Mean Well HRP-100-15 100w single output with pfc function Datasheet

HRP-100
100W Single Output with PFC Function
series
Features :
Universal AC input / Full range
Built-in active PFC function
High efficiency up to 90%
Withstand 300VAC surge input for 5 seconds
Protections: Short circuit / Overload / Over voltage
Protections: Over temperature (optional)
Cooling by free air convection
1U low profile 38mm
Built-in remote ON-OFF control
No load power consumption<0.5W
All using 105
long life electrolytic capacitors
5 years warranty
SPECIFICATION
MODEL
OUTPUT
HRP-100-3.3
HRP-100-5
HRP-100-7.5
HRP-100-12
HRP-100-15
HRP-100-24
HRP-100-36
HRP-100-48
DC VOLTAGE
3.3V
5V
7.5V
12V
15V
24V
36V
48V
RATED CURRENT
20A
17A
13.5A
8.5A
7A
4.5A
2.9A
2.2A
CURRENT RANGE
0 ~ 20A
0 ~ 17A
0 ~ 13.5A
0 ~ 8.5A
0 ~ 7A
0 ~ 4.5A
0 ~ 2.9A
0 ~ 2.2A
RATED POWER
66W
85W
101.3W
102W
105W
108W
104.4W
105.6W
RIPPLE & NOISE (max.) Note.2 80mVp-p
80mVp-p
100mVp-p
120mVp-p
150mVp-p
150mVp-p
200mVp-p
240mVp-p
VOLTAGE ADJ. RANGE
3.1 ~ 3.8V
VOLTAGE TOLERANCE Note.3 +2.5,-3.5%
4.75 ~ 5.8V
2.5%
7.1 ~ 9V
2.5%
11.4 ~ 13.8V
1.5%
14.25 ~ 18V
1.5%
22.8 ~ 28.8V
1.5%
34.2 ~ 39.6V
1.5%
45.6 ~ 55.2V
1.5%
LINE REGULATION
0.5%
0.5%
0.5%
0.3%
0.3%
0.2%
0.2%
0.2%
LOAD REGULATION
2.0%
2.0%
1.5%
0.8%
0.8%
0.5%
0.5%
0.5%
SETUP, RISE TIME
2500ms, 100ms/230VAC
HOLD UP TIME (Typ.)
50ms/230VAC
20ms/115VAC at full load
VOLTAGE RANGE
Note.5 85 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
INPUT
PF>0.95/230VAC
EFFICIENCY (Typ.)
78%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
1.2A/115VAC
35A/115VAC
LEAKAGE CURRENT
<1mA / 240VAC
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
FUNCTION
120 ~ 370VDC
POWER FACTOR (Typ.)
OVERLOAD
2500ms, 100ms/115VAC at full load
PF>0.98/115VAC at full load
83%
84%
87.5%
88%
88.5%
89%
90%
0.6A/230VAC
65A/230VAC
105 ~ 135% rated output power
Protection type : Constant current limiting for Vo=50 ~ 100% of rated voltage, recovers automatically after fault condition is removed
6 ~ 7V
9.4 ~ 10.9V
14.4 ~ 16.8V 18.8 ~ 21.8V 30 ~ 34.8V
41.4 ~ 48.6V 57.6 ~ 67.2V
3.96 ~ 4.62V
Protection type : Shut down o/p voltage, re-power on to recover
90 (3.3V ~ 7.5V) , 85 (12V ~ 48V) (TSW1 : detect on heatsink Q101 of power transistor)(optional)
REMOTE CONTROL
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
RC+/RC- : 0 ~ 0.8V= power on ; 4 ~ 10V = power off
WORKING TEMP.
-40 ~ +60
(Refer to "Derating Curve")
20 ~ 90% RH non-condensing
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
0.04%/ (0 ~ 50
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
OTHERS
NOTE
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2, heavy industry level, criteria A
MTBF
295.7K hrs min.
DIMENSION
159*97*38mm (L*W*H)
PACKING
0.38Kg; 24pcs/ 10.1Kg/0.76CUFT
MIL-HDBK-217F (25
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
File Name:HRP-100-SPEC 2011-08-09
HRP-100
100W Single Output with PFC Function
I I
Mechanical Specification
Case No.901I
series
Unit:mm
3.5
7
152.5
1
3
8.2
5
2-M
6
3L
84.5
4
=4
97
65
9.5
2
1 2
7
CN100
SVR1
3.5
4.5
Terminal Pin No. Assignment
78
24
Pin No.
Assignment
4,5
DC OUTPUT -V
6,7
DC OUTPUT +V
159
6.5
150
JST XHP
or equivalent
JST SXH-001T
or equivalent
6-M3(Both Sides) L=6
22
38
Terminal
28.5
Mating Housing
18
3.5
Assignment
RCRC+
3.5
10 max.
Remote ON/OFF (CN100) : JST B-XH or equivalent
Pin No.
1
2
18.5
9
Assignment
AC/L
AC/N
FG
9
Pin No.
1
2
3
117
Block Diagram
ACTIVE
INRUSH
CURRENT
LIMITING
EMI
FILTER
I/P
RECTIFIERS
&
PFC
POWER
SWITCHING
O.T.P.
O.L.P.
RECTIFIERS
&
FILTER
DETECTION
CIRCUIT
FG
PFC
CONTROL
O.V.P.
PWM
CONTROL
Derating Curve
+V
-V
RC+
REMOTE
CONTROL
RC-
Output Derating VS Input Voltage
100
100
90
80
80
70
LOAD(%)
LOAD (%)
60
40
20
-40
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70
(HORIZONTAL)
60
50
40
85
100
125
135
155
264
INPUT VOLTAGE (V) 60Hz
File Name:HRP-100-SPEC 2011-08-09