ETC2 A50QS70-4 Semiconductor protection fus Datasheet

AMP-TRAP®–Form 101
A50QS
SEMICONDUCTOR PROTECTION FUSES
A50QS Amp-trap® Form 101 fuses grew out of the
need to improve the overall performance of
semiconductor fuses in response to new equipment
requirements. The A50QS encompasses the best
protection features – lower I2t to provide better
protection for equipment, longer life when subjected
to cyclic loading and lower watts loss. A50QS is
today’s best choice for the protection of dynamic
solid state equipment such as motor drives,
inverters, UPS, etc.
Ratings
➤ AC: 35-60A
500VAC, 200kA I.R.
70-1200A
500VAC, 200kA I.R.
➤ DC: 35-1200A
500VDC, 100kA I.R.
Approvals
➤ UL Recognized
Component
➤ AC: UL Guide No. JFHR2
➤ DC Tested to UL
Standard 198L
parameters (70-1200A)
➤ CSA Certified
LR12636
Features / Benefits
➤ Lowest l2t for greatest protection of semiconductor
circuits
➤ Low watts loss for cooler operation
HIGHLIGHTS:
APPLICATIONS:
500V AC/DC Rated
2
➤ Lowest l t
➤ Low Watts Loss
➤ Superior Cycling
Ability
➤
➤
Protection of 500V or
less motor drives,
UPS, inverters, etc.
➤ Superior cycling ability gives an equipment design
advantage
➤ State-of-the-art protection for 500 volt equipment
➤ Ultra compact sizes allow down-sizing of existing
equipment
Catalog Numbering System
Amp-trap® Fuse
Single Pole Fuse Blocks for A50QS Fuses
FUSE
AMPERE
RATING
MOUNTING
TYPE
FUSE BLOCK
CATALOG
NUMBER
1 - 30
35-200
225-600
4
4
P243E
P266C
A
Rated Volts - 500
50
Style
QS
Amperes*
Mounting Type*
Blades, bolt-in
A 50 QS 250 - 4
250
4
* For ampere ratings and types not listed, consult the factory.
D 12
AMP-TRAP®–Form 101
A50QS
SEMICONDUCTOR PROTECTION FUSES
Standard Fuse Ampere Ratings, Catalog Numbers
AMPERE
RATING
CATALOG
NUMBER
AMPERE
RATING
CATALOG
NUMBER
35
40
50
60
70
80
90
100
125
150
175
200
225
A50QS35-4
A50QS40-4
A50QS50-4
A50QS60-4
A50QS70-4
A50QS80-4
A50QS90-4
A50QS100-4
A50QS125-4
A50QS150-4
A50QS175-4
A50QS200-4
A50QS225-4
250
300
350
400
450
500
600
700
800
900
1000
1200
A50QS250-4
A50QS300-4
A50QS350-4
A50QS400-4
A50QS450-4
A50QS500-4
A50QS600-4
A50QS700-4
A50QS800-4
A50QS900-4
A50QS1000-4
A50QS1200-4
D
For ampere ratings and styles not listed, call Technical Services.
Dimensions
CATALOG
NUMBER
MOUNTING
TYPE
A50QS35 to 100
4
A50QS125 to 200
4
A50QS225 to 400
4
A50QS450 to 600
4
A50QS700 to 800
4
A50QS900 to 1200
4
DIMENSIONS - INCHES (mm)
D
E
A
B
C
F
G
H
3.63
(92.2)
3.63
(92.2)
1.00
(25.4)
1.22
(31.0)
2.13
(54.1)
2.13
(54.1)
2.94
(74.7)
2.94
(74.7)
2.75
(69.9)
2.81
(71.4)
0.31
(7.9)
0.31
(7.9)
0.75
(19.1)
1.00
(25.4)
0.13
(3.3)
0.19
(4.8)
4.34
(110)
4.47
(114)
1.50
(38.1)
2.00
(50.8)
2.09
(53.1)
2.22
(56.4)
3.41
(86.6)
3.53
(89.7)
2.78
(70.6)
2.91
(73.9)
0.41
(10.4)
0.41
(10.4)
1.00
(25.4)
1.50
(38.1)
0.25
(6.4)
0.25
(6.4)
6.47
(164.3)
6.97
(177.0)
2.50
(63.5)
3.00
(76.2)
2.22
(56.4)
3.22
(81.8)
5.00
(127.0)
5.47
(138.9)
3.44
(87.3)
4.47
(113.5)
.53
(13.5)
.63
(15.9)
1.50
(38.1)
2.38
(60.3)
.25
(6.4)
.44
(11.1)
Watts Loss at Rated Current
Watts Loss vs. Percent Rated Current
Correction Factor for Watts Loss
AMPERE
RATING
35
40
50
60
70
80
90
100
125
150
175
200
225
WATTS
LOSS(w)
6
7
8
10
12
14
15
17
21
25
29
33
37
AMPERE
RATING
250
300
350
400
450
500
600
700
800
900
1000
1200
WATTS
LOSS(w)
41
49
57
65
69
77
92
110
130
140
160
175
Correction factor example: At 80% rated current, watts
loss equals .54 times watts loss at rated current.
Percent Rated Current
D 13
AMP-TRAP®–Form 101
A50QS
SEMICONDUCTOR PROTECTION FUSES
A50QS35 to 1200
Time in Seconds
Melting Time – Current Data, 500V Fuses
Current in Amperes
Maximum Peak Arc Volts
Maximum Arc Volts vs. System Voltage
Maximum Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – A50QS35 to 1200, 500 Volts AC
Circuit Voltage (Volts RMS)
Available Current in RMS Symmetrical Amperes
D 14
AMP-TRAP®–Form 101
A50QS
SEMICONDUCTOR PROTECTION FUSES
I2t Data – 500 Volts AC
I2t DATA
(A2s x 103)
(A2s x 103)
(A2s x 103)(Fig B)
35
40
50
60
70
80
90
100
125
150
175
200
225
250
300
350
400
450
500
600
700
800
900
1000
1200
.09
.11
.18
.25
.31
.43
.57
.74
.94
1.5
2.5
3.3
4.1
4.9
9.2
15
16
21
26
37
53
72
98
112
200
.56
.69
1.1
1.6
1.9
2.6
3.6
4.4
5.6
9
15
20
25
29
55
88
98
130
160
220
270
360
500
560
930
.34
.4
.68
.94
1.1
1.5
2.1
2.7
3.4
5.4
9
12
15
18
33
53
59
76
94
130
160
220
300
330
550
Fig. A
Load
Fault
500 VAC
Clearing I2t vs. AC Operating Voltage
D
Operating Voltage (AC RMS Volts)
Clearing I2t at 500V DC, 100kA, L/R = 10 ms
CLEARING I2t
(A2s x 103)
.48
.58
1.0
1.3
1.6
2.2
3.0
3.8
4.8
7.7
13
17
21
AMPERE
RATING
250
300
350
400
450
500
600
700
800
900
1000
1200
CLEARING I2t
(A2s x 103)
25
47
75
83
110
130
190
220
260
350
430
660
DC Voltage Capability vs. Time Constant
DC Voltage Capability
AMPERE
RATING
35
40
50
60
70
80
90
100
125
150
175
200
225
Load
Fig. B
2
RATING
Fault
500 VAC
Correction Factor for I t
FUSE
MAX. CLEARING I2t @ 500VAC
AMPERE MELTING I2t 1 FUSE (Fig A) 2 FUSES IN SERIES
DC Application: A50QS Fuses have been designed for both AC
and DC operation. A50QS fuses (70-600) have UL Component
Recognition at 500V DC and have been tested to circuit parameters
as defined in Standard 198L.