SL Power MW159RA1251F01 100 watt medical adapter family Datasheet

MW159
100 Watt Medical Adapter Family
• 100-240VAC Universal Input
• IPX1 Waterproof
• Low Life-Cycle Operation Cost
• Desktop Style
• Complies with EMI/RFI Regulations
• CE compliant (EMC, WEEE, RoHS)
• Impact Resistant, Non-vented Polycarbonate Enclosure
• Modified and Custom Designs also Available
International Safety Standard Approvals
Specifications
Output Specifications
Line and Load
Voltage Regulation
Environmental Specifications
±1%
Thermal Performance
Operating Temperature 0° C to 40° C
with no Derating
Ripple
1% Vp-p max.
Cooling
Convectional
Transient Response
ms max. for 50% load
5
change, slew rate of
0.1A/µs
Relative Humidity
Non-condensing
Protection
Excluding Cord
ycle-by-cycle current
C
limiting, automatic
recovery for overload,
short circuit or over
temperature protection;
active OVP
Voltage
100-240VAC nominal
Line Frequency
47-63Hz
Input Current
Protection
5% to 95% Altitude
0-10,000 feet
Storage Temp
-30° C to +85° C
General Specifications
Topology
ctive PFC and DC-DC
A
converter
Efficiency
up to 86% typical
Certifications
Input Specifications
Non-ventilated Enclosure
UL60601-1, EN60601-1,
IEC60601-1
Hold-up Time
>16ms at 120V input,
typical
2.0A max.
MTBF
>200,000 Hours
Input fuse, inrush limited
Weight
24.4 oz (691g)
Case and Dimension
6.6L X 3.2W X 1.6H (in)
167L X 82W X 40H (mm)
Case Material
Cord
94V-0 Polycarbonate, Black
3.28ft (1m), 2-conductor, 18AWG standard for
18V, 24V output
3.28ft (1m), 4-conductor, 22AWG standard for
12V, 15V output
SL Power Electronics Corp • 6050 King Drive • Ventura, CA 93003 • Phone:805.486.4565 • Fax:805.487.8911 • Email:[email protected] • www.slpower.com
MW159
100 Watt Medical Adapter Family
For the most current data and application support visit www.slpower.com
Output Currents
Output
Voltage
Min
Max
Ault Part Number
Max
Watts
MW159RA1251F01
12 V
0.00 A
6.66 A
80.0 W
MW159RA1551F01
15 V
0.00 A
5.33 A 80.0 W
MW159RA1803F01
18 V
0.00 A
5.00 A
90.0 W
MW159RA2403F01
24 V
0.00 A
4.20 A 100.0 W
Ault Part Number Key
MW159
R
A
12
51
F
01
Product
Family
Name
Manufacturing
Location
Type
Revision
Output
Voltage
Output
Connector
Style
Input
Connector
Style
Standard Item
(other numbers
for custom)
General Specifications (continued from p. 1)
Output Connectors
EMI Compliance
EN55011 and FCC PART15 conducted and radiated Class B
IEC 61000-3-2 Class D
IEC 61000-4-2 (ESD), CD level 2 and AD level 3, criterion B
IEC 61000-4-3 (RFS), level 2, criterion A
IEC 61000-4-4 (EFT), level 2, criterion A
IEC 61000-4-5 (Surge), level 3, criterion B
Input Connectors
IEC320
w/ground
C14
(F)
IEC320
w/o ground
C18
(Q)
N. America/
Japan
(B)
Europe
(M)
United
Kingdom
(G)
Australian
(E)
Shaver
C8
(N)
Optional Features
Ault #3, #51 high-retention barrel connector standard
arious output cord wire gauges and connector styles available. See Ault
V
connector style sheets for connector options
“Power-on” LED
Private label marking
SL Power Electronics Corp • 6050 King Drive • Ventura, CA 93003 • Phone:805.486.4565 • Fax:805.487.8911 • Email:[email protected] • www.slpower.com
Data Sheet © 2008 SL Power Electronics Corp. The information and specifications contained in this data sheet are believed to be correct at time of publication. However, SL Power accepts no responsibility for consequences arising from reproduction errors or inaccuracies. Specifications are subject to change without notice.
Rev.3/20/08
Similar pages