Cooper FRS-R-110 Fusetronâ ¢ 600 v class rk5, frs-r â 600 vac/300 vdc, 1/10-60 a, dual element, time-delay fus Datasheet

Technical Data 1017
Effective May 2016
Supersedes August 2013
BUSSMANN
SERIES
Fusetron™ 600 V Class RK5, FRS-R — 600 Vac/300 Vdc,
1/10-60 A, dual element, time-delay fuses
Catalog symbol:
•
FRS-R-(amp) (non-indicating)
•
FRS-R-(amp)ID (indicating)
Description:
•
Advanced protection, energy efficient
Class RK5 dual element, current-limiting,
time-delay fuses with optional open fuse
indication on select ratings
•
Time-delay – 10 second (minimum) at 500%
of rated current
Specifications:
Ratings
•
Volts
• 600 Vac, 300 Vdc (1/10-30 A)
•
600 Vac, 250 Vdc (35-60 A)
•
Amps — 1/10-60 A
•
Interrupting rating
• 200 kA Vac RMS Sym
•
•
•
•
•
•
Offers a 10-second time delay at 5 times the
rated current
•
The time-delay feature makes it possible
to use fuse amp ratings that are much
smaller than those of non-time delay
fuses. Considerable cost savings occur by
permitting the use of smaller size switches,
panels, and fuses themselves.
•
Provides current limitation to help protect
downstream components from high fault
currents.
•
Gives motor running back-up protection to
motors without extra costs.
Dimensions - in:
Catalog numbers (amps) — Non-indictaing fuses
FRS-R-1/10
FRS-R-1 8/10
FRS-R-8*
CE, UL® Listed, Std. 248-12, Class RK5, Guide
JDDZ, File E4273
FRS-R-1/8
FRS-R-2
FRS-R-9*
FRS-R-15/100
FRS-R-2 1/4
FRS-R-10*
CSA® Certified, C22.2 No. 248.12, Class
1422-02, File 53787
FRS-R-2/10
FRS-R-2 1/2
FRS-R-12*
FRS-R-1/4
FRS-R-2 8/10
FRS-R-15*
CE
FRS-R-3/10
FRS-R-3
FRS-R-17 1/2*
FRS-R-4/10
FRS-R-3 2/10
FRS-R-20*
FRS-R-1/2
FRS-R-3 1/2
FRS-R-25*
FRS-R-6/10
FRS-R-4
FRS-R-30*
FRS-R-8/10
FRS-R-4 1/2
FRS-R-35*
FRS-R-1
FRS-R-5
FRS-R-40*
FRS-R-1 1/8
FRS-R-5 6/10
FRS-R-45*
Closer sizing allows for smaller fuses and
less costly switches
FRS-R-1 1/4
FRS-R-6*
FRS-R-50*
FRS-R-1 4/10
FRS-R-6 1/4*
FRS-R-60*
Class RK5 fuses with a 200 kA interrupting
rating for use in a broad range of
applications
FRS-R-1 1/2
FRS-R-7*
–
FRS-R-1 6/10
FRS-R-7 1/2*
–
Features:
•
Dual-element fuses can be applied in circuits
subject to temporary motor overloads
and surge currents to provide both high
performance short-circuit and overload
protection
20 kA Vdc
Agency information:
•
•
Dual-element feature provides the best
time-delay performance, allowing closer
sizing and superior protection of motors and
transformers
•
Provides motor overload, ground fault, and
short-circuit protection
•
Helps protect motors against burnout from
overloads and single-phasing when sized
properly
* Open fuse indication available by inserting the sufix
“ID.” E.g., FRS-R-15ID.
Technical Data 1017
Fusetron™ 600 V class RK5 FRS-R — 600 Vac/
300 Vdc, 1⁄10-60 A, dual element, time-delay fuses

Effective May 2016
Carton quantity:
Amp rating
Carton qty.
1/10-60
10
For additional information on the R600, 600 volt fuse blocks, see
data sheet No. 1111.
Time-current curves–average melt
10 to 60 amps
Recommended fuse blocks
Fuse amps
1-Pole
2-Pole
3-Pole
0-30
RM60030-1
RM60030-2
RM60030-3
35-60
RM60060-1
RM60060-2
RM60060-3
Amp rating
Fuse reducers for class R fuses
Equipment
fuse clips
Desired fuse
(case) size
Catalog number
(pairs) 600V
60A
30A
No. 663-R
100A
30A
No. 216-R
60A
No. 616-R
60A
No. 626-R
200A
For additional information on class R fuse reducers, see data
sheet No. 1118.
Time-current curves–average melt
1/10 to 8 amps
Time in seconds
Time in seconds
Amp rating
Current in amps
2
Eaton.com/bussmannseries
Current in amps
Technical Data 1017
Effective May 2016
Fusetron™ 600 V Class RK5 FRS-R — 600 Vac/
300 Vdc, 1⁄10-60 A, dual element, time-delay fuses

Current-limitation curves
Current-limiting effects
B
400000
Prosp.
S.C.C.
300000
Instantaneous peak-let-through current in amps
Amp rating
200000
100000
90000
80000
70000
60000
50000
40000
30000
20000
60A
10000
9000
8000
7000
6000
30A
5000
4000
3000
A
Let-through current
(apparent RMS symmetrical vs. fuse rating)
—
30A
60A
5000
1000
1000
10,000
1000
2000
15,000
1000
2000
20,000
2000
2000
25,000
2000
2000
30,000
2000
3000
35,000
2000
3000
40,000
2000
3000
50,000
2000
3000
60,000
2000
3000
70,000
3000
4000
80,000
3000
4000
90,000
3000
4000
100,000
3000
4000
150,000
3000
5000
200,000
4000
6000
2000
200000
50000
60000
70000
80000
90000
100000
30000
40000
20000
6000
7000
8000
9000
10000
5000
3000
4000
2000
1000
1000
RMS Stmmetrical current in amps
A-B = asymmetrical available peak (2.3 x sym RMS amps)
The only controlled copy of this Data Sheet is the electronic read-only version located on the Eaton Network Drive. All other copies of this
document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical
information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction
of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice,
any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible
applications.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2016 Eaton
All Rights Reserved
Printed in USA
Publication No. 1017 – BU-MC16054
May 2016
3
Eaton.com/bussmannseries
For Eaton’s Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Eaton, Bussmann and Fusetron are
valuable trademarks of Eaton in the US
and other countries. You are not permitted
to use the Eaton trademarks without prior
written consent of Eaton.
CSA is a registered trademark of the
Canadian Standards Group.
UL is a registered trademark of the
Underwriters Laboratories, Inc.
Follow us on social media to get the
latest product and support information.
Similar pages