EPCOS A80-C350X 2-electrode-arrester Datasheet

Surge Arrester
2-Electrode-Arrester
A80-C350X
Ordering code: B88069X2360C103
DC spark-over voltage 1) 2)
350
± 20
V
%
< 700
< 650
V
V
< 900
< 800
V
V
Nominal impulse discharge current (wave 8/20 µs)
Single impulse discharge current
(wave 8/20 µs)
20
25
kA
kA
Nominal alternating discharge current (50 Hz, 1 s)
Alternating discharge current (50 Hz, 9 cycles)
20
100
A
A
Insulation resistance at 100 Vdc
> 10
GΩ
Capacitance at 1 MHz
< 1.5
pF
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
~ 15
~ 0.5
~ 60
V
A
V
Weight
~ 1.5
g
Operation and storage temperature
-40 ... +90
°C
Climatic category (IEC 60068-1)
40/ 90/ 21
Marking, blue
NGC 40101 350V YY
Impulse spark-over voltage
at 100 V/µs - for 99 % of measured values
- typical values of distribution
at 1 kV/µs
- for 99 % of measured values
- typical values of distribution
NGC 40101
350V
YY
- Customer type name
- Nominal voltage
- Year of production
1)
At delivery AQL 0.65 level II, DIN ISO 2859
In ionized mode
Terms in accordance with ITU-T Rec. K12 and DIN 57845/VDE0845
2)
AB E / AB PM
Issue 03, 18.04.2002
Page 1 of 2
Surge Arrester
2-Electrode-Arrester
A80-C350X
Ordering code: B88069X2360C103
Not to scale
Dimensions in mm
Non controlled document
 EPCOS AG 2002. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and
Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Association), unless
otherwise agreed.
AB E / AB PM
Issue 03, 18.04.2002
Page 2 of 2
Similar pages