ETAL ESX50-S100-DC24V-1A-6A Current rating (1a - 10a, in whole numbers) Datasheet

Electronic Circuit Protector ESX50D-S (ControlPlex®)
Description
The type ESX50D-Sxx is an electronic circuit protector capable of
communication, which forms the intelligent power distribution system
ControlPlex® type SVS201-CP together with the bus terminal
controller CPC10 and the power distribution board SVS201-PWR
By means of its communication interface, the measuring values
recorded by the ESX50D-Sxx will be forwarded to the CPC10 via
the proprietary device bus ELBus® and then to a superordinate
programmable control unit. This allows flexible adjustment of the current
rating and its parameters to the requirements of the system and its
direct controllability. So the user can import the relevant information
regarding his DC 24 V voltage supply and process it accordingly.
The ESX50D-S is available in two different versions. The first version
has a rotary switch to allow current rating adjustment directly on the
circuit protector in a range from 1 A to 10 A. The second version
offers this adjustment feature via a field bus system or a USB service
interface.
At a width of only 12.5 mm the ESX50D-S provides selective protection
for all DC 24 V load circuits. This is achieved by a combination of
active electronic current limitation in the event of a short circuit and
by a parameterisable overload disconnection.
A typical application is the protection of DC 24 V switched mode
power supplies which are widely used in in factory automation today.
In the event of an overload, however, they turn down the output
voltage which is intended to power all connected loads. So if there is
a failure in a single load of the system, the supply voltage will break
down also in all other load circuits. Not only does this frequently cause
undefined fault conditions, but it can even lead to machine stoppages
or system downtimes. This is exactly where the ESX50D-S comes in
by responding to the overload conditions faster than the switched
mode power supply. The max. possible overcurrent is limited to
typically 1.4 times of the selected current rating (see table 1). This
allows switching on capacitive loads up to min. 20,000 µF, disconnection
is effected in the event of overload or short circuit or at undervoltage
and overheating.
Visual status and failure indication is by a multi-coloured LED on the
protector and is transmitted to the superordinate control unit via the
communication interfaces. The manual ON/OFF swtich on the device
as well as the control units which are programmable from memory
and which are connected to the communication interfaces allow the
start-up of selected load circuits.
As soon as the ESX50D-S detects an overload or short circuit in its
load circuit, it blocks the load output transistor after a parameterisable
period of time and disconnects the current flow in the faulty circuit.
After remedy of the failure, the load output of the ESX50D-S is re-activated by an electronic reset signal or manually by actuating the ON/
OFF switch on the device.
ESX50D-Sxxx
Technical data (Tamb = 25 °C, UB = DC – 24 V)
Operating data
Operating voltage UB
DC 24 V (18...32 V)
adjustable ratings:
1 A through 10 A in 1 A steps
in ON condition:
typically 20 mA with the versoins -S100/ -S110
multicoloured LED:
green
- load circuit connected
flashing (green/yellow):
- load current warning limit reached
yellow:
- overload or short circuit until disconnection
red:
- after disconnection due to overload,
short circuit or temperature
- after undervoltage disconnection in
ON condition of operating voltage
with automatic reset
flashing (red/OFF):
- upon changed rating adjustment
(only ESX50D-S110)
OFF:
- devices switched off via
ON/OFF switch
- device switched off via the communication interface
- no operating voltage with
ON/OFF switch in ON condition
Load circuit
Load output power MOSFET switching output
(plus switching)
Current ratings IN
Standby current I0
Visual status indication
Load current warning limit 0.8 x IN* (adjustable from 0.5 to 1.0 x IN)
hysteresis
5 % (adjustable from 5 % to 20 %)
Overload disconnection (IOL) 1.2 x IN* (adjustable from 105 %
to 135 % IN)
see time/current characteristic
Short circuit current (IKS)active current limitation with IKS =
typically 2.5 x IN, 1 A
typically 1.4 x IN, 2 A-10 A
(see time/current characteristic)
Trip times overload disconnection (IÜL) = 3000ms*
(adjustable from 50ms ... 10,000ms)
short circuit disconnection (IKS) = 100ms*
(adjustable from 50ms ... 1.000ms)
(see time/current characteristic)
* factory settings
1646
www.e-t-a.de
1
7
Electronic Circuit Protector ESX50D-S (ControlPlex®)
Technical data (Tamb = 25 °C, UB = DC – 24 V)
Technical data (Tamb = 25 °C, UB = DC – 24 V)
Temperature internal temperature monitoring with
monitoring electronic disconnection
General data
Fail-safe-elementintegral fail-safe-element 15A
Max. rupture capacity of the element is
300 A at 24 V DC
disconnection typically +100 °C
hysteresis typically 10 °C
Operating voltage OFF at typically UB < 16.0 V
monitoring ON at typically UB> 17.5 V
with regard to low voltagewith automatic ON and
OFF switching
ON delay tStart100ms* (adjustable from 100ms
to 2,500ms)
Disconnection of
load circuit- manually on the device with the
ON/OFF switch (OFF)
- by a superordinate control unit via
communication interface
- after disconnection due to overload or
short circuit
- temporarily at undervoltage
- at excess temperature of the device
(only ESX50D-S110)
- upon changed rating adjustment
- during switch-on delay
- at no operating voltage
Leakage current in load
circuit in the OFF condition typically < 1 mA
Capacitive loads
min. 20,000 µF
Free-wheeling diodeexternal free-wheeling diode recommended
for inductive load
Parallel connection of
several load outputs
not allowed
Terminals
LINE+ / LOAD+ / GND / Ad / COM
Blade terminals
6.3 mm to EN60934-6.3-0.8
Housing material
moulded
Mounting of enclosure
plug-in type, suitable for SVS201-PWR-xx
Ambient temperature0...+50 °C (without condensation,
cf. EN 60204-1)
Storage temperature
-40...+70 °C
Humidity96 hrs / 95% RH 40°C to
IEC 60068-2-78-Cab
climate class 3K3 to EN 60721
Vibration
3 g, test to IEC 60068-2-6 test Fc
Degree of protection
IEC 60529, DIN VDE 0470)
operating area
IP30
terminal area
IP00
EMC requirements
emission: EN 61000-6-3
(EMC directive, CE logo) susceptibility: EN 61000-6-2
Insulation co-ordination 0.5 kV / pollution degree 2
(IEC 60934)
reinforced insulation in operating area
Dielectric strength
max. DC 30 V (load circuit)
Insulation resistance
n/a, only electronic disconnection
(OFF condition)
Approvals
CE logo
Dimensions (w x h x d)12.5 x 70 x 60 mm (tolerances to
DIN ISO 286 part 1 IT13)
Mass
approx. 40 g
* factory settings
Order numbering code
Features and Benefits
Type No.
ESX50D-S Electronic Circuit Breaker, with current limitation
Mounting
Splug-in, with rotary switch for current rating adjustment
from 1 A to 10 A
Version
1 without physical isolation
Current rating adjustment
00 current rating adjustable via communication interface
10 current rating adjustable via rotary switch
Operating voltage
DC 24 V
voltage rating DC 24 V
Current rating
1 A - 10 A adjustable
l
ESX50 - S
l
1
00 - DC 24 V - 1 A-10 A ordering example
l
l
l
l
l
l
l
Notes for installation
l
l
l
l
7
2
The user has to ensure that the cable cross section of the load
circuit in question complies with the current rating of the ESX50D-S
used.
In addition special precautions must be taken in the system
or machine (e.g. use of a safety PLC) which reliably prevent
an automatic re-start of parts of the system (cf. Machinery
Directive 2006/42/EG and EN 60204-1, Safety of Machinery). In
the event of a failure (short circuit/overload) the load circuit will be
disconnected electronically by the ESX50D-S.
l
www.e-t-a.de
Communication capability with superordinate control units which
are programmable from memory
Import and adjust parameters of the device
Remote control of load outputs and selective load protection,
electronic trip curve
All types of loads can be connected (DC 24 V motors upon
request)
Active current limitation when switching on capacitive loads up
to min. 20,000 µF and in case of overload/short circuit
Whole-number adjustable current ratings from 1A to 10 A by
means of rotary switch and superordinate control unit
Reliable parameterisable overload disconnection (factory setting:
1.2 x IN) even with long load lines or small cable cross sections
Manuel ON/OFF switch (S1)
Clear status indication through LED and signalling to the superordinate control system
Integral fail-safe-element
Width per channel only 12.5 mm
Plug-in type mounting on power distribution system SVS201PWR-xx
1646
Electronic Circuit Protector ESX50D-S (ControlPlex®)
Communication interface
Overview of commands:
- Writing/reading of configuration (parameters)
l
Current rating (1A - 10A, in whole numbers)
(writable only for ESX50D-S100)
l
Switch-on behaviour (latest state, OFF, ON)
l
Overload disconnection (105 % ... 135 % IN)
l
Trip time at overload (50 ms ... 10,000 ms)
l
Trip time at short circuit (50 ms ... 1,000 ms)
l
ON delay (50 ms ... 2,500 ms)
l
Current limit value (50 % ... 100 %)
l
Hysteresis limit value (5 % ... 20 %)
- Reading of static product information
l
Product type
l
Serial number
l
Hardware version
l
Software version
- Reading of dynamic product information / measuring values
l
Error memory
l
Trip counter
l
Reason of last trip
l
Status / event of device
l
Load voltage
l
Load current
l
Operating voltage
l
Temperature
-
Switch on/off or reset load output
Reset error memory
Reset trip counter
Read / delete histogramm memory
Set parameters to factory setting
Table 1: typical voltage drop, current limitation, max. load current
Current rating
IN
Typical voltage drop UON at IN
Active current limitation
ILimit typically
Max. load current at 100 % ON duty
TAMB = 40 °C
TAMB = 50 °C
1A
15 mV
2,5 x IN
1A
1A
2A
30 mV
1,4 x IN
2A
2A
3A
45 mV
1,4 x IN
3A
3A
4A
60 mV
1,4 x IN
4A
4A
5A
75 mV
1,4 x IN
5A
5A
6A
90 mV
1,4 x IN
6A
5A
7A
105 mV
1,4 x IN
7A
6A
8A
120 mV
1,4 x IN
8A
7A
9A
135 mV
1,4 x IN
9A
8A
10 A
150 mV
1,4 x IN
10 A
9A
Note:
When mounted side-by-side without convection, the devices should carry max.
80% of their rated load continuously (100 % ON duty).
7
1646
www.e-t-a.de
3
Electronic Circuit Protector ESX50D-S (ControlPlex®)
Technical data (Tamb = 25 °C, UB = DC – 24 V)
Wiring diagrams
ESX50D-S100 / -S110
10000
with communication and address contact
1000
2 LOAD+
0,1
3 COM
Short circuit current limitation
typ. 2,5 x IN with IN 1 A
typ. 1,4 x IN with IN 2 A to 10 A
^
13 Ad
1
1 LINE+
10
5
11 GND
Trip time in sec
100
Failsafe
overload
disconnection
1,2 x IN (factory settings)
0,01
0
1
2
5 IK
4
3
... times rated current
l
Without the current limitation there would be a much higher
overcurrent in the event of an overload or short circuit.
Dimensions ESX50D-S...
60
Schematic diagram ESX50D-S100 (example)
operating area
Electronic Overcurrent Protector
ESX50D-S1xx-DC24V-1A-10A
ON/OFF
operating condition
green/yellow/red
COM
0V
GND (-)
Bus - interface
mounting area
Devices - address
10,3
Ad
LOAD (+)
load output
Made in Germany
XXXX
S1
70
electronic control unit
Rsense
Failsafe
LINE (+)
DC 24 V
Optional manual rated current
Settings on the device.
6,8
blade terminals
EN 60934-6,3-0,8
6x6,8 = 40,8
IN
/
A
1-10A
on
on
off
r
e
s
e
t
off
r
e
s
e
t
ESX50D
-S110DC24V
ESX50D
-S100DC24V
12,3
polarizing tooth
7
All dimensions without tolerances are for reference only. E-T-A reserves the right change
specifications at any time in the interest of improved design, performance and cost effectiveness, the right to make changes in these specifications without notice is reserved. Product
markings may not be exactly as the ordering codes. Errors and omissions excepted.
4