LEM DHR200C420 Ac/dc current transducer Datasheet

AC/DC Current Transducer DHR-C420
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement). True RMS 4-20 mA
current output.
IPN = 100 .. 400 A
Electrical data
Primary Nominal
DC & AC Current
IPN (A.t.RMS)
100
200
300
400
RL
VC
IC
ISL
ÎP
Primary AC Current
Max. Peak Value 1)
IP (A)
600
600
1000
1000
Output current
IOUT (mA DC)
4-20
4-20
4-20
4-20
Load resistance
Supply voltage2)
Current consumption
Output current limitation
Overload capability (Ampere Turns)
Type
Features
DHR 100 C420
DHR 200 C420
DHR 300 C420
DHR 400 C420
< 300
+ 20 .. 50
30 mA + IOUT
< 25
30000
W
V DC
mA
A.t
Performance data
X
e
L
IOUT
IOE
TCIOE
TCIOUT
tr
BW
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (1% of IPN .. ± IPN)
Output current @ IP=0, TA = 25°C
Electrical offset current @ TA = 25°C
Temperature coefficient of IOE ( 0..+60 °C)
(-40..+70 °C)
Temperature coefficient of IOUT (% of reading)
Response time to 90 % of IPN step
Frequency bandwidth (± 1 dB) < ± 1
% of IPN
< ± 1.0
% of IPN
4 mA+/- IOE
< ± 1.0
% of IPN
± 3.2
mA/K
± 6.4
mA/K
± 0.1 %/K
< 150
ms
DC 20..6000
Hz
General data
TA
TS
m
IPxx
Surrounding operating temperature
Surrounding storage temperature
Mass
Protection degree
- 40 .. + 70
- 40 .. + 85
260
IP20
°C
°C
g
Notes : 1) The Max. Peak AC Current is the highest peak level of the primary signal that is taken into account for accurate True RMS calculation. Yet the device is designed for maximum continuous True RMS value equal to
IPN, whereas the output is limited by the above specified output limitation.
2)
According to the UL 508 Standard for Safety for Industrial Control Equipment, the supply voltage must not exceed 42VDC.
●● VFD and SCR waveforms current
measurement
●● True RMS output
●● 4-20 mA current output
●● Panel mounting
●● Eliminates insertion loss
●● Isolated plastic case recognized
according to UL94-V0
Advantages
●● Large aperture for cable up to
Ø32mm
●● High isolation between primary
and secondary circuits
●● Easy installation
Applications
●● VFD Controlled Loads
VFD output indicates how the
motor and attached load are
operating.
●● SCR Controlled Loads
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs. Current
measurement gives faster
response than temperature
measurement.
●● Switching Power Supplies and
Electronic Ballasts
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Application domain
●● Energy and Automation
Page 1/4
120426/21
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer DHR-C420
Isolation characteristics
Vb
Vd
Vw
dCp
dCl
CTI
Rated isolation voltage rms 3)
300
V
according to the standard IEC 61010-1 and with the following conditions:
- Reinforced isolation
- Over voltage category CAT III
- Pollution degree PD2
- Heterogeneous field
Rms voltage for AC isolation test 4), 50 Hz, 1min
4.0
kV
Impulse withstand voltage 4), 1.2/50 uS
7.3 kV
Creepage distance
7.2
mm
Clearance distance
7.2
mm
Comparative tracking index (Group I)
> 600
Notes :3) Between primary conductor voltage and ground. The voltage category could be improved according to the insulation characteristic given by the cable manufacturer. The UL 508 Standard for Safety for Industrial Control Equipment requires that only insulated conductors are used as primary circuit with this transducer.
4)
Between primary (completely filling the aperture) and secondary.
Transfer characteristics
Output in mA
20
4
-Ipn
+Ipn
Page 2/4
120426/21
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer DHR-C420
Safety and warning notes
In order to guarantee safe operation of the transducer and to be able to make proper use of all features and functions,
please read these instructions thoroughly!
Safe operation can only be guaranteed if the transducer is used for the purpose it has been designed for and within the
limits of the technical specifications.
Ensure you get up-to-date technical information that can be found in the latest associated datasheet under www.lem.com.
Caution! Risk of danger
Ignoring the warnings can lead to serious injury and/or cause damage!
The electric measuring transducer may only be installed and put into operation by qualified personnel
that have received an appropriate training.
The corresponding national regulations shall be observed during installation and operation of the transducer and any electrical conductor.
The transducer shall be used in electric/electronic equipment with respect to applicable standards and
safety requirements and in accordance with all the related systems and components manufacturers’
operating instructions.
Caution! Risk of electrical shock
When operating the transducer, certain parts of the module may carry hazardous live voltage (e.g.
primary conductor, power supply).
The user shall ensure to take all measures necessary to protect against electrical shock.
The transducer is a built-in device containing conducting parts that shall not be accessible after installation.
A protective enclosure or additional insulation barrier may be necessary.
The transducer shall not be put into operation if the jaw opening is open (split core version) or the
installation is not completed.
Installation and maintenance shall be done with the main power supply disconnected except if there
are no hazardous live parts in or in close proximity to the system and if the applicable national regulations are fully observed.
Safe and trouble-free operation of this transducer can only be guaranteed if transport, storage and installation are carried
out correctly and operation and maintenance are carried out with care.
Page 3/4
120426/21
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions DHR-C420 (in mm. 1 mm = 0.0394 inch)
25
70
Dimensions DHR-C420 (in mm.
60 1 mm = 0.0394 inch)
4.
60
25
40
40
4
22.28
20.34
10
2.50
15
25
8.30
22.28
90
6.80
8.30
6.80
10
70
32
25
15
6.80
6.80
4.
60
70
32
70
60
15
25.60
2.50
4
15
25.60
7
78
6
8.30
6
4.60
33.80
8.30
4.60
33.80
90
Plug
connector:
Plugin in
connector:
FKC2.5/4-ST-5.08
FKC 2.5/4-ST-5.08-RF
(Phoenix
Contact)
(Phoenix
Contact)
78
DHR-C420
Connections
Connections
●● Wires up to Ø 2 mm
DHR
• Wires
to ∅ 2connector
mm
●● up
Female
provided (spring terminal blocks)
(springconnection
terminal blocks)
• Female
connector provided
●● User-friendly
spring-cage
for no-tool direct
• User-friendly
spring-cage
connection for no-tool
conductor
connection
direct conductor connection
Output Connector
1(Vcc) 2(Iout) 3(NC) 4(GND)
Mechanical characteristics
24 VDC Power
●● General
tolerance
Mechanical
characteristics
±1 mm
●● Primary aperture
Ø 32.0 mm
• General
tolerance
±1 mm
●● Panel
mounting
4 holes Ø 4.6 mm
• Primary
aperturebetween holes
∅ 32.0 mm 70.0 mm & 78 mm
●● Distance
• Panel mounting
4 holes ∅ 4.6 mm
(see above dimensions)
• Distance
holes
70 M4
mm screws
& 78 mm
Forbetween
panel mounting,
use
(not supplied) with
(see
above
drawings)
appropriate length to panel´s thickness,
and tighten to
For panel0.75Nm
mounting,
replace
M4 screws by new one (not supplied)
+/-20%
torque.
(+)
(-)
(-)
(+)
Load
with appropriate length to panel´s thickness.
(Controller, meter etc)
Remarks
●● The temperature of the primary busbar can not exceed
Remarks
90 °C.
OUT
Is
+24VDC
Ip
GND
120426/21
080725/16
• The ●temperature
of the primary conductor
canwith
not a
exceed
90 °C.
● Dynamic performances
are the best
primary
• Dynamic
performances
arefilling
the best
a primary
conductor
busbar
completely
the with
primary
aperture.
completely
the primary
aperture.
●● Thisfilling
is a standard
model.
For different versions
• This is (supply
a standard
model.
For
different
versions
(supply voltages,
voltages, different
outputs,
bidirectional
differentmeasurements...),
outputs, bidirectional
measurement,...),
please contact us. please
Page 4/4
contact us.