Power-One FXP1800-48G 1500 to 5400-watt front-end power solution Datasheet

FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
1500 to 5400-Watt
Front-End Power Solutions
Features
(1500 or 1800 Watts)
Front-Ends are available using either a front-mounted
AC receptacle (FNP models) or a rear-mounted AC
connector (FXP models).
I2C Management Software: All FNP/FXP front-ends can be
controlled via Power-One's GUI-driven I2C Management
software and an I2C-to-USB interface (P/N HZZ02002G). An
2
I C Programming Manual describes the complete range of
parameters that can be programmed to the FNP and
FXP1500/1800 front-ends. This manual is available by
searching on "FNP1500" at www.power-one.com.
•
•
•
•
•
•
•
•
•
RoHS compliant for all six substances
High density front-ends 15.2 to 18.3 W/in3
Wide input voltage range 85 to 264 VAC
12 V standby voltage, 1A per front-end
Highly efficient topology reduces operating costs
I2C interface status and control
I2C voltage and current limit setting
Analog output voltage setting
Overtemperature, output overvoltage, and output
overcurrent protection
ORing circuits for true redundant operation:
Vo1: ORing FETs; Vo2: ORing Diodes
Status LEDs: AC OK, DC OK, and
Fan Fail/Overtemperature Fail
•
•
Applications
•
•
•
•
Telecommunications
Data communications
Servers
Distributed power
FNR-3
Power Shelf
FNR-3 and FXR-3 shelves provide up to 5400 watts in a 19" rack.
(See the Rack section for power shelf details.)
Description
The FNP/FXP-1500/1800 are power-factor-corrected (PFC) front-ends which (depending on model type) provide a 12 VDC or 48
VDC (1500 or 1800 watt) output, and can be used in hot-swap redundant systems. Their very small dimensions allow
configuration of up to three units in a 1U rack. The FNP front-ends have a front-mounted AC receptacle and the FXP front-ends
have a rear-mounted AC connector. The highly-efficient thermal design with internal-fan cooling permits their use over wide
temperature ranges and provides very-high reliability.
Status information is provided with front panel LEDs, logic signals, and via an I2C management interface. In addition, the I2C bus
can enable the power supply, set high fan speed, adjust the output voltage, and set the output current limit. The FNP and
FXP-1500/1800's meet international safety standards and display the CE-Mark for the European Low Voltage Directive (LVD).
Power-shelf solutions provide rectification, system management, and power distribution, while maintaining high reliability and
offering flexibility for future expansion. The power shelves can be configured with up to three hot-swappable 1500 or 1800-watt
AC-DC front-ends.
DEC 12, 2006 revised to FEB 22, 2007
Page 1 of 15
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Model Selection
Model
FNP1500-12G
&
FXP1500-12G
FNP1500-48G
&
FXP1500-48G
FNP1800-48G
&
FXP1800-48G
1
2
Output 1
Output 2
Input voltage
VAC
1
auto selected
Vo1 nom
VDC
Io1 max
ADC
Vo2 nom
VDC
Io2 max
ADC
108 – 264
85 – 105
12
12
129 @ 11.64V
101.8 @ 11.78A
12
12
105 – 264
85 – 105
48
48
32.2
25.4
180 – 264
105 – 180
85 – 105
48
48
48
39.2
32.2
25.4
Rated power
W
Compatible
2
Shelf
1
1
1512
1212
FNR-3-12G &
FXR-3-12G
12
12
1
1
1512
1212
FNR-3-48G &
FXR-3-48G
12
12
12
1
1
1
1812
1512
1212
FNR-3-48G &
FXR-3-48G
The available output power is automatically adjusted depending on the input voltage.
1U standard racks are available from Power-One. See the Rack (Power Shelf) section of this data sheet for configurations and details.
Absolute Maximum Ratings
Stress in excess of the absolute maximum ratings may cause performance degradation, adversely effect long-term reliability, or
cause permanent damage to the converter.
Parameter
Input voltage
Conditions/Description
Min
Continuous
Transient, 60 ms max.
Operating ambient temperature
Storage temperature
Max
Unit
264
300
VAC
VAC
Vi min-Vi max, Io nom, cooling by internal fan
@ 100 % load
@ 50 % load
0
0
50
70
°C
°C
Non-Operating
-40
85
°C
Environmental, Mechanical, & Reliability Specifications
Parameter
Altitude
Relative humidity, non-condensing
Temperature coefficient
Shock
Sinusoidal vibration
Random vibration
MTBF
DEC 12, 2006 revised to FEB 22, 2007
Conditions/Description
Min
Nom
Operating
Non-Operating
Max
Unit
10 k
40 k
ASL Ft.
ASL Ft.
Operating
10
90
% RH
Storage
5
95
% RH
0 °C to 70 °C (after 15 min warm-up)
0.02
%/K
IEC/EN 60068-2-27, 11 ms
40
gpk
IEC/EN 60068-2-6
2-8 Hz
8-200 Hz
200-500 Hz
7.5
2
4
mil
gpk
gpk
10-2000 Hz
6.15
grms
Calculated per Bellcore (SR-332, Issue 1):
GB 25 °C
GB 25 °C (FNP1500-12G)
Demonstrated
Page 2 of 15
230
TBD
250
kh
kh
kh
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Safety Specifications
Maximum electric strength testing is performed in the factory according to EN 550116, IEC/EN 60950, and UL 60950.
Input-to-output electric strength tests should not be repeated in the field. Power-One will not honor any warranty claims resulting
from electric strength field tests.
Parameter
Conditions/description
Agency approvals
Insulation safety rating
Input to case
Input to output
Output to case
Electric strength test voltage
1
Min
Nom
Max
Unit
UL60950, (UL) CSA 60950 (cUL),
EN 60950(TÜV), CE Mark for LVD
Basic
Reinforced
Functional
Input to case
Input to output
Output to case
Output 1 to output 2
kVDC
kVDC
kVDC
kVDC
2.12
1
4.2
0.5
0.1
Subassemblies are pre-tested with 4.2 kVDC in accordance with EN50116 and IEC/EN60950.
EMC Specifications
Parameter
Description
Criterion
Electrostatic discharge
Electromagnetic field
Electrical fast transients/burst
Surge
Voltage dips and interruptions
RF conducted immunity
IEC/EN 61000-4-2, level 4
IEC/EN 61000-4-3, level 3
IEC/EN 61000-4-4, level 3
IEC/EN 61000-4-5, level 3
IEC/EN 61000-4-11
IEC/EN 61000-4-6
Emissions conducted
Emissions radiated
Harmonics
Voltage fluctuation and flicker
Voltage sag
CISPR 22/EN 55022/EN 61204
CISPR 22/EN 55022/EN 61204
IEC/EN 61000-3-2
IEC/EN 61000-3-3
SEMI F47-0200 (High Line 230V)
Performance criterion B
Performance criterion A
Performance criterion B
Performance criterion B
Performance criterion B or better
10 VAC, AM 80 %, 1 kHz
Performance criterion A
Class B
Class A
Class B
Pass
Pass
Input Specifications
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
Parameter
Conditions/description
Min
Nom
Max
Unit
VAC
Input voltage
85
230
264
Input frequency
47
50/60
63
Hz
Turn-on input voltage
Ramping up
79
-
85
VAC
Turn-off input voltage
Ramping down
70
-
78
VAC
50
Apk
Inrush current limitation
Hold-up time
115/230 VAC acc. ETS 300 132-1
< 100 ms
After last AC line peak ,Vi = 230 VAC, Po nom
20
Vi nom, Io nom
0.95
Power factor
Efficiency
Vi = 230 VAC, Io nom, TC = 25 °C
89
1
ms
W/VA
90
Max input current
Input connector
1
%
20
Arms
16A – 20 A / 250 VAC; according to IEC320 C19
87% for FNP1500-12
Input Connector Description (FXP1500/1800)
Protection Earth
P1
Phase
P2
L
Neutral
P3
N
DEC 12, 2006 revised to FEB 22, 2007
PE
Page 3 of 15
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Output Specifications, 12Vout Models
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
Parameter
Nominal output voltage
Output voltage set point accuracy
Output voltage trimming
Conditions/Description
Min
Io = 64.5 A
Vi = 230 VAC, Io1 = 65.5 A, TC = 25 °C
(Factory setting)
2
Adjustable via I C (Vo1 set)
Adjustable via Margin pin (R input)
Nom
12.05
+0.42
VDC
% Vo1 nom
7
6.2
12
13
Vo1 set
VDC
VDC
129.0
ADC
ADC
Io1 nom @ Vi =108 VAC – 264 VAC, Po 1.5 kW
Io1 nom @ Vi = 85 VAC – 105 VAC, Po 1.2 kW
129.0
101.8
Current
limit
output 1
FNP1500-12G
Io1 max @ Vi = 108 VAC – 264 VAC droop hiccup
Io1 max @ Vi = 85 VAC – 105 VAC droop hiccup
147.4
120..2
Static line regulation output 1
Static load
regulation
output 1
(droop
characteristic)
FNP1500-12G
Static load regulation
output 2 (droop characteristic)
Dynamic
load
regulation
Current
Share
Io2 nom @ Vi = 85 VAC – 265 VAC, Po 12 W
1.0
Io2 max @ Vi = 85 VAC – 265 VAC
1.5
Vi min - Vi max, 50 % Io nom, Ta = 25 °C
Vi = 230 V, 5 - 100 % Io nom
Full load to no load [0..129 A] at Vo set = 12V
dVo1 over the setting range [7 to 13V]
VDC
12
FNP1500-12G
Current limit output 2
Units
11.93
-0.42
Nominal
current
output 1
Nominal current output 2
Max
12
-0.5
11.64
-0.36
Full load to no load @ Vi = 85 VAC – 265 VAC
- 5.58
12
ADC
ADC
1.0
ADC
ADC
0.5
% Vo nom
12.36
+0.36
mV/A
VDC
VDC
0.4
VDC
Load change 50 % <─> 100 % Io nom, dIo/dt =1A/μs
Voltage deviation (droop + over- or undershoot)
FNP1500-12G
FNP1500-12G
-2
Max. recovery time to within 1% of Vo1 nom
2
% Vo nom
400
μs
Difference in current between two units for Vo1 above
10 % load.
FNP1500-12G
Start-up time
Output voltage ripple and noise
(Filter 10nF/10µF)
Remote sense
DEC 12, 2006 revised to FEB 22, 2007
12.9
Time required for output within regulation after initial
application of AC-input (Vi nom, Io nom)
after removal of inhibit (Vi nom, Io nom)
ADC
1.5
s
ms
Vi nom, Io nom, 20 MHz bandwidth
Vo1
Vo2
120
120
mVpp
mVpp
Total compensation for cable losses
500
mV
Page 4 of 15
100
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Output Specifications, 48Vout Models
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
Parameter
Conditions/Description
Min
Nom
Max
Units
Nominal output voltage Vo1
Io = 16.1 A
48
VDC
Nominal output voltage Vo2
Io = 0.5 A
12
VDC
Output voltage set point accuracy
Output voltage trimming
2
(via I C or with external resistor)
Nominal
current
output 1
Current
limit
output 1
Vi = 230 VAC, Io1 =16.1 A, TC = 25 °C
(47.8 - 48.2 VDC)
-0.5
+0.5
% Vo1 nom
Adjustable (44.16 to 51.84 VDC)
-8
+8
% Vo1 nom
FNP/FXP1500-48G
Io1 nom @ Vi =105 VAC – 264 VAC, Po 1.5 kW
Io1 nom @ Vi = 85 VAC – 105 VAC, Po 1.2 kW
32.2
25.4
FNP/FXP1800-48G
Io1 nom @ Vi =180 VAC – 264 VAC, Po 1.8 kW
Io1 nom @ Vi =105 VAC – 180 VAC, Po 1.5 kW
Io1 nom @ Vi = 85 VAC – 105 VAC, Po 1.2 kW
39.2
32.2
25.4
FNP/FXP1500-48G
Io1 max @ Vi = 105 VAC – 264 VAC
Io1 max @ Vi = 85 VAC – 105 VAC
droop hiccup
droop hiccup
36.8
30
ADC
ADC
FNP/FXP1800-48G
Io1 max @ Vi = 180 VAC – 264 VAC
Io1 max @ Vi = 105 VAC – 180 VAC
Io1 max @ Vi = 85 VAC – 105 VAC
droop hiccup
droop hiccup
droop hiccup
43.8
36.8
30
ADC
ADC
ADC
Nominal current output 2
Io2 nom @ Vi = 85 VAC – 264 VAC, Po 12 W
1.0
Current limit output 2
Io2 max @ Vi = 85 VAC – 264 VAC
1.5
Static line regulation output 1
FNP1500-48G
FXP1500-48G
Static load
regulation
output 1
(droop
characteristic)
FNP1800-48G
FXP1800-48G
Static load regulation
output 2 (droop characteristic)
Dynamic
load
regulation
-0.5
Vi = 230 V, 5-100 % Io nom
Vo : full load (32.2 ADC) to no load
46.54
Vi = 230 V, 5-100 % Io nom
Vo : full load (32.2 ADC) to no load
39.2
1.0
ADC
ADC
ADC
ADC
ADC
0.5
% Vo nom
90.1
48
49.44
mV/A
VDC
46.65
83.5
48
49.34
mV/A
VDC
Vi = 230 V, 5-100 % Io nom
Vo : full load (32.2 ADC) to no load
45.91
90.1
48
49.44
mV/A
VDC
Vi = 230 V, 5-100 % Io nom
Vo : full load (32.2 ADC) to no load
46.07
83.5
48
49.34
mV/A
VDC
Vi = 230 V, 5-100 % Io nom
Vo : full load (32.2 ADC) to no load
VDC
0.4
% Vo nom
Load change 50 % <─> 100 % Io nom, dIo/dt =1 A/μs
Voltage deviation (droop + over- or undershoot)
FNP/FXP1500-48G
-5
5
% Vo nom
FNP/FXP1800-48G
-5.7
5.7
% Vo nom
400
μs
All models
Current
Share
Vi min - Vi max, 50 % Io nom
ADC
ADC
Max. recovery time to within 1 % of Vo1 nom
Difference in current between two units for Vo1 above
10 % load.
FNP1500-48G
3.2
ADC
FXP1500-48G
5.7
ADC
8
ADC
1.5
s
ms
Vi nom, Io nom, 20 MHz bandwidth
Vo1
Vo2
480
120
mVpp
mVpp
Total compensation for cable losses
500
mV
FNP/FXP1800-48G
Start-up time
Output voltage ripple and noise
(Filter 10 nF/10 µF)
Remote sense
DEC 12, 2006 revised to FEB 22, 2007
Time required for output within regulation
after initial application of AC-input (Vi nom, Io nom)
after removal of inhibit
(Vi nom, Io nom)
Page 5 of 15
100
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Protection
Parameter
Conditions/Description
Input fuse
Min
Not user accessible
Inrush current limitation
Max
Unit
With NTCs
Output
No-load -, short circuit - and overload proof
Overvoltage protection latching
Tracking
Absolute
1
Overtemperature protection
1
Nom
25A, fast blow
115
Automatic power shutdown at TC
122
59.5
95
% Vo nom
V
°C
Remove input voltage to reset.
Control
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
Parameter
Conditions/Description
Status Indication
LEDs: DC OK (green), AC OK (green); fan fail and overtemperature (amber)
2
I C digital bus
Monitors alarm functions and sets parameters
PS present pin
Contact closure to logic ground ( internal pull-down resistor of 1 kΩ)
PS remote shutdown / Inhibit pin
TTL compatible signal, inhibited when open contact, high or at TTL logic “1”
Signal referenced to logic return (LRTN)
2
Power supply OK (I C)*
AC OK & DC OK & no overcurrent & no overtemperature & fans working
2
DC current fail (I C)*
Overcurrent on Io1
Provides a warning that the input power has failed at least 5 ms before the
output falls out of regulation (<90% Vo1 set).
Open collector signal with 20 mA pull-down capability, referenced to logic
return (LRTN). AC fail will go high or open during power fail condition
and will go low when input is within the operating range. A Power Fail
warning will turn off the green AC OK LED.
Internal undervoltage and overvoltage supervision of Vo1. Open collector signal with 20
mA pull-down capability, referenced to logic return (LRTN). DC fail will go high or open if
Vo1 is < 90% or > 110% of Vo1 set, measured in front of the ORing FETs. A green LED on
the front panel indicates normal operation. The LED will flash if in parallel operation Vo1 is
ok, but the unit is disabled.
AC fail / Power down warning
2
(I C & OC)*
DC fail / Output voltage fault
2
(I C & OC)*
2
2
1
Temperature warning (I C & OC)
2
1
2
1
DC voltage monitoring (I C)
Monitors the voltage Vo1 at the output connector.
Accuracy ± 0.45 V over setting range, temperature and load.
DC current monitoring (I C)
Monitors the output current Io1 : Accuracy ± 0.4A over the load range.
DC voltage trimming
2
1
(I C or external resistor)
Output voltage trimming Vo1: ± 8 % of Vo set
2
Setting accuracy over I C: ± 50mV at Vo nom, ± 150 mV over setting range
2
Fan speed control (I C)
2
Fan OK (I C & OC)
1
1
Two fan speed levels automatically set depending on the internal temperature.
The fan speed can be set to full speed or automatic control.
Indicates if the fans are operating or have failed.
Overcurrent signal which can be used for synchronous startup of units in parallel or to
recover from an overload condition. (See application note).
Synch. startup pin
1
I C critical temperature warning: Indicates that the operating temperature
has reached [Tshut-down – 10K]
2
I C & OC overtemperature warning: Indicates if the unit is in overtemperature
shutdown. Open collector signal with 20 mA pull-down capability, referenced
to logic return (LRTN). The OC-output will go low 100 ms before an overtemperature condition shuts down the unit. An amber LED on the front panel
indicates overtemperature or fan fail.
2
Provided over the I C interface or as an open collector signal on the output connector (OC).
2
2
For detailed Information on I C, please see document “FNP1500-I2C-controlling.pdf” or use the Power-One I C Management Interface
document.
DEC 12, 2006 revised to FEB 22, 2007
Page 6 of 15
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Output Connector Pinning and Signal Specification (12V Models)
Output
Connector
Description
Overtemperature /
Fan Fail
AC Fail /
Power down warning
Power Supply
Present
DC Fail /
Output voltage fault
Internal ground
ADDR0, I2C address
bus
ADDR1, I2C address
bus
ADDR2, I2C address
bus
ADDR3, I2C address
bus
ADDR4, I2C address
bus
Pin
Location
U1
U2
U3
U4
U5
T1
T2
T3
T4
T5
Type
Low level
High level
U max
I max
OC-output, protected by 16 V Zener diode and a
10 Ω resistor in series, referenced to logic GND
< 0.4 V @ 20 mA
Pull up
15 V
20 mA
< 0.4 V @ 20 mA
Pull up
Open
Resistor (1 kΩ) connected to logic GND
Pull up
OC-output, protected by 16 V Zener diode and a < 0.4 V @ 20 mA
Pull up
10 Ω resistor in series, referenced to logic GND
Internal ground (Vo1– line before the output filter).
Do not connect the internal grounds in
systems with several units.
15 V
20 mA
10 V
10 mA
15 V
20 mA
-
OC-output, protected by 16 V Zener diode and a
10 Ω resistor in series, referenced to logic GND
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
Switch closed
Switch open
Switch closed
Switch open
Switch closed
Switch open
Switch closed
Switch open
Switch closed
Switch open
2
I C compatible signal
referenced to logic GND
I2C compatible signal
referenced to logic GND
5V
5V
5V
5V
5V
-
DATA, I2C data line
S1
CLOCK, I2C clock
line
S2
Vo2 + output
S3
Auxiliary power pin, insulated from main output
-
-
Vo2 – output
S4
Auxiliary ground pin, insulated from main output
-
-
-
-
Logic ground
S5
Internally connected over 10 Ω to Auxiliary GND.
Wire separately form Auxiliary - and main output
2
GND to minimize noise on signals and I C.
Leave open if not used.
Output inhibit
R1
< 0.8 V
> 2.0 V
10 V
3.5 mA
V sense +
R2
V sense -
R3
Output margin
R4
PS active when pulled low
(DC-DC stage off when left open)
Referenced to logic GND
Open or connected to Vo1+ at the load
(Internally connected to Vo1+ over 100 Ω)
Open or connected to Vo1- at the load
(Internally connected to Vo1- over 100 Ω)
Open or connected over resistor to internal
ground. Do not connect the margin pins in
systems with several units.
-
dU < 3 Vpp
30 mA
dU < 3 Vpp
30 mA
3 VDC
-
Synch. Startup
R5
Open or connected to synch startup circuit,
referenced to Vo1 - at the output connector
-
12V
3mA
-
-
-
-
Vo1 + output
Vo1 – output
P2, P4, P6,
P8, P10, P12
P1, P3, P5,
P7, P9, P11
DEC 12, 2006 revised to FEB 22, 2007
Main output + pins
Main output – pins
Page 7 of 15
5 V or 3.3 V logic
5 V or 3.3 V logic
-
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Output Connector Pinning and Signal Specification (48V Models)
Output Connector
Description
Overtemperature /
Fan Fail
AC Fail /
Power down warning
Pin
Location
U1
U2
Power Supply Present
U3
DC Fail /
Output voltage fault
U4
Internal ground
U5
Type
Low level
High level
V max
I max
OC-output, protected by 16 V Zener diode and a 10 Ω
resistor in series, referenced to logic GND
OC-output, protected by 16 V Zener diode and a 10 Ω
resistor in series, referenced to logic GND
<0.4 V @ 20 mA
Pull up
<0.4 V @ 20 mA
Pull up
Open
Pull up
<0.4 V @ 20 mA
Pull up
-
15 V
20 mA
15 V
20 mA
10 V
10 mA
15 V
20 mA
-
Resistor (1 kΩ) connected to logic GND
OC-output, protected by 16 V Zener diode and a 10 Ω
resistor in series, referenced to logic GND
Internal ground (Vo1– line before the output filter).
Do not connect the internal grounds in
systems with several units.
2
T1
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
Switch closed
Switch open
5V
-
2
T2
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
Switch closed
Switch open
5V
-
2
T3
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
Switch closed
Switch open
5V
-
2
T4
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
Switch closed
Switch open
5V
-
2
T5
DIP switch or wire to internal ground,
Internally pull up to 5V (10 kΩ).
Switch closed
Switch open
5V
-
DATA, I C data line
S1
I C compatible signal
referenced to logic GND
CLOCK, I C clock line
2
S2
I C compatible signal
referenced to logic GND
5 V or 3.3 V logic
Auxiliary power +12 V
S3
Vo2+ output, insulated from main output
-
-
Auxiliary power ground
S4
Vo2 - output, insulated from main output
-
-
-
-
Logic ground
S5
Internally connected over 10 Ω to Auxiliary GND.
Wire separately form Auxiliary - and main output GND
2
to minimize noise on signals and I C. Leave open if not
used.
Output inhibit
R1
PS active when pulled low
(DC-DC stage off when left open)
Referenced to logic GND
<0.8 V
>2.0 V
10 V
3.5 mA
V sense +
R2
Open or connected to Vo1+ at the load
(Internally connected to Vo1+ over 100 Ω)
dV < 3 Vpp
30 mA
V sense -
R3
Open or connected to Vo1- at the load
(Internally connected to Vo1- over 100 Ω)
Open or connected to internal ground
(+8 % Vo1) or V sense+ (-8 % Vo1)
Do not connect the margin pins in
systems with several units.
dV < 3 Vpp
30 mA
-
60V
-
ADDR0, I C address bus
ADDR1, I C address bus
ADDR2, I C address bus
ADDR3, I C address bus
ADDR4, I C address bus
2
2
5 V or 3.3 V logic
2
-
Output margin
R4
Synch. Startup
R5
Open or connected to synch startup circuit,
referenced to Vo1 - at the output connector
-
12V
2mA
P1, P3, P5
Main output – pins
-
-
Main output + pins
-
-
Vo1 Vo1 +
P2, P4, P6
Fulcrum:
The handle has been designed to allow easy plug-in and -out in a rack system. The handle (lever) fits into a counter piece
(fulcrum) which is fixed to the bottom of the rack. During the plug, the fulcrum holds the unit down and guides it towards the
output connector. The Power-One part number of the fulcrum and its associated mounting accessories is: HZZ01223.
DEC 12, 2006 revised to FEB 22, 2007
Page 8 of 15
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Mechanical Data
FNP1500/1800 Mechanical Data (H, W, D)
1.6” (40.6 mm) x 5.6” (142.2 mm) x 11” (279.4 mm)
FXP1500/1800 Mechanical Data (H, W, D)
1.6” (40.6 mm) x 5.6” (142.2 mm) x 12” (304.8 mm)
Note: FNP1500/1800's have only 11" (279.4 mm) depth
Output Connector Descriptions (12V Models)
Rear View
Connector: FCI (51732-026 LF)
Female ledge connector:
Manufacturer: FCI
Right Angle type: Part No. FCI (manufacturer): 51762-11202000AA LF; Power-One Part No.: ZES260-G
Vertical type:
Part No. FCI (manufacturer): 51742-11202000AA LF; Power-One Part No.: ZES282-G
Information on availability of FCI connectors under http://www.stkcheck.com/evs/fcielectronics/fcisearch.asp
IEC AC power cord with C19 connector VDE 16A: Interpower Components Ltd. 70009110250
IEC AC power cord with C19 connector UL 20A: Interpower Components Ltd. 70025110250
DEC 12, 2006 revised to FEB 22, 2007
Page 9 of 15
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
FNP1500/1800 (48V Model) Output Connector
Descriptions
Rear View
Connector: FCI (51732-020 LF)
Female ledge connector:
Manufacturer: FCI
Right Angle type: Part No. FCI (manufacturer): 51762-106020000AA LF; Power-One Part No.: ZES258-G
Vertical type:
Part No. FCI (manufacturer): 51742-106020000AA LF; Power-One Part No.: ZES271-G
Locate information on availability of FCI connectors at http://www.stkcheck.com/evs/fcielectronics/fcisearch.asp
FXP1500/1800 (48V Model) Input and Output Connector Descriptions
Rear View
Female ledge connector:
Output connector Part No.:
Output connector Part No.:
Input connector Part No.:
Input connector Part No.:
Output con.: FCI (51732-020 LF)
Input con.: FCI (51939-126 LF)
Manufacturer: FCI
51762-106020000AA LF (Horizontal)
51742-106020000AA LF (Vertical)
51915-056LF (Horizontal)
51940-099LF (Vertical)
Locate information on availability of FCI connectors at http://www.stkcheck.com/evs/fcielectronics/fcisearch.asp
Paralleling Front-Ends:
For parallel use in minimal configuration systems, only the inhibit pins must be shorted to logic GND. All other pins can be left
open. The power supplies will share the output current automatically (droop current share).
For parallel applications without I2C bus, but the use of all other features, it is recommended to connect all logic GND’s on a
backplane together, to connect all Vo2 -, all V o2 + and to leave the internal GND’s open.
The sense wires can be left open or connected to a common load point, the synch-start pin can be left open or connected to a
synch-start circuit, the inhibit pins can be connected together or used individually. All I2C signals (T1-T5, S1, and S2) can be left
open.
Use of a small foil capacitor > 3µF directly at the power outputs of each unit is recommended in order to prevent voltage drops at
the hot plug. For additional information on paralleling see the following Rack (Power Shelf) section.
DEC 12, 2006 revised to FEB 22, 2007
Page 10 of 15
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Racks
(FNR-3-12G, FXR-3-12G, FNR-3-48G, and FXR-3-48G Power Shelves)
Each rack (power shelf) is 1U high with backplane and designed for up to three front-end models in parallel or in n+1 operation.
Each power shelf has:
• Massive copper bus bars for low-loss current distribution.
• Output terminals with two M4-screws on each power tab.
• Two fast-on contacts for system earthing.
• Address coding over five pole DIP switch on each unit, 37-pin D-Sub connector with I2C-lines, monitoring signals and
support functions.
• Provides a start-up synchronization circuit and EMV filters.
FNR-3-12G and FNR-3-48G Power Shelf Front View
FXR-3-12G and FXR-3-48G Power Shelf Front View
Overall Mechanical Dimensions (FNR-3-12G and FNR-3-48G Power Shelves)
FNR-3 Mechanical Data (W, H, D)
17.7” (449.6 mm) x 1.7” (43.1 mm) x 13” (330.2 mm)
FXR-3 Mechanical Data (W, H, D)
17.7” (449.6 mm) x 1.7” (43.1 mm) x 14” (355.6 mm)
DEC 12, 2006 revised to FEB 22, 2007
Page 11 of 15
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Output Connector Descriptions (FNR-3-12G and FNR-3-48G)
A
B
D
C
F
E
G
H
I
Location
Description
A
5-Bit DIP switch for I2C addressing of PSU 1
B
Earth connection
C
Earth connection
D
Earth connection
E
Output 1 minus
F
Output 1 plus
G
5-Bit DIP switch for I2C addressing of PSU 2
H
37-pin SUB-D connector, controlling and auxiliary power (output 2)
I
5-Bit DIP switch for I2C addressing of PSU 3
Output Connector Descriptions (FXR-3-12G and FXR-3-48G)
PE3
L3
A
Location
B
N3
C
D
E
F
PE2
PE1
L2 N2
L1 N1
G
H
I
J
Description
A
Earth connection
B
5-bit DIP switch for I2C addressing of PSU #3
C
Mains connector of PSU #3
D
Output 1 Minus
E
Output 1 Plus
F
5-bit DIP switch for I2C addressing of PSU #2
G
Mains connector of PSU #2
H
37-pin SUB-D connector, control, sense, check and Auxiliary power (Output 2)
I
5-bit DIP switch for I2C addressing of PSU #1
J
Mains connector of PSU #1
DEC 12, 2006 revised to FEB 22, 2007
Page 12 of 15
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Mechanical Data (FNR-3-12G and FNR-3-48G Power Shelves)
(To Be Supplied)
Mechanical Data (FXR-3-12G and FXR-3-48G Power Shelves)
DEC 12, 2006 revised to FEB 22, 2007
Page 13 of 15
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Accessories:
Center Angular Brackets are set in the middle for shelf mounting:
Center Angular Bracket sets can be ordered: Power-One part no.: HZZ01222
Note: Each Center Angular Bracket set contains 2 brackets and 8 screws.
Fulcrums:
Individual fulcrum sets can be also ordered: Power-One part no.: HZZ01223.
Note: Each HZZ01223 set contain 2 fulcrums, 2 supports, and mounting accessories.
DEC 12, 2006 revised to FEB 22, 2007
Page 14 of 15
www.power-one.com
FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
I2C to USB Interface HZZ02002G:
I2C <to>USB
Interface
An I2C to RS232 Interface can be ordered from Power-One. The interface part number to order is HZZ02002G.
All FNP/FXP front-ends can be controlled via Power-One's GUI-driven I2C Management software and the I2C-to-USB interface.
2
An I C Programming Manual describes the complete range of parameters that can be programmed to the FNP and
FXP1500/1800 front-ends. This manual is available by searching on "FNP1500" at www.power-one.com.
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical
components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent
of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.
DEC 12, 2006 revised to FEB 22, 2007
Page 15 of 15
www.power-one.com
Similar pages