DRP20 SERIES
20A REDUNDANT MODULE
FEATURES
‧SUITABLE FOR REDUNDANT OPERATION
OF 24V SYSTEM MAX 20A
‧READY RELAY CONTACTS
‧DECOUPLING DIODES
‧LED INDICATOR FOR INPUT FAILURE ALARM
‧3 YEARS WARRANTY
R
H
a
UL 60950-1
IND. CONT. EQ.
UL 508
EN 60950-1
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
GENERAL
Characteristics
Conditions
min.
Isolation voltage
Input / Relay contact
100
Isolation resistance
Input / Relay contact, @ 100VDC
100
Ambient temperature
Operating at Vi nom
-40
Storage temperature
Non operational
Relative humidity
Vi nom, Io nom
MTBF
Bellcore Issue 6 @40 oC, GB
Altitude during operation
IEC 60068-2-13
typ.
max.
VDC
MΩ
+ 71
o
C
-40
+ 85
o
C
20
95
% RH
Hours
792,000
m
4,850
Dimension
mm
L90 x W54 x D114
Cooling
Free air convection
Installation position
Vertical ( other direction may derating using )
unit
Pollution degree
2
INPUT SPECIFICATIONS
Characteristics
Rated input voltage
Conditions
Io nom
min.
max.
unit
28
VDC
20
A
max.
unit
A
21
Number of inputs
Rated input current
typ.
2
Each channel
OUTPUT SPECIFICATIONS
Characteristics
Conditions
min.
typ.
Output voltage drop
Vin - Vout
Output current
Vi nom
20
Maximum output current
Vi nom
30A for 300 sec.
0.5
V
Reverse voltage (max)
DC ON indicator
Two LEDs indicating each input is ok
30
V
max.
unit
Green LED
CONTROL FUNCTION
Characteristics
Power Rdy
Conditions
2015.05.12
typ.
OK
When input is>20V(±5%) or <30V(±5%)
Fail
When input is<20V(±5%) or >30V(±5%)
Contact rating at 30VDC
www.chinfa.com
min.
1.0
A
[email protected]
P1
DRP20 SERIES
SPECIFICATION
APPROVALS AND STANDARDS
UL / cUL
UL 508 Listed
UL 60950-1 Recognized
TUV
EN 60950-1
CE
EN 55022 Class B, EN 55024
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8
ENV 50204, EN 61204-3
Vibration resistance
meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis )
Shock resistance
meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
PHYSICAL CHARACTERISTICS
Screw terminal type
90 x 54 x 114 mm (3.6 x 2.13 x 4.49 inches)
Case material
Plastic
Weight
210g
Packing
0.28kg ; 32
/ 10kg / 1.85CUFT
MECHANISM & PIN CONFIGURATION
mm [inch]
CONSTRUCTION
Easy snap-on mounting onto the DIN-Rail
(TS35/7.5 or TS35/15), unit sits safeIy and
firmly on the rail.
54.0 0 [2.1 3]
INSTALLATION
114.0 0 [4.4 9]
1 2 3 4 5 6
LED A
LED B
OK
FAIL
OK
90.00 [3.60]
FAIL
DRP20
A+
B+
Ventilation / Cooling
Normal convection
All sides 25mm free space
For cooling recommended
Connector size range
IN / OUT : AWG24-10 (0.2~4mm2 ) flexible / solid
cable, connector can withstand torque at maximum
5.5 pound-inches.
Relay : AWG24-12 (0.2~2.5mm2 ) flexible / solid
cable, connector can withstand torque at maximum
6 pound-inches.
7~8 m/m stripping at cable end recommends
Use copper conductors only, 60 / 75oC
+
GENERAL TOLERANCE
7 8 9 10 11 12
0.00[0.00] - 30.00[1.18]
±0.30[0.01]
30.00[1.18] - 120.00[4.72]
±0.50[0.02]
PIN ASSIGNMENT
Designation
PIN NO.
1
RDY A
4
9
10
IN
OUT
8
www.chinfa.com
2015.05.12
OUT
11
12
COM B
O.K
6
7
A normal open relay contact for DC ON level control
FAIL
RDY B
5
COM A
O.K
OUT
2
3
Description
FAIL
+
A+
+
-
B+
-
Input terminal
Negative output terminal / input terminal
+
Positive output terminal
[email protected]
P2
DRP20 SERIES
TYPICAL APPLICATION NOTES
1.) 1+1 Redundancy : Using 1 more PS as the redundant unit.
PS#1
PS#2
DRP20
Vout
Load
2.) Single Use : Connecting only one PS to one DRP20 to reduce the stress of the diodes and
hence increase the reliability.
PS#1
Vin A
PS#1
Vin B
Vin A
Vin B
DRP20
DRP20
Vout
Vout
Load
3.) 1+N Redundancy : Using 1 more PS as the redundant units to increase the reliability.
PS#1
Vin A
PS#2
PS#1
Vin B
PS#2
Vin A
Vin B
DRP20
PS#1
Vin A
DRP20
Vout
Vout
PS#2
Vin B
DRP20
Vout
Load
CIRCUIT SCHEMATIC
Vin A+
OK
RELAY
A
Vin B+
RDY A
FAIL
OK
Vin - / Vout-
RELAY
B
RDY B
FAIL
Vout+
www.chinfa.com
2015.05.12
[email protected]