Lineage Power CAR1248FPBCXZ01A Universal input with pfc constant power characteristic 3 front panel leds: 1-input;2-output; 3 - fault Datasheet

GE
Data Sheet
CAR1248FP series rectifier
Input: 90VAC to 264VAC; Output: 48VDC @ 1200W; 5 VDC @ 0.5A
RoHS Compliant
Features

Universal input with PFC

Constant power characteristic

3 front panel LEDs: 1-input;2-output; 3 - fault

Remote ON/OFF control of the 48VDC output

Remote sense on the 48VDC output

No minimum load requirements

Redundant parallel operation

Active load sharing (single wire)

Hot Plug-ability
Applications

Efficiency: typically 91% @ 50% load

48VDC distributed power architectures

Standby 5VDC


Auto recoverable OC & OT protection
Cellular Base Stations

Operating temperature: 0 - 70C (de-rated above 50C)

Blade Servers

Digital status & control: I2C serial bus

Network Equipment

EN/IEC/UL60950-1 2nd edition; UL, CSA and VDE

Network Attached Storage

EMI: class A FCC docket 20780 part 15, EN55022


Meets EN6100 immunity and transient standards
Telecom Access Nodes

Shock & vibration: NEBS GR-63-CORE, level 3

Routers/Switches

Broadband Switches

ATE Equipment
Description
The CAR1248FP series of rectifiers provide highly efficient isolated +48VDC power from worldwide input mains in a
compact density of 19W/in3 within a 1U industry standard form factor.
The high-density, front-to-back airflow is designed for minimal space utilization and is highly expandable for future
growth. I2C communications offers remote control and monitoring capabilities.
*
†
‡
§
**
UL is a registered trademark of Underwriters Laboratories, Inc.
CSA is a registered trademark of Canadian Standards Association.
VDE is a trademark of Verband Deutscher Elektrotechniker e.V.
Intended for integration into end-user equipment. All the required procedures for CE marking of end-user equipment should be followed. (The CE mark is placed on selected products.)
ISO is a registered trademark of the International Organization of Standards.
February 26, 2013
©2013 General Electric Company. All rights reserved.
GE
Data Sheet
CAR1248FP series rectifier
Input: 90VAC to 264VAC; Output: 48VDC @ 1200W; 5 VDC @ 0.5A
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional
operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet.
Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.
Parameter
Symbol
Min
Max
Unit
Input Voltage: Continuous
VIN
0
264
VAC
Operating Ambient Temperature
TA
-10
701
°C
Storage Temperature
Tstg
-40
I/O Isolation voltage to Frame (100% factory Hi-Pot tested)
85
°C
1500
VAC
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.
INPUT
Parameter
Symbol
Min
Typ
Max
Unit
VIN
FIN
90
110/230
264
VAC
Frequency Range
47
50/60
63
Hz
Main Output Turn_OFF
VIN
80
VAC
IIN
7.9
12.75
AAC
IIN
40
Apeak
Operational Range
Maximum Input Current (IOUT=IO, max) VIN= 180VAC
VIN= 100VAC
Cold Start Inrush Current
(Excluding x-caps, 25C, <10ms, per ETSI 300-132)
Efficiency
(TAMB=25C, VIN= 230VAC, VOUT= 48VDC, IOUT=IO, max)
Power Factor
(VIN=230VAC, IOUT=IO, max)
Holdup time
Vin=
230VAC
(VOUT= 48VDC, TAMB 25C, IOUT=IO, max)
VIN= 90VAC
Early warning prior to loss of DC output below regulation
Ride through
Leakage Current
(Vin= 250VAC, Fin = 60Hz)
Isolation
Input/Output

91
PF
0.99
T
16.7
20
ms
T
2
8.3
ms
ms
IIN
3
mArms
Input/Frame
Output/Frame
%
3000
VAC
1500
VAC
500
VDC
48VDC MAIN OUTPUT
Parameter
Output Power
180 – 264 VAC
90 – 132VAC
Set point
Overall regulation (load, temperature, aging)
Ripple and noise2
Turn-ON overshoot
1
2
Symbol
W
VOUT
Min
Typ
Max
Unit
0
-
1200
W
0
47.76
-3
48.00
1000
48.24
+3
540
+3
W
VDC
%
mVp-p
%
Derated above 50C at 2.5%/C
Measured across a 10µf electrolytic and a 0.1µf ceramic capacitors in parallel. 20MHz bandwidth
February 26, 2013
©2013 General Electric Company. All rights reserved.
Page 2
GE
Data Sheet
CAR1248FP series rectifier
Input: 90VAC to 264VAC; Output: 48VDC @ 1200W; 5 VDC @ 0.5A
48VDC MAIN OUTPUT (continued)
Parameter
Symbol
Max
Unit
2
40
50
sec
ms
ms
-5
+5
%VOUT
42.8
56
VDC
60
VDC
0
25
20.8
ADC
Current limit, Hiccup (programmable level)
110
130
% of FL
Active current share
-10
+10
% of FL
Max
Unit
Turn-ON delay
Remote ON/OFF delay time
Turn-ON rise time (10 – 90% of VOUT)
Transient response 50% step [10%-60%, 50% - 100%]
(dI/dt – 1A/µs, recovery 300µs)
Programmable range (hardware & software)
Overvoltage protection, latched
(recovery by cycling OFF/ON via hardware or software)
Output current Vin – high line
Vin – low line
Min
Typ
T
VOUT
58
IOUT
59
STANDBY OUTPUT
Parameter
Symbol
Set point
VOUT
Overall regulation (load, temperature, aging)
VOUT
Ripple and noise
Output current
Overload protection Isolation
Output/Frame
Min
Typ
5.0
VDC
-5
+5
%
50
IOUT
0
mVp-p
ADC
ADC
VDC
0.5
1.5
500
General Specifications
Parameter
Min
Reliability
Typ
Max
100,000
Service Life
10
Units
Notes
Hrs
Full load, 50C ; MTBF per SR232 Reliability
protection for electronic equipment, method I,
case III,
Yrs
Full load, excluding fans
Kgs
(Lbs)
Weight
Feature Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions. See
Feature Descriptions for additional information.
Parameter
Symbol
Min
Typ
Max
Unit

20
µA
Remote ON/OFF (Needs to be pulled HI via an external resistor)
Logic High (Module ON)
IIH
Logic Low (Module OFF)
VIH
0.7VDD

12
VDC
IIL
VIL

0


1
0.8
mA
VDC
Feature Specifications (continued)
February 26, 2013
©2013 General Electric Company. All rights reserved.
Page 3
GE
Data Sheet
CAR1248FP series rectifier
Input: 90VAC to 264VAC; Output: 48VDC @ 1200W; 5 VDC @ 0.5A
Parameter
Symbol
Min
Typ
Max
Unit
Vprog range
Programmed output voltage range
Voltage adjustment resolution (8-bit A/D)
Vprog
Vo
Vo
0.364
43.2
3.27
52.8



12

VDC
VDC
mVDC
Output configured to the 48VDC set-point
Vprog
4.0


VDC
48V output OFF
VI
0.7VDD

12
VDC
48V output ON
VI
0

0.8
VDC
VI
VI
0.7VDD
0


12
0.8
VDC
VDC

20
µA
VOH
0.7VDD

12
VDC
IOL
VOL

0


20
0.4
mA
VDC

20
µA
VOH
0.7VDD

12
VDC
IOL


20
mA
VOL
0

0.4
VDC

20
µA
VOH
0.7VDD

12
VDC
Output Voltage programming (Vprog)
Equation: VOUT = 43.2 +3.3 (Vprog -0.364)
Enable [short pin controlling presence of the 48VDC output]
Write protect (Wp)
Write protect enabled
Write protect disabled
INPUT-OK (Needs to be pulled HI via an external resistor)
Logic High (Input within normal range)
IOH
Logic Low (Input out of range)
DC-OK ( Internally connected to 3.3V via a 10kΩ resistor)
Logic High (Output voltage is present)
IOH
Logic Low (Output voltage is not present)
Over Temperature Warning (Needs to be pulled HI via an external
i t )
Logic High (temperature within normal range)
Logic Low (temperature is too high)
Delayed shutdown after Logic Low transition
IOH
IOL


20
mA
VOL
0

0.4
VDC
Tdelay
10
sec
Fault (Needs to be pulled HI via an external resistor)
Logic High (No fault is present)
IOH
Logic Low (Fault is present)

20
µA
VOH
0.7VDD

12
VDC
IOL
VOL

0


20
0.4
mA
VDC
VIL
0

0.1
VDC

20
µA
0.7VDD



12
4
0.4
VDC
mA
VDC
PS Present (Needs to be pulled HI via an external resistor)
Logic High (Power supply is not plugged in)
Logic Low (Power supply is present)
SMBAlert# (Interrupt) (Needs to be pulled HI via an external
resistor)
Logic High (No Alert - normal)
Logic Low (Alert is set)
February 26, 2013
IOH
VOH
IOL
VOL

0
©2013 General Electric Company. All rights reserved.
Page 4
GE
Data Sheet
CAR1248FP series rectifier
Input: 90VAC to 264VAC; Output: 48VDC @ 1200W; 5 VDC @ 0.5A
Parameter
Symbol
Min
Typ
Max
Unit
Measurement range
Io
0
25
ADC
Analog output range
Vmon
0
5
VDC
5
mADC
Output current monitor (Imon)
Resolution
0.2
V/A
Sourced output current
Digital Interface Specifications
Parameter
Conditions
Signal Interface Characteristics
Input Logic High Voltage (CLK, DATA)
Input Logic Low Voltage (CLK, DATA)
Input high sourced current (CLK, DATA)
Output Low sink Voltage (CLK, DATA, SMBALERT#)
Output Low sink current (CLK, DATA, SMBALERT#)
Output High open drain leakage current
(CLK,DATA, SMBALERT#)
Operating frequency range
IOUT=3.5mA
Symbol
Min
VIH
VIL
2.1
0
IIH
0
VOL
Typ
Max
Unit
5.5
0.8
VDC
VDC
10
μA
0.4
VDC
IOL
3.5
mA
VOUT=5.5V
IOH
0
10
μA
Slave Mode
FPMB
10
400
kHz
25
ms
Measurement System Characteristics
Clock stretching
February 26, 2013
tSTRETCH
©2013 General Electric Company. All rights reserved.
Page 5
GE
Data Sheet
CAR1248FP series rectifier
Input: 90VAC to 264VAC; Output: 48VDC @ 1200W; 5 VDC @ 0.5A
Environmental Specifications
Parameter
Min
Max
Units
Ambient Temperature
-103
Typ
70
°C
Storage Temperature
-40
85
°C
Operating Altitude
2250/7382
m/ft
8200/30k
m / ft
Power Derating with Temperature
2.5
%/°C
Power Derating with Altitude
2.0
C/301 m
C/1000 ft
55
dbA
Non-operating Altitude
Acoustic noise
Over Temperature Protection
Humidity
Operating
Storage
120/110
30
10
Shock and Vibration acceleration
Notes
Derated above 50C
50C to 70C
Above 2250 m/7382 ft
Full load
°C
Shutdown / restart
95
95
%
Relative humidity, non-condensing
6
Grms
NEBS GR-63-CORE, Level 3, 20 2000Hz, min 30 minutes
Zone
NEBS GR-63-CORE, all floors, Seismic
Zone 4 Designed and tested to meet
NEBS specifications.
Earthquake Rating
4
EMC Compliance
Parameter
AC input
AC input
immunity
Enclosure
immunity
Criteria
Standard
Level
Test
Conducted emissions
EN55022, FCC Docket 20780 part 15, subpart J
A
0.15 – 30MHz
Radiated emissions**
EN55022
A
30 – 10000MHz
Voltage dips
EN61000-4-11
A
-30%, 10ms
B
-60%, 100ms
B
-100%, 5sec
Voltage surge
EN61000-4-5
A
4kV, 1.2/50µs, common mode
A
2kV, 1.2/50µs, differential mode
Fast transients
EN61000-4-4
B
5/50ns, 2kV (common mode)
Conducted RF fields
EN61000-4-6
A
130dBµV, 0.15-80MHz, 80% AM
Radiated RF fields
EN61000-4-3
A
10V/m, 80-1000MHz, 80% AM
ENV 50140
A
EN61000-4-2
B
ESD
4kV contact, 8kV air
** Radiated emissions compliance is contingent upon the final system configuration.
3
Designed to start at an ambient down to -40°C; meet spec after  30 min warm up period, may not meet operational limits below -10°C.
February 26, 2013
©2013 General Electric Company. All rights reserved.
Page 6
GE
Data Sheet
CAR1248FP series rectifier
Input: 90VAC to 264VAC; Output: 48VDC @ 1200W; 5 VDC @ 0.5A
Control and Status
Analog controls: Details of analog controls are provided in
this data sheet under Signal Definitions.
Common ground: All signals and outputs are referenced to
Output return. These include ‘Vstb return’ and ‘Signal return’.
Control Signals
Voltage programming (Vprog): An analog voltage on this signal
can vary the output voltage from 43.2VDC to 52.8VDC. The
equation of this signal is:
Interrupt: A TTL compatible status signal. Needs to be pulled
HI externally through a resistor. Open collector (HI) on this
signal indicates that no Interrupt has been triggered.
Serial Bus Communications – CAR1248FPxC
The I²C interface facilitates the monitoring and control of
various operating parameters within the unit and transmits
these on demand over an industry standard I²C Serial bus.
All signals are referenced to ‘Signal Return’.
Device addressing: The microcontroller (MCU) and the
EEPROM have the following addresses:
VOUT = 43.2 + 3.3 (Vprog – 0.364) 0.364 < Vprog < 3.27
Device
If Vprog is ≥ 4V, or left open the programming signal is ignored
and the unit output is set at the setpoint of 48VDC.
MCU
EEPROM
Load share (Ishare): Single wire analog signal between power
supplies connected in parallel. The Ishare pins should be tied
together for power supplies. No resistors or capacitors should
get connected to this pin.
Remote ON/OFF: Controls the presence of the main 48VDC
output voltage. This is an open collector, TTL level control
signal. Logic 1 turns ON the 48VDC output, while a Logic 0 turns
OFF the 48VDC output.
A turn OFF command either through this signal or firmware
commanded would turn OFF the 48V output.
Enable: This is a short signal pin that controls the presence of
the 48VDC main output. This pin should be connected to
‘output return’ on the system side of the output connector. The
purpose of this pin is to ensure that the output turns ON after
engagement of the power blades and turns OFF prior to
disengagement of the power blades.
Write protect (WP): This signal protects the contents of the
external EEPROM. When left open the EEPROM is write
protected. A LO permits writing to the EEPROM. This signal is
pulled HI internally by the power supply.
Status signals
Output current monitor (Imon): A voltage level proportional to
the output current is present on this pin.
AC OK: TTL compatible open collector. A (HI) on this signal
indicates that the input voltage is present within limits.
DC OK: TTL compatible, open collector. A (HI) on this signal
indicates that the output voltage is present.
1
1
Address Bit Assignments
(Most to Least Significant)
0
1
1
A2
A1
A0
0
1
0
A2
A1
A0
Address lines (A2, A1, A0): Up to eight (8) modules to be
addressed on a single I²C bus. The pins are pulled HI internal
to the power supply. For a logic LO connect to ‘Output Return’
Serial Clock (SCL): Host generated, this signal needs to be
pulled up externally ensuring that rise and fall time timing and
the maximum sink current is in compliance to the I²C
specification.
Serial Data (SDA): This is a bi-directional line that needs to be
pulled up externally ensuring that rise and fall time timing and
the maximum sink current is in compliance to the I²C
specification.
Command code:
All registers are 16 bits, written as LSB followed by MSB.
All A/D’s are 10 bit (1024 steps). All constants can be fine-tuned
to compensate for manufacturing tolerances;
Name
CMD
Access
Default
/Name
VOUT
IOUT
Temperature
ON/OFF
Ilimit
Vset
Vprog
OT trip
OT recover
DC_OK_HI
DC_OK_LO
00
01
02
03
04
05
06
07
08
09
0A
R
R
R
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
48
-
STATUS
0B
R
0C
0D7C
R
R/W
Over temp warning: TTL compatible, open collector. A (HI) on
this signal indicates that temperatures are normal.
If an over temperature should occur, this signal changes to LO
for 10 seconds prior to shutdown. Unit restarts if internal
temperatures recover to normal operational levels.
Fault: TTL compatible, open collector. A (HI) on this signal
indicates that no faults are present. This signal activates for
OTP, OVP, OCP, or AC fault.
PS Present: Connected to ‘output return’. Its intent is to
indicate to the system that a power supply is present. This
signal may need to be pulled HI externally through a resistor.
12 April 2012
R/W
R/W
Firmware
EEPROM
©2012 General Electric Company. All rights reserved.
Bits
Constant
0.102
0.042
0.005
1 – OFF, 0 – ON
28.6
0.042
48
0.094
VOUT=43.2 + 3.3 (Vprog – 0.364)
120
0.0049
110
0.005
67.5
0.102
28.9
0.102
Input
0
1-LL
AC_OK
1
DC_OK
2
OT
3
1-normal
Fault
4
Intrpt
5
OV
6
DC_INT
7
Page 7
GE
Data Sheet
CAR1248FP series rectifier
Input: 90VAC to 264VAC; Output: 48VDC @ 1200W; 5 VDC @ 0.5A
VOUT [00]: Output voltage read back, returns the voltage on
the anode side of the or’ing function, data LSB followed by
MSB.
The default value is 48VDC
Example; readback 01EBh, convert into its decimal equivalent
and then multiply by the constant, VOUT = 491 x 0.102 =
50.08VDC
IOUT [01]: Output current read back, data LSB followed by MSB.
Vprog [06]; Reads back the hardware configured analog
voltage program value via i2c.
The value can range from 0.364V to 3.27V.
Example: set the output to 44VDC. From the equation
determine that Vprog = 0.6. The 10bit D/A is set for the range
of 0 – 5VDC, therefore with a resolution of 1024 bits each bit is
0.00488V. So the corresponding value to enter is 0.6/0.00488 =
123 decimal. This corresponds to 7Bh. The data should be sent
across the bus as LSB [7B] followed by MSB [00].
Example; readback 021Fh, convert into its decimal equivalent
and multiply by the constant, IOUT=543 x 0.042 = 22.8A
OT trip[07] and OT recover[08]; Configures the OT shutdown
and recovery levels. The default values are;
Temperature [02]: Temperature read back, data LSB followed
by MSB.
OT trip: 120C corresponds to 1.03/0.00488 = D3h
Example; readback 037Bh, convert into its decimal equivalent
and multiply by the xonstant, temp = 891 x 0.0049 = 4.36. In
the table below this corresponds to 25C
Data
Temp
C
Data
Temp
C
Data
Temp
C
4.83
4.78
4.72
4.65
4.56
4.46
4.35
4.21
4.06
3.89
-5
0
5
10
15
20
25
30
35
40
3.71
3.51
3.3
3.09
2.88
2.67
2.46
2.25
2.06
1.88
45
50
55
60
65
70
75
80
85
90
1.7
1.54
1.4
1.26
1.14
1.03
0.93
0.84
95
100
105
110
115
120
125
130
Example: Change the recovery temperature to 100C. In the
look up table above the corresponding level is 1.54. Divide by
the conversion ration, 1.54/0.0049 = 315 dec. Converting to its
hex equivalent yields 013B hex. The data should be sent
across the bus as LSB [3B] followed by MSB [01].
DC_OK_HI[09] and DC_OK_LO[0A]: Changes the DC_OK signal
comparator level. The default values are;
DC_OK_HI: 02CDh, corresponding to 67.5V
DC_OK_LO: 0133h, corresponding to 28.9V
Example: Change the upper level of comparison to 55V.
Determine the corresponding register value setting; 55/0.0941
= 584dec. This is equivalent to 0248h. The data should be
sent across the bus as LSB [48] followed by MSB [02].
STATUS [0B]: All read backs are two bytes and so read back
two bytes but ignore the MSB.
ON/OFF [03]: A logic ‘1’ turns OFF the 48V output of the
power supply.
Ilim [04]: This feature lowers the current limit from the default
values of 02A8h (680), corresponding to 28.6A at high line and
0265h (613) corresponding to 25.8A at low line.
The delivered output current cannot exceed the maximum
power capacity of the unit. Thus, at high line the power supply
is limited to 1200W, thus, at 28.6A the output voltage is limited
to 41.96VDC,
Example: At high line, reduce the current limit to 20A.
Compute the data to be sent to the controller; 20 / 0.042 =
476. The hex equivalent of this decimal data is 01DCh. The
data should be sent across the bus as LSB [DC] followed by
MSB [01].
Vset [05]: Changes the output voltage via i2c, if the Vprog
hardware signal is > 4VDC. If the Vprog pin voltage level is <
4VDC, this command is ignored.
The output voltage setting must be between 42.8 – 56VDC.
The default value is 01FEh, corresponding to 48VDC.
Example; set the output to 54VDC. Compute the data to be
sent to the controller; 54 / 0.094 = 574. The hex equivalent of
this decimal data is 023Eh. The data should be sent across the
bus as LSB [3E] followed by MSB [02].
February 26, 2013
OT recover: 110C that corresponds to 1.26/0.0049 = 0102h
Firmware [0C]: Reads back the latest firmware revision.
MCUeeprom [0D – 7C]: 125 bytes of information may be
stored in the EEPROM section of the micro controller starting
from register location 0Dh. Each byte of data needs to be
stored into its specific register location, one byte at a time.
External EEPROM
A separate EEPROM, with its own i2c address and with
write_protect capability, provides 128 bytes of memory. This is
a standard i2c compliant generic EEPROM with a single byte
for its memory location. Standard i2c command structure
applies.
The following FRU_ID information is stored in this EEPROM
Start
Location
Length
00
07
08
0C
0D
1E
1F
7
1
4
1
17
1
1
Value
20
20
20
©2013 General Electric Company. All rights reserved.
Description
Serial number, ascii
space
Date code [YYWW] ascii
space
Code CAR1248FPBXXXX1A ascii
space
Revision
Page 8
GE
Data Sheet
CAR1248FP series rectifier
Input: 90VAC to 264VAC; Output: 48VDC @ 1200W; 5 VDC @ 0.5A
LEDs
expander that is accessible via address 0 x 4Eh (A2, A1, A0 are
pilled HI). This byte takes the form;
Three LEDs are located on the front faceplate. The AC_OK LED
provides visual indication of the INPUT signal function. When
the LED is ON GREEN the power supply input is within normal
design limits.
7
n/s
6
n/s
5
Fault
4
ON/OFF
3
Temp_OK
2
n/s
1
DCOK
0
ACOK
n/s – not supported
When the DC_OK LED is GREEN the DC output is present.
Bits 0, 1, 3, and 5 are ‘read_only’ and are HI [1] during normal
operation. The rectifier needs to be biased externally in order to ‘read’
its operational state without the presence of input power.
When the FAULT_LED is RED then a fault condition exists and
the power supply may not provide output power. The table
below further defines these states:
Bit 4 is a ‘read/write’ bit that can be used to verify the ON/OFF
commanded state or change the commanded output of the rectifier.
In order to turn the output OFF this bit needs to be pulled LO [0].
I/O Expander option
No PEC support is provided. Standard i2c commands apply.
The CAR1248FPx without extended i2c communications (blank
under the software option) has a single status/control byte I/O
Alarm Table
LED Indicator
Monitoring Signals
Test Condition
AC OK
DC OK
FAULT
FAULT
DC OK
AC OK
TEMP OK
Normal Operation
Low or NO INPUT
Green
Green
OFF
OFF
OFF
OFF
High
Low
High
Low
High
Low
High
High
3
OVP
Green
OFF
Red
Low
Low
High
High
4
Over Current
Green
OFF
Red
High
Low
High
High
Green
Red
5
Over Temp Fault
OFF
Low
Low
Note: Test condition #2 has 2 modules working in parallel. One module is running and the other has no AC.
High
Low
1
2
Connector
FCI Berg P/N: 51939-070
Mating connector: FCI Berg P/N: 51915-050
Pin
Function
Pin
Function
Pin
Function
Pin
Function
A1
Vstb
B1
Fault
C1
ISHARE
D1
VProg
A2
Vstb Return
B2
I Monitor (IMON)
C2
N/C
D2
OVP Test Point
A3
Signal Return
B3
Enable: “0” –ON “1” -OFF
C3
Over Temp Warning
D3
Remote ON/OFF
A4
Write Protect (WP)
B4
PS Present
C4
I2C Address (A0)
D4
DC OK
A5
Remote Sense (+)
B5
SDA (I2C bus)
C5
I2C Address (A1)
D5
AC OK
A6
Remote Sense (-)
B6
SCL (I2C bus)
C6
I2C Address (A2)
D6
Interrupt
P1
Line
P2
Neutral
P3
Chassis
P4
+VOUT
P5
Output Return
February 26, 2013
©2013 General Electric Company. All rights reserved.
Page 9
GE
Data Sheet
CAR1248FP series rectifier
Input: 90VAC to 264VAC; Output: 48VDC @ 1200W; 5 VDC @ 0.5A
Outline Drawing
February 26, 2013
©2013 General Electric Company. All rights reserved.
Page 10
GE
Data Sheet
CAR1248FP series rectifier
Input: 90VAC to 264VAC; Output: 48VDC @ 1200W; 5 VDC @ 0.5A
Ordering Information
Please contact your GE Energy Sales Representative for pricing, availability and optional features.
PRODUCT
DESCRIPTION
PART NUMBER
1200W Front-End
+48VOUT Front-End, 5VSTDBY,
CAR1248FPXXXZ01A
1200W Front-End
+48VOUT Front-End, 5VSTDBY, w/bezel
CAR1248FPBXXZ01A
1200W Front-End
+48VOUT Front-End, 5VSTDBY , w/bezel, i2c communications
CAR1248FPBCXZ01A
PART NUMBER DEFINITION GUIDE EXAMPLE
CAR
12
48
Power
12 = 1200W
Output voltage
48 = 48Vdc
FP
x
x
x
Options
B – bezel
C – i2c option
R – reverse airflow
Vsb – 3 or 5
Type
FP – AC; Vo-positive
TN – AC; Vo-negative
DC - DC
TE – AC; high efficiency
Z
01 A
A – Standard
model
RTM
RoHS
Blank – non compliant
Y – 5 of 6 compliant
Z – 6 of 6 compliant
Contact Us
For more information, call us at
USA/Canada:
+1 888 546 3243, or +1 972 244 9288
Asia-Pacific:
+86.021.54279977*808
Europe, Middle-East and Africa:
+49.89.878067-280
India:
+91.80.28411633
www.ge.com/powerelectronics
February 26, 2013
©2013 General Electric Company. All rights reserved.
Page 11
Similar pages