10 mA at 5 VDC
(120 VDC/250 VAC)
0.12 µA
8 µA
100 mΩ
Minimum switching load .................................
Off-state leakage current.................................
DC ............................................................
50/60 Hz ....................................................
On resistance (typical)......................................
Expected relay life
Mechanical ................................................ 2 x 107 operations/s (cFP-RLY-421)
1 x 107 operations/s (cFP-RLY-423)
Electrical (at 30 cpm)................................. 300,000 operations at 1.5 A, 35 VDC
100,000 operations at 1.5 A, 250 VAC
Operate time
cFP-RLY-421 ............................................... <10 ms
cFP-RLY-423 ............................................... <10 ms typ, 13 ms max
Release time
cFP-RLY-421 ............................................... <10 ms
cFP-RLY-423 ............................................... 5 ms typ, 7 ms max
Bounce time
cFP-RLY-421 ............................................... 10 ms max
cFP-RLY-423 ............................................... 3 ms typ, 6 ms max
Contact material
cFP-RLY-421 ............................................... Gold-plated silver cadmium oxide
cFP-RLY-423 ............................................... Silver cadmium oxide
Power Requirement (from Network Module)
cFP-RLY-421 ...................................................... 1.95 W
cFP-RLY-423 ...................................................... 1.0 W
Physical Characteristics
LED indicators
Power (green) ............................................ Indicates power is on and self-test passed
Ready (green)............................................. Indicates module is configured and ready
2
<0...7> or <0...3>........................................
Dimensions (including terminal base)..............
Weight
cFP-RLY-421 ...............................................
cFP-RLY-423 ...............................................
Maximum isolation voltage ............................. 250 Vrms, Installation Category II
Channel-to-channel isolation ........................... No isolation between channels
Transient overvoltage....................................... 2,300 Vrms
Environmental
FieldPoint modules are intended for indoor use only. For outdoor use, they must be mounted inside
a sealed enclosure.
Operating temperature..................................... -40 to 60 °C
Storage temperature ........................................ -55 to 85 °C
Relative humidity ............................................. 10 to 90%, noncondensing
Maximum altitude ............................................ 2,000 m; at higher altitudes the isolation voltage ratings
must be lowered.
Pollution Degree............................................... 2
Safety
This product is designed to meet the requirements of the following standards of safety for electrical
equipment for measurement, control, and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 3121-1, UL 61010C-1
• CAN/CSA C22.2 No. 1010.1
For UL, hazardous location, and other safety certifications, refer to the product label or to ni.com
Electromagnetic Compatibility
CE, C-Tick, and FCC Part 15 (Class A) Compliant
Emissions.......................................................... EN 55011 Class A at 10 m
FCC Part 15A above 1 GHz
Immunity........................................................... EN 61326:1997 +A2:2001, Table 1
For EMC compliance, you must operate this device with shielded cabling.
CE Compliance
This product meets the essential requirements of applicable European Directives, as amended for
CE Marking, as follows:
Low-Voltage Directive (safety)......................... 73/23/EEC
Electromagnetic Compatibility
Directive (EMC).......................................... 89/336/EEC
Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory compliance
information. To obtain the DoC for this product, visit ni.com/hardref.nsf/ and search by model number
or product line.
National Instruments • Tel: (800) 433-3488 • Fax: (512) 683-9300 • [email protected] • ni.com
Global Services and Support
NI has the services and support to meet your needs around the globe
and through the application life cycle – from planning and
development through deployment and ongoing maintenance – and
tailored for customer requirements in research, design, validation, and
manufacturing. We have direct operations in more than 37 countries
and distributors in another 12 locations. Our local sales and support
representatives are degreed engineers, ready to partner with you to find
solutions that best fit your needs.
Local Sales and Technical Support
In offices around the globe, our staff is local to the country so that
you have access to field engineers who speak your language and are
available to consult on your unique needs. We also have a worldwide
support organization staffed with Applications Engineers trained to
quickly provide superior technical assistance. Use our online Request
Support interface (ni.com/support) to define your question, then
speak to or e-mail an Applications Engineer, or access more than
14,000 worldwide measurement and automation professionals
within NI Developer Exchange Discussion Forums. ni.com/support
also provides immediate answers to your questions through self-help
troubleshooting, product reference, and application development
resources. For advanced technical support and software maintenance
services, sign up for Premier Support, a program that provides
expanded hours of support availability and
expedited phone/e-mail response time
(typically four business hours).
Professional Services
Our Professional Services team consists of National Instruments
Applications Engineers, NI Consulting Services, and the worldwide
National Instruments Alliance Partner Program (a network of 600
independent consultants and integrators). Our Professional Services
team can offer services ranging from basic start-up assistance and
collaborative development with
your engineers, to turnkey
system
integration
and
maintenance of your system.
In addition to our NI Alliance Partners, we have developed global
relationships with many industry partners that range from computer
software and hardware companies, such as Microsoft, Dell, Siemens,
and Tektronix. By collaborating with these companies, you receive a
complete spectrum of solutions – from components to turnkey
systems. Find the Alliance Partner directory at ni.com/alliance
Product Services
NI hardware products are warranted against defects in workmanship
and material for one year from the date of shipment. To help you
meet project life-cycle requirements, NI offers extended warranties
for an additional charge. NI provides complete repair services for our
products. Express repair and advanced replacement services are also
available. Or, order your software and hardware installed in PXI and
PXI/SCXI™ systems with NI Factory Installation Services.
Ordering Made Easy
Training and
Certification
CUSTOMER
NEEDS
NI recognizes that both initial
instruction and ongoing education
contribute to your success. NI provides a
variety of training alternatives, from selfpaced tutorials and interactive CDs, to worldwide
hands-on courses taught by experienced instructors – all designed so
that you can choose how to learn about our products. Further, NI offers
certifications acknowledging individual expertise in working with NI
products and technologies. Visit ni.com/training for more information.
Visit ni.com/products to browse product specifications, make
comparisons, or access technical representatives via online chat or
telephone. Worldwide customers can use a purchase order or credit
card to buy in local currency and receive direct shipments from local
NI offices. Our North American Customer Service Representatives
are available Monday through Friday between 7 a.m. and 7 p.m.
Central Time. Outside North America, please contact the NI office in
your country.
Order Status and Service Requests
National Instruments brings you real-time status on current orders at
ni.com/status Similarly, find out the status of open technical support
incidents or hardware repair requests at ni.com/support/servicereq
ni.com • (800) 433-3488
National Instruments • Tel: (512) 683-0100 • Fax: (512) 683-9300 • [email protected]
© 2003 National Instruments Corporation. All rights reserved. Product and company names listed are trademarks or trade names of their respective companies.