GE EN61000-4-2 Car2512fp series rectifier input: 90vac to 264vac output: 12vdc 208a 3.3vdc or 5 vdc 1a Datasheet

GE Energy
Data Sheet
CAR2512FP series rectifier
Input: 90Vac to 264Vac; Output: 12Vdc @ 208A; 3.3Vdc or 5 Vdc @ 1A
Features

Universal input with PFC

Constant power characteristic

2 front panel LEDs: 1-input;2-[output, fault, over temp]

Remote ON/OFF control of the 12Vdc output

Remote sense on the 12Vdc output

No minimum load requirements

Active load sharing (single wire)

Hot Plug-ability
Applications

Efficiency: typically 92.5% @ 50% load
and 90.0% @ 20% load

12Vdc distributed power architectures

Standby orderable either as 3.3Vdc or 5Vdc

Datacom and Telecom applications

Auto recoverable OC & OT protection

Mid to high-end Servers

Operating temperature: -10 - 70C (de-rated above 50C)

Enterprise Networking

Digital status & control: I2C and PMBus serial bus


EN/IEC/UL60950-1 2nd edition; UL, CSA and VDE
Network Attached Storage

EMI: class A FCC docket 20780 part 15, EN55022

Telecom Access Nodes

Meets EN6100 immunity and transient standards

Routers/Switches

Shock & vibration: NEBS GR-63-CORE, level 3

Broadband Switches

ATE Equipment
Description
The CAR2512FP series of Front-End rectifiers provide highly efficient isolated power from worldwide input mains in a
compact 1U industry standard form factor in an unprecedented power density of 25W/in3. These rectifiers are ideal
for datacom applications such as enterprise networking, mid to high-end servers, and storage equipment, where mid
to light load efficiency is of key importance given the nature of the power consumption of the end application.
The high-density, front-to-back airflow is designed for minimal space utilization and is highly expandable for future
growth. The industry standard PMBus compliant I2C communications buss offers a full range of control and
monitoring capabilities. The SMBAlert signal pin alerts customers automatically of any state change within the power
supply.
July 18, 2012
©2012 General Electric Company. All rights reserved.
GE Energy
CAR2512FP series rectifier
Input: 90Vac to 264Vac; Output: 12 Vdc @ 208A; 3.3Vdc or 5 Vdc @ 1A
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional
operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet.
Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.
Device
Symbol
Min
Max
Unit
Input Voltage: Continuous
Parameter
All
VIN
0
264
Vac
Operating Ambient Temperature
All
TA
-10
1
70
°C
Storage Temperature
All
Tstg
-40
85
°C
I/O Isolation voltage to Frame (100% factory Hi-Pot tested)
All
1500
Vac
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.
INPUT
Parameter
Min
Typ
Max
Unit
VIN
90
110/230
264
Vac
FIN
47
50/60
63
Hz
VIN
80
Vac
All
IIN
14.3
16
Aac
All
IIN
40
Apeak
50% load
20% load
Power Factor
(Vin=230Vac, IO=IO, max)
Holdup time2
Vin= 230Vac
(Vout= 12Vdc, Tamb 25C, IO=IO, max)
Vin= 100Vac
Early warning prior to output falling below regulation
All

All
PF
All
T
Ride through
All
T
All
IIN
Operational Range
Frequency Range
(ETSI 300-132-1 recommendation)
Main Output Turn_OFF
Maximum Input Current
VIN= 100Vac
(VO= VO, set, IO=IO, max)
VIN= 180Vac
Cold Start Inrush Current
(Excluding x-caps, 25C, <10ms, per ETSI 300-132)
Efficiency
Device
Symbol
All
All
All
100% load
(Tamb=25C, Vin = 230V, Vout= 12V, IO, max)
Leakage Current
(Vin= 250Vac, Fin = 60Hz)
Isolation
%
0.99
12
15
All
ms
2
Input/Output
Input/Frame
91.6
92.5
90
All
Output/Frame
ms
10
ms
3
mArms
3000
Vac
1500
Vac
100
Vdc
12Vdc MAIN OUTPUT
Parameter
Output Power
Device
HL / LL [180 – 264 / 90-132 Vac] Vdc ≥ 12Vdc
Vdc = 10.8Vdc
All
Set point
Overall regulation (load, temperature, aging)
All
All
Ripple and noise3
All
Turn-ON overshoot
All
Turn-ON delay
All
Symbol
W
Vout
Min
Typ
Max
Unit
0
-
2500/1200
W
0
11.9
-3
12.00
2246/1078
12.1
+3
W
Vdc
%
120
mVp-p
T
+3
%
2
sec
Derated above 50C at 2.5%/C
12V output can decay down to 10.8V
3 Measured across a 10µf electrolytic and a 0.1µf ceramic capacitors in parallel. 20MHz bandwidth
1
2
July 18, 2012
©2012 General Electric Company. All rights reserved.
Page 2
GE Energy
CAR2512FP series rectifier
Input: 90Vac to 264Vac; Output: 12 Vdc @ 208A; 3.3Vdc or 5 Vdc @ 1A
12Vdc MAIN OUTPUT (continued)
Max
Unit
Remote ON/OFF delay time
Parameter
Device
All
40
ms
Turn-ON rise time (10 – 90% of Vout)
All
50
ms
Transient response 50% step [10%-60%, 50% - 100%]
(dI/dt – 1A/outµs, recovery 300µs)
All
-5
+5
%Vout
Programmable range (hardware & software)
All
10.8
13.2
Vdc
Overvoltage protection, latched
(recovery by cycling OFF/ON via hardware or software)
Output current [V
All
15.8
Vdc
0
208
100
Adc
110/110
130/140
% of FL
-5
+5
% of FL
Current limit, Hiccup (programmable level)
Vin = HL
Vin = LL
All
HL / LL
All
Symbol
Min
Vout
13.8
Iout
All
Active current share
Typ
14.8
AUXILIARY OUTPUT
Device
Symbol
Set point
Parameter
All
Vout
Overall regulation (load, temperature, aging)
All
Vout
Ripple and noise
All
Output current
All
Min
Typ
Max
3.3 / 5.0
-5
Iout
0
Unit
Vdc
+5
%
50
mVp-p
1
Adc
Overload protection Overvoltage protection
Isolation
Output/Frame
All
Vdc
100
Environmental, Reliability
Parameter
Min
Typ
Max
Units
50
1524/5k
2.5
2.0
°C
m / ft
%/°C
C/1000 ft
85
8200/30k
°C
m / ft
55
dbA
Notes
Ambient Temperature
Operating
Altitude Operating
Power Derating
-104
Storage
Altitude non-operating
-40
Acoustic noise
Over Temperature Protection
Humidity
Operating
Storage
125/110
30
10
Reliability
Service Life
4
51°C to 70C
Above 5,000 ft
Full load
Shutdown / restart
95
95
%
6
Grms
NEBS GR-63-CORE, Level 3, 20 -2000Hz, min 30 minutes
Zone
NEBS GR-63-CORE, all floors, Seismic Zone 4 Designed
and tested to meet NEBS specifications.
250,000
Hrs
Full load, 25C ; MTBF per SR232 Reliability protection
for electronic equipment, method I, case III,
10
Yrs
Full load, excluding fans
Shock and Vibration acceleration
Earthquake Rating
°C
Air inlet from sea level to 5,000 feet.
4
Relative humidity, non-condensing
Designed to start at an ambient down to -40°C; meet spec after  30 min warm up period, may not meet operational limits below -10°C.
July 18, 2012
©2012 General Electric Company. All rights reserved.
Page 3
GE Energy
CAR2512FP series rectifier
Input: 90Vac to 264Vac; Output: 12 Vdc @ 208A; 3.3Vdc or 5 Vdc @ 1A
EMC
Parameter
AC input
Criteria
Level
Test
Conducted emissions
EN55022, FCC Docket 20780 part 15, subpart J
EN61000-3-2
A*
0.15 – 30MHz
0 – 2 KHz
Radiated emissions
EN55022
A*
30 – 10000MHz
Voltage dips
EN61000-4-11
A
-30%, 10ms
B
-60%, 100ms
B
-100%, 5sec
A
4kV, 1.2/50µs, common mode
A
2kV, 1.2/50µs, differential mode
Voltage surge
Enclosure
Standard
EN61000-4-5
immunity
Fast transients
EN61000-4-4
B
5/50ns, 2kV (common mode)
immunity
Conducted RF fields
EN61000-4-6
A
130dBµV, 0.15-80MHz, 80% AM
Radiated RF fields
EN61000-4-3
A
10V/m, 80-1000MHz, 80% AM
ENV 50140
A
EN61000-4-2
B
ESD
4kV contact, 8kV air
* Note: Contact the factory for a recommended external EMI filter to meet Class B emissions
Status and Control
Some functions have two means of monitor/control; A signal
level that represents the analog value being measured or
controlled, or, reading/writing via the i2C port the measured
value or the control command.
Unless otherwise noted, control via the signals pins is ‘active’
so long that a firmware based command is not initiated.
Once firmware initiates a command that is also represented
on a signal pin, the firmware takes over and replaces the
hardware based control signal. Firmware control is
maintained until bias power to the processor is interrupted.
Once bias power is removed the processor resets and the
analog signal pin control is ‘active’ until firmware takes over
control.
Details of analog controls are provided in this data sheet
under Signal Definitions. GE Energy will provide separate
application notes on the I2C protocol. Contact your local GE
Energy representative for details.
Signal Definitions
All signals and outputs are referenced to Output return.
These include ‘Vstb return’ and ‘Signal return’.
Input Signals
Voltage programming (Vprog): An analog voltage on this
signal can vary the output voltage ± 10% from 10.8Vdc to
13.2Vdc. The equation of this signal is:
Vout = 10.8 + (Vprog * 0.96) 0 < Vprog < 2.5
July 18, 2012
If 2.5 < Vprog < 3, the output is 13.2V. If Vprog is > 3V or left
open the programming signal is ignored and the unit output
is set at the setpoint of 12Vdc.
Load share (Ishare): This is a single wire analog signal that is
generated and acted upon automatically by power supplies
connected in parallel. The Ishare pins should be tied
together for power supplies if active current share among
the power supplies is desired. No resistors or capacitors
should get connected to this pin.
Remote ON/OFF: Controls the presence of the main 12Vdc
output voltage. This is an open collector, TTL level control
signal. This signal needs to be pulled HI externally through a
resistor. Maximum collector voltage is 12Vdc and the
maximum sink current is 1mA. A Logic 1 (TTL HI level) turns
ON the 12Vdc output, while a Logic 0 (TTL LO level) turns OFF
the 12Vdc output.
A turn OFF command either through this signal (Remote
ON/OFF) or firmware commanded would turn OFF the 12V
output.
Enable: This is a short signal pin that controls the presence
of the 12Vdc main output. This pin should be connected to
‘output return’ on the system side of the output connector.
The purpose of this pin is to ensure that the output turns ON
after engagement of the power blades and turns OFF prior
to disengagement of the power blades.
Write protect (WP): This signal protects the contents of the
EEPROM from accidental over writing. When left open the
EEPROM is write protected. A LO (TTL compatible) permits
writing to the EEPROM. This signal is pulled HI internally by
the power supply.
©2012 General Electric Company. All rights reserved.
Page 4
GE Energy
CAR2512FP series rectifier
Input: 90Vac to 264Vac; Output: 12 Vdc @ 208A; 3.3Vdc or 5 Vdc @ 1A
Output signals
Device
Address
Output current monitor (Imon): A voltage level of 3V = 200A
proportional to the delivered output current is present on
this pin.
MCU
EEPROM
0xBx
0xAx
AC OK: A TTL compatible status signal representing whether
the input voltage is within the anticipated range. This signal
needs to be pulled HI externally through a resistor.
Maximum sink current ≤ 20mA and the max voltage is
12Vdc. Open collector (HI) on this signal indicates that the
input voltage is applied within the specified input range.
DC OK: A TTL compatible status signal representing
whether the output voltage is present. This signal is
internally pulled HI to 3.3V via a 10kΩ resistor. Maximum
sink current ≤ 4mA and the max voltage is 12Vdc. Open
collector (HI) on this signal indicates that the output voltage
is present.
Over temp warning: A TTL compatible status signal
representing whether an over temperature exists. This signal
needs to be pulled HI externally through a resistor.
Maximum sink current ≤ 20mA and the max voltage is
12Vdc. Open collector (HI) on this signal indicates that
temperatures are normal.
If an over temperature should occur, this signal would pull
LO for approximately 10 seconds prior to shutting down the
power supply. The unit would restart if internal temperatures
recover within normal operational levels. At that time the
signal reverts back to its open collector (HI) state.
Fault: A TTL compatible status signal representing whether
a Fault occurred. This signal needs to be pulled HI externally
through a resistor. Maximum sink current ≤ 4mA and the
max voltage is 12Vdc. Open collector (HI) on this signal
indicates that no Fault is present.
This signal activates for OTP, OVP, OCP, AC fault or No
output.
PS Present: This pin is connected to ‘output return’ within the
power supply. Its intent is to indicate to the system that a
power supply is present. This signal may need to be pulled
HI externally through a resistor.
Interrupt (SMBAlert): A TTL compatible status signal,
representing the SMBusAlert# feature of the PMBus
compatible i2C protocol in the power supply. This signal
needs to be pulled HI externally through a resistor.
Maximum sink current ≤ 4mA and the pull up resistor should
be tied to 3.3Vdc. Open collector (HI) on this signal indicates
that no Interrupt has been triggered.
Serial Bus Communications
1
1
Address Bit Assignments
(Most to Least Significant)
0
1
1 A2 A1 A0
0
1
0 A2 A1 A0
R/W
R/W
Address lines (A2, A1, A0): These signal pins allow up to eight
(8) modules to be addressed on a single I²C bus. The pins are
pulled HI internal to the power supply. For a logic LO these
pins should be connected to ‘Output Return’
Serial Clock (SCL): The clock pulses on this line are generated
by the host that initiates communications across the I²C
Serial bus. This signal is pulled up internally to 3.3V [ 5V5 ] by
a 10kΩ resistor. The end user should add additional pull up
resistance as necessary to ensure that rise and fall time
timing and the maximum sink current is in compliance to
the I²C specifications.
Serial Data (SDA): This line is a bi-directional data line. . This
signal is pulled up internally to 3.3V [ 5V ] by a 10kΩ resistor.
The end user should add additional pull up resistance as
necessary to ensure that rise and fall time timing and the
maximum sink current is in compliance to the I²C
specifications.
EEPROM
The microcontroller has 96 bytes of EEPROM memory
available for the system host.
Another separate EEPROM IC will provide another 128 bytes
of memory with write protect feature. Minimum information
to be included in this separate EEPROM: model number,
revision, date code, serial number etc.
See the communications protocol for further information.
Communications Protocol
The I²C protocol is described in detail by the I2C and PMBus
Serial Communications Protocol for the CAR Family of Power
Supplies application note.
The Y01A suffix module supports only the I2C command set.
LEDs
Two LEDs are located on the front faceplate. The AC_OK LED
provides visual indication of the INPUT signal function.
When the LED is ON GREEN the power supply input is within
normal design limits.
The second LED DC/FLT is a tri-state LED. When GREEN there
are no faults and DC output is present. When AMBER a fault
condition exists but the power supply still provides output
power. When RED then a fault condition exists and the
power supply does not provide output power.
The I²C interface facilitates the monitoring and control of
various operating parameters within the unit and transmits
these on demand over an industry standard I²C Serial bus.
All signals are referenced to ‘Signal Return’.
Device addressing: The microcontroller (MCU) and the
EEPROM have the following addresses:
5
July 18, 2012
Module configured with 5V standby output
©2012 General Electric Company. All rights reserved.
Page 5
GE Energy
Preliminary Data Sheet
CAR2512FP series rectifier
Input: 90Vac to 264Vac; Output: +12 Vdc @ 208A; 3.3Vdc or 5 Vdc @ 1A
Alarm Table
LED Indicator
Monitoring Signals
Test Condition
LED1
AC
Tri-Color LED2
DC / FLT
FAULT
DC OK
INPUT OK
TEMP OK
1
Normal Operation
Green
Green
High
High
High
High
2
Low or NO INPUT
Off
Red
Low
Low
Low
High
3
OVP
Green
Red
Low
Low
High
High
4
Over Current
Green
Red
Low
Low
High
High
5
Temp Alarm Warning
Green
Orange
High
High
High
Low
6
Fault Over Temp
Green
Red
Low
Low
High
Low
7
Remote ON/OFF
Green
Red
Low
Low
High
High
Notes: Test condition #2 had 2 modules plug in. One module is running and the other one is with no AC.
Outline Drawing
airflow
12 April 2012
©2012 General Electric Company. All rights reserved.
Page 6
GE Energy
CAR2512FP series rectifier
Input: 90Vac to 264Vac; Output: 12 Vdc @ 208A; 3.3Vdc or 5 Vdc @ 1A
Connector Pin Assignments
Input Mating Connector:
IEC320, C19 type
Output Connector:
Tyco P/N 6600122-7 or equivalent
Mating connector: Primary Source: FCI berg P/N 51915-176LF
Secondary Source: Tyco P/N 6450171-5
Pin
Function
Pin
Function
Pin
Function
Pin
Function
A1
Vstb [3.3V]
B1
Fault
C1
IShare
D1
VProg
A2
PS Present
B2
I Monitor (IMON)
C2
No connect
D2
OVP Test Point
A3
Signal Return
B3
Enable: “0” –ON “1” -OFF
C3
Over Temp Warning
D3
Remote ON/OFF
A4
Write Protect (WP)
B4
Vstb [3.3V] Return
C4
I2C Address (A0)
D4
DC OK
A5
Remote Sense (+)
B5
2
SDA (I C bus)
C5
I C Address (A1)
D5
AC OK
A6
Remote Sense (-)
B6
SCL (I2C bus)
C6
I2C Address (A2)
D6
SMBAlert
P1 – P6
Output Return
P7– P12
+12Vout
2
Ordering Information
Please contact your GE Energy Sales Representative for pricing, availability and optional features.
PRODUCT
DESCRIPTION
PART NUMBER
2500W Front-End
+12Vout Front-End, 3.3Vaux, with face plate and PMBus interface, RoHS 6 of 6
CAR2512FPBXXZ01A
2500W Front-End
+12Vout Front-End, 5Vaux, with face plate and PMBus interface, RoHS 6 of 6
CAR2512FPBC5Z01A
Part number definition guide
CAR
25
12
F
P
x
x
x
x
-01A
Contact Us
For more information, call us at
Series
Revision
25 = 2500W
Y = 5 of 6, Z = 6 of 6
12 = 12Vdc
Blank = 3.3V, 5 = 5V
Blank = PMBus, C = I2C
F = front end
Blank = none, B = bezel option
P = positive, N = negative
USA/Canada:
+1 888 546 3243, or +1 972 244 9288
Asia-Pacific:
+86.021.54279977*808
Europe, Middle-East and Africa:
+49.89.878067-280
India:
+91.80.28411633
www.ge.com/powerelectronics
July 18, 2012
©2012 General Electric Company. All rights reserved.
Page 7
Similar pages