Powerbox NAM-16-000 Ac filter Datasheet

OPEN FRAME & ENCLOSED
NAM
A C F I LT E R
Features
•
•
•
•
•
Low leakage current type.
Single Phase 250Vac.
Selectable leakage current.
Quick and easy push down terminal.
Din rail installation type (Option).
Specifications
Ordering Information
INPUT
Voltage
250Vac/250Vdc, 1 phase
Test voltage
(Terminal-mounting plate)
2.5kVac (cutoff current = 20mA), 1 minute at
room temperature and humidity.
Isolation resistance
(Terminal-mounting plate)
500Vdc, 100MW minute at room temperature
and humidity.
OUTPUT
Current
See table.
Leakage current
5mA/10mA max (125/250Vac, 60Hz)
Voltage drop
1.0V max
NAM
(1)
CODE
CURRENT
04
4A
-25°C to 85°C (Refer to derating ).
Operating temperature
-40°C to 85°C (Refer to derating curve).
Storage temperature
-40°C to 85°C
Humidity
20% to 95% RH (Non-condensing)
Vibration
10 to 55Hz, 19.6m/s2 (2G), 3min. Period, 1 hour
each X, Y and Z axis.
Impact
196.1m/s2 (20G), 11ms once each X, Y and Z axis.
STANDARDS
Safety
142
UL1283, CSA C 22.2 No. 8 (C-UL), DIN EN133200
VDE0565 Teil3-1, ENEC (At only AC input).
-000
(3)
_
(4)
1.Model name
2.Rated current
3.
Line to ground capacitor code
4.
Options
D: Din rail installation type
ENVIRONMENTAL
Safety agency approval
Temperature
-10
(2)
06
6A
10
10A
16
16A
20
20A
30
30A
CODE
LEAKAGE
CURRENT(INPUT
125/250V 60HZ)
LINE TO GROUND
CAPACITOR(NOMINAL
VALUE)
000
5MA / 10MA max
Not Provided
101
12.5MA / 25MA max
100pF
221
25MA / 50MA max
220pF
331
37.5MA / 75MA max
330pF
471
50MA / 100MA max
470pF
When the line to ground capacitor code is different, the attenuation
characteristic is different.
Similar pages