Crydom DRA3P48A2 Din rail mount Datasheet

DRA3P Series
• 2.4 & 4.2 Amp rated Solid State Contactor
• Load voltage range of 48-510VAC, 3-Phase
• Fits standard 35mm DIN-RAIL
• LED input status indicator
• AC or DC control
• Zero-crossing (resistive loads) or random turn-on (inductive loads) output
• cUL Recognized, IEC Rated, CE & RoHS Compliant, Horsepower Rated
• Built in Overvoltage Protection
PRODUCT SELECTION
Description
4-6 VDC Control
18-28 VDC Control
36-60 VAC Control
90-140 VAC Control
200-265 VAC Control
2.4A
4.2A
DRA3P48D2
DRA3P48E2
DRA3P48C2
DRA3P48B2
DRA3P48A2
DRA3P48D4
DRA3P48E4
DRA3P48C4
DRA3P48B4
DRA3P48A4
2.4 A
4.2 A
48-510
1200
2.4/2.4
2.1/2.1 (4)
0.15
1.0
500
1.3 per Channel
285/300
410/375
0.5/0.37 (6)
1.0/0.75 (7)
1.0/0.75 (8)
0.5
24/10
0.5-4.0
12.0 in lb (1.36 Nm)
48-510
1200
4.2/2.4
3.4/2.1
0.15
1.0
500
1.3 per Channel
285/300
410/375
0.75/0.37
1.5/0.75
2.0/0.75
0.5
24/10
0.5-4.0
12.0 in lb (1.36 Nm)
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS AC Output (1)
Description
Operating Voltage (47-63Hz) [Vrms]
Transient Overvoltage [Vpk] (2)
Maximum Resistive Load Current UL/AC51 [Arms] (3)
Maximum Motor Load Current UL/AC53 [Arms] (3)
Minimum Load Current [Arms]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (5)
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Maximum Surge Current (50/60 Hz, 1 cycle) [Apk]
Maximum I²t for Fusing (50/60 HZ, 1/2 cycle) [A² sec]
HP/IEC 60947 Rating @ 240V, 40°C [HP/KW]
HP/IEC 60947 Rating @ 380V, 40°C [HP/KW]
HP/IEC 60947 Rating @ 480V, 40°C [HP/KW]
Minimum Power Factor (with Maximum Load)
Min/Max stranded/solid wire [AWG]
Min/Max stranded/solid wire [IEC mm²]
Load Terminal Screw Torque Range:
INPUT SPECIFICATIONS (1)
Description
Control Voltage Range
Minimum Turn-On Voltage
Minimum Turn-Off Voltage
Minimum Input Current [mA]
Maximum Input Current [mA]
Nominal Input Impedance [Ohms]
Maximum Turn-On Time (9)
Maximum Turn-Off Time
Min/Max stranded/solid wire [AWG]
Min/Max stranded/solid wire [IEC mm²]
Control Terminal Screw Torque Range:
DRA3P48Dx
DRA3P48Ex
GENERAL SPECIFICATIONS (1)
Description
Dielectric Strength, Input/Output/Base (50/60Hz)
Minimum Insulation Resistance (@ 500 V DC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Weight (typical)
Housing Material (bottom cover)
Housing Material (end pieces)
Parameters
3750Vrms
109 Ohms
20 pF
-20ºC to 60ºC
-40ºC to 85ºC
4.75 oz. (135g)
PVC Class V0 (UL94)
Polyamide Class V0 (UL94)
GENERAL NOTES
1) Relay will self trigger between 900-1200V. Not Suitable for capacitive loads.
2) All parameters at 25°C unless otherwise specified.
3) Mounted in the Vertical position
4) For AC control AC53 maximum current is 1.6A
5) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
6) For AC control, rating is ½HP/0.25KW
7) For AC control, rating is1HP/0.37KW
8) For AC control, rating is 1HP/0.55KW
9) Turn-on time for DC control random turn-on versions is 0.1 msec.
MECHANICAL SPECIFICATIONS
DRA3P48Cx
DRA3P48Bx
DRA3P48Ax
4-6 VDC
18-28 VDC
36-60 VAC
90-140 VAC
200-265 VAC
4 VDC
18 VDC
36 VAC
90 VAC
200 VAC
2 VDC
4 VDC
10 VAC
20 VAC
100 VAC
17
15
7.5
5
4.5
35
25
13.5
8
5.7
120
1.2K
4.2K
16K
46K
1/2 Cycle
1/2 Cycle
20 ms
20 ms
20 ms
1/2 Cycle
1/2 Cycle
30 ms
30 ms
30 ms
24/12
24/12
24/12
24/12
24/12
0.5-2.5
0.5-2.5
0.5-2.5
0.5-2.5
0.5-2.5
4.3 in lb (0.485 Nm) 4.3 in lb (0.485 Nm) 4.3 in lb (0.485 Nm) 4.3 in lb (0.485 Nm) 4.3 in lb (0.485 Nm)
WIRING DIAGRAM
THERMAL DERATE INFORMATION
AGENCY APPROVALS
Rev 090512
Similar pages