ETC2 A82-2025 Monitoring relays ac current transformer Datasheet

Monitoring Relays
AC Current Transformer
Types A 82-10, A 82-20
• 5 types of input: 0 - 25 AAC
0 - 50 AAC
0 - 100 AAC
0 - 250 AAC
0 - 500 AAC
• Output: A 82-10: 0 - 20 mADC (source)
A 82-20: 4 - 20 mADC (sink)
• Easy interface to PLC or setpoint relays
Product Description
Ordering Key
AC current metering transformer for 25, 50, 100, 250 or
500 AAC. Output current from
the transformer is 0-20 mADC
or 4-20 mADC in accordance
with IEC 60381-1. Can be
used with relays DIB01,
PIB01, DIC01, PIC01 or
S183 or directly connected
to a PLC. Power supply ON
is indicated by a green LED
on the side of the housing.
Type
Output
Input current
Input current
Output current
Type no.
25 AAC
50 AAC
100 AAC
250 AAC
500 AAC
0 - 20 mA
0 - 20 mA
0 - 20 mA
0 - 20 mA
0 - 20 mA
A 82-10 25
A 82-10 50
A 82-10 100
A 82-10 250
A 82-10 500
25 AAC
50 AAC
100 AAC
250 AAC
500 AAC
4 - 20 mA
4 - 20 mA
4 - 20 mA
4 - 20 mA
4 - 20 mA
A 82-20 25
A 82-20 50
A 82-20 100
A 82-20 250
A 82-20 500
A 82-10 50
Type Selection
Input Specifications
A 82-10/20 25
Current range
0 - 25 AAC
Max. current (continuously)
30 AAC
Max. overload current (t = 30 s)
250 AAC
Rated insulation voltage
Input - output
1000 VAC rms
Overvoltage category
IV (IEC 60664)
Dielectric strength
Dielectric voltage
6 kVAC rms
Rated impulse withstand volt.
12 kV
(1.2/50 µs)
A 82-10/20 50
0 - 50 AAC
60 AAC
300 AAC
A 82-10/20 100
0 - 100 AAC
120 AAC
700 AAC
A 82-10/20 250
0 - 250 AAC
300 AAC
1500 AAC
A 82-10/20 500
0 - 500 AAC
600 AAC
3000 AAC
1000 VAC rms
IV (IEC 60664)
1000 VAC rms
IV (IEC 60664)
1000 VAC rms
IV (IEC 60664)
1000 VAC rms
IV (IEC 60664)
6 kVAC rms
12 kV
(1.2/50 µs)
6 kVAC rms
12 kV
(1.2/50 µs)
6 kVAC rms
12 kV
(1.2/50 µs)
6 kVAC rms
12 kV
(1.2/50 µs)
Specifications are subject to change without notice (25.01.06)
1
A 82-10, A 82-20
Output Specifications
General Specifications
Rated insulation voltage (cable)
Output current
10:
20:
Power supply (loop voltage)
Tolerance of output current
@ 50 Hz
A 82-10
A 82-20
Temperature variation
250 VACrms
0 - 20 mADC
4 - 20 mADC
10 - 40 VDC
Power ON delay
Reaction time
Frequency range
40 Hz -1 kHz
Frequency variation
10 ppm/Hz
Maximum output current
35 mADC
Indication for
Power supply ON
Environment
Degree of protection
Pollution degree
Operating temperature
Housing
Dimensions
Material
Weight
A 82-10
A 82-20
Connection cable A 82-10
A 82-20
Approval
CE marking
EMC
Immunity
±2% ±0.08 mA
± 2%
±400 ppm/ºC
Emission
<1s
τ < 100 ms
worst case reaction time
may be up to 5 x τ
LED, green
IP 20
3 (IEC 60664)
-20° to 50ºC (-4° to +122 ºF)
95 x 67.5 x 20 mm
ABS
300 g
270 g
2 m, 3 x 0.25 mm2
2 m, 2 x 0.25 mm2
UL
Yes
Electromagnetic Compatibility
Acc. to EN 61000-6-1
(tolerance of output current:
± 2%)
Acc. to EN 61000-6-2
(tolerance of output current:
± 5%)
Acc. to EN 61000-6-3
Mode of Operation
A 82-10, A 82-20 are current
metering transformers with
standard source/sink output
0 - 20 mA/4 - 20 mA. This
makes it very useful as an
AC current interface to a
PLC with mADC input.
Used with relays DIB01,
PIB01, DIC01, PIC01 or
S183 one or more setpoints
can monitor the current and
signal alarm. S 183 also provides the DC voltage supply
for the A 82-10, A 82-20.
The metered conductor is
drawn through the central
hole of the current metering
transformer. It is possible to
meter currents below the
nominal range by drawing
the conductor through the
hole several times. If the
conductor is drawn through
the central hole e.g. 5 times,
the transformer will register
50 A when the current in the
conductor is 10 A.
A 82-10 has factory-set gain
(span) adjustment, whereas
A 82-20 has zero as well as
gain (span) adjustment, both
factory-set.
Note: Do not change the set
values.
Wiring Diagrams
A 82-10 ... (source)
A 82-20 ... (sink)
I
I
Grey
Red
2
Black
Black
R load
Power +
supply
Loop +
voltage
R load
Yellow
Specifications are subject to change without notice (25.01.06)
A 82-10, A 82-20
Input/Output Curve
Resistance/Voltage Curve
Output
(mADC)
Max. R load (Ω)
20
16
12
8
4
A
0
-2
82
A
0
-1
82
50
100
Input
(% of range)
(V)
Power supply
(loop voltage)
Max. load resistance versus Power supply (loop voltage)
Dimensions
Specifications are subject to change without notice (25.01.06)