LEM APR100B10 Ac current transducer Datasheet

AC Current transducer APR-B10
IPN = 10 .. 400 A
Split core transducer for the electronic measurement distorted AC
waveforms current, with galvanic isolation between the primary (High
power) and the secondary circuits (Electronic circuit). Switch selectable
ranges and True RMS 0-5V and 0-10V switch selectable voltage output.
Electrical data
Primary Nominal Current
I PN (A.t.RMS)
10,25,50
50,75,100
100,150,200
200,300,400
RL
VC
IC
Analogue Output Signal
V OUT (V)
0-5V
0-5V
0-5V
0-5V
or
or
or
or
0-10V
0-10V
0-10V
0-10V
Load resistance
Supply voltage
Current Consumption
Limitation of voltage output (0-10V)
Limitation of voltage output (0-5V)
Overloaded input current
Type
APR
APR
APR
APR
Features
• VFD and SCR waveforms current
measurement
50 B10
100 B10
200 B10
400 B10
≥ 10
kΩ
+24 ±5% V DC
< 30
mA
14
V
7
V
no limitation
Accuracy-Dynamic performance data
X
ε
L
VOE
VOT
TCε G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (±1%)
< ±1
% of IPN
< ±0.5 % of IPN
< ±0.5 % of IPN
±1
mV/K
±0.1
%/K
< 400
ms
30 .. 6000 Hz
General data
TA
TS
m
dCp
dCl
CTI
Ambient operating temperature
Ambient storage temperature
Mass
Protection type
Creepage distance
Clearance distance
Comparative tracking index (Group I)
UL94 classification
-20 .. +60
°C
-20 .. +85
°C
90
g
IP20
5.5
mm
5.5
mm
600
V
V0
Insulation category
Vb
Vd
Ve
Vw
Rated Voltage
300
with IEC 61010-1 standards and following conditions :
- Single insulation
- Over voltage category CAT III
- Pollution degree PD2
- None uniform field
R.m.s. voltage for AC insulation test, 50Hz, 1mn
5
R.m.s. voltage for partial discharge extinction @ 10pC 1.5
Peak impulse withstand voltage 1.2/50µs
6.1
If insulated cable is used for the primary circuit, the voltage category
could be improved with the following table :
Cable insulation (primary)
Category
HAR 05
600V CAT III
HAR 07
1000V CAT III
V
• True RMS output
• Split core type
• 5V & 10V switch selectable voltage
output
• DIN mounting & Panel mounting
• Eliminates insertion loss
• Switch selectable ranges
Advantages
• Large aperture for cable up to
Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Applications
• VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
• SCR Controlled Loads:
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs. Current
measurement gives faster
response than temperature
measurement.
• Switching Power Supplies and
kV
kV
kV
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
041029/3
Notes : Installation and maintenance should be done with power supply disconnected.
The operator must have accrediation to install this material.
The users must take care of all protection gurantee against electrical shock.
LEM Components
www.lem.com
Dimensions AP(R)-B10
Output Vo ltage
Selection Switch
(unit : mm, 1mm = 0.0394 inch)
Front Vie w
Left View
55
16.40
DIN size35.50
69
14.80
Rang e Selection Switch
4.7 0
20
40(distance between screws)
21
33.50
37
Axis of ape rture
25
18 .50
67
Plug-in connector included : XW4B-03C1-H1 (OMRON)
18.50
Bottom View
Mechanical characteristics
• General tolerance
• Primary aperture
±1 mm
∅ 18.5 mm
• Panel mounting
• Distance between holes
2 holes ∅ 4.0 mm
40.0 mm
For panel mounting, replace M4 screws by new one (not supplied) with appropriate length to panel´s thickness.
Connections
• Wires up to 2 mm ∅
0-5, 10V Selectable
GND
RL
OUTPUT
+24VDC
AP/APR
Is
+24VDC
OUT
Output
Connector
Ip
GND
3(-) 2(out)1(+)
Output Switch
Range Switch
Front
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Similar pages