POWERDYNAMICS HGN-368-4M-F2 Iec 60320 inlet socket with switch, flange mount Datasheet

HGN-368
IEC 60320 INLET SOCKET WITH SWITCH, FLANGE MOUNT
MECHANICAL DIMENSIONS (Unit: mm)
46.0
36.0+- 0.2
35.0
2x
3.3x90 CSK
0.8 TYP.
32.5
FEATURES
The HGN-368 series power entry module features an IEC
Connector with an integral switch. The filter is designed to for
applications where Common Mode and Differential Mode
noise must be controlled. Fully enclosed metal housing prevents input of high frequency noise and protects ultra-sensitive
equipment.
28.0
6.3 TYP.
These filters are also available for Medical equipment with
low leakage current to comply with UL544 & 2601.
APPLICATIONS
Computer & networking equipment, Measuring & control
equipment, Data processing equipment, laboratory instruments,
Switching power supplies, other electronic equipment.
58.5
TECHNICAL DATA
• Rated Voltage: 115/250VAC
• Rated Current: 1A, 2A, 4A, 6A,
• Power Line Frequency: 50/60Hz
• Max. Leakage Current each
Line to Ground:
@ 250VAC 50Hz: 0.5mA, max
@ 250VAC 50Hz: 2µA*, max
• Hipot Rating (one minute)
Line to Ground: 2250VDC
Line to Line: 1450VDC
• Temperature Range: -25C to +85C
* Medical application
6.0
36.0+- 0.2
29.0 +- 0.3
33.0+- 0.3
2x M3
4x R1.5
Specifications subject to change without notice. Dimensions (mm). See Appendix A for
recommended power cord. See PDI full line catalog for detailed specifications on power cords.
145 Algonquin Parkway, Whippany, NJ 07981 • 973-560-0019 • FAX: 973-560-0076
e-mail: [email protected] • www.powerdynamics.com
75
HGN-368 Series Example & Ordering Code
HGN-368 - 1
CURRENT RATING (A):
=
=
=
=
SCHEMATIC:
M - F1
1
2
4
6
STANDARD TYPE
=
WITHOUT C(Y); C(X) ONLY
=M
TERMINAL:
BLANK
QUICK CONNECT (6.3 x 0.8)
= F1
= F2
SOLDER
Attenuation Tables & Schematics
Non-Medical Applications
Insertion loss in dB (50 Ohm circuit)
Current
L
Comm. Mode(L-G) MHz
Diff. mode(L-L) MHz
Rating Value .01 .05 .1 .15 .5 1 5 10 30 .01 .05 .1 .15 .5 1 5 10 30
29
30
19
18
32
35
21
20
49
50
32
30
60 58
58 58
40 60
35 49
70
70
50
60
30 2
40 3
38 2
33 10
5
8
5
12
6
10
9
15
5
10
11
13
43
35
9
9
67
60
40
40
82
83
81
75
70
78
73
75
39
38
39
60
E
P
2200pF
N'
E'
2200pF
LOAD
21
24
10
10
0.068 F
11
12
3
4
1M
10.3mA
4.6mA
1.2mA
0.8mA
LINE
1A
2A
4A
6A
L(mH)
N
P'
L(mH)
Medical Applications
Insertion loss in dB (50 Ohm circuit)
76
23
18
10
8
32
30
17
13
38
35
20
17
41
36
22
19
51
41
30
26
47 36
42 37
33 33
28 29
31
30
30
29
22
21
22
24
3 5
2 5
5 8
8 13
5
5
8
11
4 50 69 81 74
8 48 69 82 73
7 9 48 82 78
8 9 41 83 80
34
35
45
62
E
P
N'
E'
LOAD
10.3mA
4.6mA
1.2mA
0.8mA
L(mH)
N
0.068 F
1A
2A
4A
6A
Comm. Mode(L-G) MHz
Diff. mode(L-L) MHz
.01 .05 .1 .15 .5 1 5 10 30 .01 .05 .1 .15 .5 1 5 10 30
1M
L
Value
LINE
Current
Rating
P'
L(mH)
145 Algonquin Parkway, Whippany, NJ 07981 • 973-560-0019 • FAX: 973-560-0076