120W Single Output Industrial DIN RAIL Power Supply DRH-120 series Features : Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Built-in constant current limiting circuit Can be installed on DIN rail TS-35/7.5 or 15 EN61000-6-2(EN50082-2) industrial immunity level 100% full load burn-in test Fixed switching frequency at 70KHz 3 years warranty SPECIFICATION MODEL OUTPUT DRH-120-24 DRH-120-48 DC VOLTAGE 24V 48V RATED CURRENT 5A 2.5A CURRENT RANGE 0 ~ 5A 0 ~2.5A RATED POWER 120W 120W RIPPLE & NOISE (max.) Note.2 80mVp-p 80mVp-p VOLTAGE ADJ. RANGE 48 ~ 55V 1.0% 24 ~ 28V VOLTAGE TOLERANCE Note.3 1.0% LINE REGULATION 0.5% LOAD REGULATION 0.5% 0.5% 0.5% SETUP, RISE, HOLD UP TIME 1700ms, 120ms, 16ms/400VAC INPUT VOLTAGE RANGE 340 ~ 550VAC FREQUENCY RANGE 47 ~ 63Hz EFFICIENCY (Typ.) 85% AC CURRENT INRUSH CURRENT (max.) 0.65A/400VAC 0.6A/500VAC COLD START 50A LEAKAGE CURRENT OVERLOAD PROTECTION OVER VOLTAGE WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS SAFETY & WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC (Note 4) <3.5mA / 530VAC 5 (TSW) detect on heatsink of power switch Protection type : Shut down o/p voltage, recovers automatically after temperature goes down -20 ~ +60 (Refer to output load derating curve) 20 ~ 90% RH non-condensing -40 ~ +85 , 10 ~ 95% RH 0.03%/ (0 ~ 50 Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting clip: Compliance to IEC60068-2-6 UL60950-1 approved, IEC60950-1 CB approved by SIQ I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A MTBF 178.7Khrs min. DIMENSION 65.5*125.2*100mm (W*H*D) 0.75Kg; 20pcs/16Kg/1.29CUFT PACKING NOTE 86% I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH EMI CONDUCTION & RADIATION Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B EMS IMMUNITY OTHERS 480 ~ 780VDC 105 ~ 160% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 30 ~ 36V 59 ~ 66V Protection type : Shut down o/p voltage, re-power on to recover 85 OVER TEMPERATURE 1000ms, 120ms, 30ms/500VAC at full load MIL-HDBK-217F (25 ) 1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. File Name:DRH-120-SPEC 2009-04-27 DRH-120 120W Single Output Industrial DIN RAIL Power Supply Mechanical Specification Case No.921A series Unit:mm 100 125.2 +V ADJ. TB2 TB1 1 2 3 4 65.5 1 2 3 LED Terminal Pin No. Assignment (TB1) 35 Pin No. 1 2 3 ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15 Assignment FG AC/L2 AC/L1 Terminal Pin No. Assignment (TB2) Pin No. 1,2 3,4 Block Diagram Assignment DC OUTPUT +V DC OUTPUT -V fosc : 70KHz RECTIFIERS & FILTER EMI FILTER I/P POWER SWITCHING RECTIFIERS & FILTER +V -V DETECTION CIRCUIT FG CURRENT LIMIT O.L.P. O.T.P. PWM CONTROL O.V.P. Derating Curve 100 80 LOAD (%) 60 50 40 20 -20 0 10 20 30 40 50 60 70 (VERTICAL) AMBIENT TEMPERATURE ( ) File Name:DRH-120-SPEC 2009-04-27