Emerson Network Power LPS208-M Medical and ite safety Datasheet

Embedded Power for
Business-Critical Continuity
Rev. 7.9.09_#98
LPS200-M Series
of 3
LPS200-M Series
250 Watts
Total Power:
Input Voltage:
# of Outputs:
125 - 250 Watts
90 - 264 Vac
Single
Special Features
•
•
•
•
•
•
•
•
•
•
•
•
•
Medical and ITE safeties
Active power factor correction
3” x 5” footprint
Less than 1U high
EN61000-3-2 compliant
Remote sense
Power fail
Adjustable main output
Built-in Class B EMI filter
Overvoltage protection
Overload protection
Thermal overload protection
Isolated 12V Fan output
Electrical Specifications
Input
Input ra­nge:
Frequency:
Inrush current:
Efficiency:
EMI/RFI:
Power factor:
Safety ground
leakage current:
90 - 264 Vac; 120 - 300 Vdc
47-63 Hz
50 A max., cold start @ 25 °C
86% typical at full load
FCC Class B conducted; CISPR22 Class B conducted;
EN55022 Class B conducted; VDE0878PT3 Class B conducted
0.99 typical
275 uA @ 50/60 Hz, 264 Vac input
Output
125 W for convection (100 W for LPS202-M) ; 250 W (200 W for LPS202-M)
with 30CFM forced air
Adjustment range:
±10% minimum on the main outputs
Fan output:
12 V @ 0.5 A convection, @ 1 A forced air isolated, ±10%
Hold-up time:
16 ms @ 250 W load, 120 Vac input
Short circuit protection on all outputs. Case overload protected @ 110-160%
Overload protection:
above rating
Overvoltage protection: 15-50% above nominal output
Maximum power:
Logical Control
Power failure:
Safety
•
•
•
•
•
TUV 60950, 60601-1
UL
60950, 60601-1
cULus
60950, 60601-1
CB
Certificate & report
CE
Mark (LVD)
Remote sense:
Open collector logic signal goes high 100-500 msec after main output; it
goes low at least 6 msec before loss of regulation
Compensates for 0.5 V lead drop min. Will operate without remote sense
connected. Reverse connection protected.
Embedded Power for
Business-Critical Continuity
Rev. 7.9.09_#98
LPS200-M Series
of 3
Environmental Specifications
Operating temperature:
Storage temperature:
Electromagnetic
susceptibility:
Humidity:
Vibration:
MTBF demonstrated:
0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C
start up
-40 °C to +85 °C
Designed to meet EN61000-4;
-2, -3, -4, -5, -6, -8, -11 Level 3
Operating; non-condensing 10% to 95% RH
IEC68-2-6 to the levels of IEC721-3-2
>550,000 hours at full load and 25 °C ambient conditions
Ordering Information
Model
Number
Output
Voltage
Minimum
Load
Maximum Load with
Convection Cooling
Maximum Load with
30CFM Forced Air
LPS202-M
5V
0A
20 A
40 A
44 A
±2%
50 mV
LPS203-M
12 V
0A
10.3 A
20.8 A
22 A
±2%
120 mV
LPS204-M
15 V
0A
8.3 A
16.6 A
18 A
±2%
150 mV
LPS205-M
24 V
0A
5.2 A
10.4 A
11.5 A
±2%
240 mV
LPS208-M
48 V
0A
2.6 A
5.2 A
5.8 A
±2%
480 mV
Peak Load Regulation2
Ripple
P/P (PARD)3
1. Peak current lasting <30 seconds with a maximum 10% duty cycle.
2­. At 25°C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
3­. Peak-to-peak with 20 mHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage and load ranges.
Pin Assignments
Mating­ Connectors
Connector LPS200-M
SK1
Pin 1
Neutral
Pin 3
Line
SK2
TB-1
Common
TB-2
Main output
SK3
Pin 1
+V1 Remote sense
Pin 2
-V1 Remote sense
Pin 3
N/C
Pin 4
N/C
Pin 5
+Power fail
Pin 6
Common
Pin 7
N/C
Pin 8
Common
Pin 9
+12 V Fan
Pin 10
+12 Fan Return (isolated)
AC Input (SK1): Molex 09-50-8031 (connector)
PINS: 08-52-0113
AC Ground:
Molex 01-90020001
DC Output
(SK2):
Control Signals
(SK3):
Molex 19141-0058/0063/0083
Spade lug based on Cable Ampacity/AWG
Molex 90142-0010 (USA)
PINS: 90119-2110 or
Amp: 87977-3
PINS: 87309-8
Emerson Network Power Connector Kit #70-841-020, includes all of the
above.
1. Specifications subject to change without notice.
­2. All dimensions in inches (mm), tolerance is ±0.02”­­ (±0.5mm)
3. Mounting holes MH1 and MH2 should be grounded for EMI purposes.
4. Mounting hole MH1 is safety ground connection.
5. Specifications are for convection rating at factory settings at 115 VAC
input, 25 °C unless otherwise stated.
6. This power supply requires mounting on metal
standoffs 0.20” (5m) in height.
7. Warranty: 2 years
8. Weight: 0.75 lb/0.34 kg
Embedded Power for
Business-Critical Continuity
­Americas
Mechanical Drawing
3.00
(76.2)
0.15 Dia.
(4)
4 Places
2.55
(64.8)
MH1
SK1
3
1
5810 Van Allen Way
Carlsbad, CA 92008
USA
Telephone: +1 760 930 4600
Facsimile: +1 760 930 0698
Rev. 7.9.09_#98
LPS200-M Series
of 3
Europe (UK)
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
Telephone: +44 (0) 1384 842 211
Facsimile: +44 (0) 1384 843 355
Asia (HK)
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
Telephone: +852 2176 3333
Facsimile: +852 2176 3888
5.00
(127.0)
4.55
(115.6)
For global contact, visit:
www.PowerConversion.com
techsupport.embeddedpower
@emerson.com
While every precaution has been taken to ensure
accuracy and completeness in this literature, Emerson
Network Power assumes no responsibility, and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
Emerson Network Power.
The global leader in enabling
business-critical continuity.
AC Power
Connectivity
DC Power
2
MH2
SK2
Embedded Computing
SK3
1
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
1.32
(33.6)
1
SK3
VR1
Output Voltage
Adjust Pot
Precision Cooling
Racks & Integrated Cabinets
Services
5
10
Surge Protection
0.197” (5.0)
Minimum
Standoff Height
EmersonNetworkPower.com
Emerson Network Power and the Emerson
Network Power logo are trademarks and
service marks of Emerson Electric Co. ©2009 Emerson Electric Co.
Similar pages