NI NICFP-BP-4 Analog output modules for compact fieldpoint Datasheet

Analog Output Modules for Compact FieldPoint
NI cFP-AO-200, NI cFP-AO-210
• 8 voltage or current outputs
• 0 to 10 V
• 0 to 20, 4 to 20 mA
• 12-bit resolution
• Output ranges software-configurable
per channel
• 2,300 Vrms bank isolation for transient
overvoltage protection
• Hot-swappable with autoconfiguration
• -40 to 70 °C operating range
Module
cFP-AO-200
cFP-AO-210
Input Channels
8
8
Resolution
12 bits
12 bits
Output Types
Current
Voltage
Output Ranges
(Software Configurable per Channel)
0 to 20 mA, 4 to 20 mA
0 to 10 V (up to 10 mA/ch)
All Channel Update Rate1
200 Hz
200 Hz
1The
all-channel update rate refers to the time the module takes to sample all channels. The overall system update rate is affected by other factors, such as the aggregate module update rate and
software loop rate. To calculate the system update rate, visit ni.com/info and enter “systemrate.”
Overview
National Instruments cFP-AO-2xx devices are versatile analog output
modules for Compact FieldPoint that you can use to control valves,
gauges, and other industrial actuators. All modules include overranging
and onboard diagnostics to ensure trouble-free installation and
maintenance. The NI cFP-AO-2xx modules come with NIST-traceable
calibration certificates, ensuring accurate and reliable analog control.
Smart I/O Modules
With cFP-AO-2xx modules, you can directly connect to your industrial
actuators or units under test and get high-accuracy control. The
I/O modules calibrate and scale engineering units to sensor signals,
as well as perform self-diagnostics to detect problems with the module
or with the wiring such as open current loops. With cFP-AO-2xx modules,
your software application writes an engineering value to the I/O module,
eliminating the error-prone step of converting voltage or current to
binary values. The cFP-AO-2xx modules have an update rate of 200 Hz.
Overall data throughput to the controller or PC depends on the software
loop speeds and the network speeds.
The cFP-AO-200 includes eight 0 to 20 mA or 4 to 20 mA analog
output channels, generated with a 12-bit DAC. Each output channel
features a monitoring circuit and LED indicator for open current loop
detection. The cFP-AO-200 requires an external power supply that
provides 5 to 24 VDC.
The cFP-AO-210 includes eight 0 to 10 V output channels, generated
with a 12-bit DAC. Each channel provides a voltage source capable
of supplying up to 1 mA. You can obtain up to 10 mA by powering the
cFP-AO-210 with an optional external power supply of 15 to 30 VDC.
Isolation
The cFP-AO-2xx modules feature optical bank isolation with 2,300 Vrms
of breakdown isolation. They do not have channel-to-channel isolation.
Field I/O Connections
Compact FieldPoint modules include a built-in power distribution bus that
provides multiple power connections on the module. A field-wired power
supply connected to the voltage (V) and common (C) terminals is internally
connected to a power distribution bus that offers additional breakout
terminals for voltage supply (VSUP) and common (COM). These terminals
deliver a convenient way to distribute power to field devices that require
external power.
The cFP-AO-200 has:
• 8 current output terminals (IOUT)
• 16 common terminals (COM)
• 8 power connections for field devices or current loops (VSUP)
The cFP-AO-210 has:
• 8 voltage output terminals (VOUT)
• 16 common terminals (COM)
• 8 power connections for field devices or current loops (VSUP)
Analog Output Modules for Compact FieldPoint
+
External
15 to 30 VDC
Supply
+
–
V
C
C
–
Loop
Supply
VSUP
V
VSUP
+
–
Current
Limit
VOUT
COM
IOUT
3-wire
device
requiring
COM power
V+
Vin
Load
COM
VSUP
VSUP
+
–
Current
Limit
VOUT
COM
Load
requiring up to
10 mA current
IOUT
cFP-AO-210
3-wire
device
requiring
power
COM
Figure 1. Wiring Schematic for the cFP-AO-210 Module
cFP-AO-200
Figure 2. Wiring Schematic for the cFP-AO-200 Module
Ordering Information
NI cFP-AO-200 ....................................................................777318-200
NI cFP-AO-210 ....................................................................777318-210
Recommended Compact FieldPoint System Products
NI cFP-2120 ......................................................................777317-2120
NI cFP-BP-4 ............................................................................778617-04
NI cFP-CB-1............................................................................778618-01
NI PS-5 power supply............................................................778805-90
NI Developer Suite Professional Control Edition ....................777906-03
BUY NOW!
For complete product specifications, pricing, and accessory
information, call 800 813 3693 (U.S.) or go to ni.com/compactfieldpoint.
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)
2
Analog Output Modules for Compact FieldPoint
Physical Characteristics
Specifications
Typical for -40 to 70 °C unless otherwise noted.
Output Characteristics
Number of channels............................ 8 single-ended
DAC resolution.................................... 12 bits, 1 in 4,096
Current Output (cFP-AO-200)
Output range ....................................... 0 to 20 or 4 to 20 mA,
programmable (0 to 21 or 3.5 to
21 mA with overranging)
Output type ......................................... Current source
(external loop power required)
External loop power............................ 5 to 24 VDC
Internal voltage drop........................... 3 V
Resistive load .......................................... Up to 1 kΩ with 24 VDC supply,
up to 100 Ω with 5 V supply
Protection and error detection............ Short-circuit and open-circuit
Default power-up state....................... 0 mA
Resolution ........................................... 6 µA
LED indicators
POWER (green) ............................... Power on and self-test passed
READY (green) ................................ Module configured and ready
Fault status (red)............................. Open circuit (cFP-AO-200) or current
limit (cFP-AO-210) on channel
Dimensions.......................................... 127.0 by 65.9 by 23.9 cm
(5.00 by 2060 by 0.94 in.)
Weight
cFP-AO-200 ..................................... 113 g (4.0 oz)
cFP-AO-210 ..................................... 115 g (4.1 oz)
Power Requirement
Power from network module
cFP-AO-200 ..................................... 350 mW
Environment
Operating temperature ....................... -40 to 70 °C
Storage temperature........................... -55 to 85 °C
Relative humidity ................................ 10 to 90%, noncondensing
Voltage Output (cFP-AO-210)
Shock and Vibration
Output range ....................................... 0 to 10 V (0 to 10.2 V with
overranging)
Output type ......................................... Voltage source
(external power optional)
External power supply ........................ 15 to 30 VDC
Internal voltage drop........................... 3 V
Current drive ....................................... 1 mA sourcing or sinking,
10 mA sourcing with external
power supply
Overvoltage protection ....................... -10 to 20 V
Default power-up state....................... 0 V
Resolution ........................................... 2.5 mA
Operating vibration, random
(IEC 60068-2-64) ............................. 10 to 500 Hz, 5 grms
Operating vibration, sinusoidal
(IEC 60068-2-6) ............................... 10 to 500 Hz, 5 g
Operating shock
(IEC 60068-2-27) ............................. 50 g, 3 ms half sine,
18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations
Isolation Voltage
Maximum isolation voltage ................ 250 Vrms, Installation Category II
Channel-to-channel isolation.............. No isolation between channels
Transient overvoltage.......................... 2,300 Vrms
Accuracy
Absolute accuracy (cFP-AO-200).........
Gain error (cFP-AO-210) ......................
Offset error (cFP-AO-210)....................
Monotonicity .......................................
Offset temperature coefficient
cFP-AO-200 .....................................
cFP-AO-210 .....................................
Gain temperature coefficient
cFP-AO-200 .....................................
cFP-AO-210 .....................................
0.1% typ, 0.3% max
0.2% typ, 0.4% max
4 mV typ, 14 mV max
Guaranteed over temperature range
50 nA/°C
70 µV/°C
40 ppm/°C
20 ppm/°C
Dynamic Characteristics
Maximum update rate ........................ 200 updates/s
Slew rate
cFP-AO-200 ..................................... 0.4 mA/µs
cFP-AO-210 ..................................... 0.5 V/µs
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)
3
Analog Output Modules for Compact FieldPoint
Safety and Compliance
Safety
This product is designed to meet the requirements of the following
standards of safety for electrical equipment for measurement, control,
and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 61010-1, CSA 61010-1
Note: For UL and other safety certifications, refer to the product label or
visit ni.com/certification, search by model number or product line, and
click the appropriate link in the Certification column.
Electromagnetic Compatibility
This product is designed to meet the requirements of the following
standards of EMC for electrical equipment for measurement, control,
and laboratory use:
• EN 61326 EMC requirements; Minimum Immunity
• EN 55011 Emissions; Group 1, Class A
• CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A
Note: For EMC compliance, operate this device according to
product documentation.
CE Compliance
This product meets the essential requirements of applicable European
Directives, as amended for CE marking, as follows:
• 2006/95/EC; Low-Voltage Directive (safety)
• 2004/108/EC; Electromagnetic Compatibility Directive (EMC)
Note: Refer to the Declaration of Conformity (DoC) for this product for
any additional regulatory compliance information. To obtain the DoC for
this product, visit ni.com/certification, search by model number or
product line, and click the appropriate link in the Certification column.
Waste Electrical and Electronic Equipment (WEEE)
EU Customers: At the end of their life cycle, all products must be
sent to a WEEE recycling center. For more information about WEEE
recycling centers and National Instruments WEEE initiatives,
visit ni.com/environment/weee.htm.
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)
4
IN
TA
PL
AN
MA
IN
NI Services and Support
P
DE
LO
Y
EL
OP
SERVICE
NEEDS
V
DE
NI has the services and support to meet
your needs around the globe and through
the application life cycle – from planning
and development through deployment
and ongoing maintenance. We offer
services and service levels to meet
customer requirements in research,
design, validation, and manufacturing.
Visit ni.com/services.
Training and Certification
NI training is the fastest, most certain route to productivity with our
products. NI training can shorten your learning curve, save development
time, and reduce maintenance costs over the application life cycle. We
schedule instructor-led courses in cities worldwide, or we can hold a
course at your facility. We also offer a professional certification program
that identifies individuals who have high levels of skill and knowledge on
using NI products. Visit ni.com/training.
Professional Services
Our NI Professional Services team is composed of NI applications
and systems engineers and a worldwide National Instruments Alliance
Partner program of more than 600 independent consultants and
integrators. Services range
from start-up assistance to
turnkey system integration.
Visit ni.com/alliance.
OEM Support
We offer design-in consulting and product integration assistance if you
want to use our products for OEM applications. For information about
special pricing and services for OEM customers, visit ni.com/oem.
ni.com • 800 813 3693
National Instruments • [email protected]
Local Sales and Technical Support
In offices worldwide, our staff is local to the country, giving you access
to engineers who speak your language. NI delivers industry-leading
technical support through online knowledge bases, our applications
engineers, and access to 14,000 measurement and automation
professionals within NI Developer Exchange forums. Find immediate
answers to your questions at ni.com/support.
We also offer service programs that provide automatic upgrades to
your application development environment and higher levels of technical
support. Visit ni.com/ssp.
Hardware Services
NI Factory Installation Services
NI Factory Installation Services (FIS) is the fastest and easiest way to
use your PXI or PXI/SCXI combination systems right out of the box.
Trained NI technicians install the software and hardware and configure
the system to your specifications. NI extends the standard warranty by
one year on hardware components (controllers, chassis, modules)
purchased with FIS. To use FIS, simply configure your system online
with ni.com/pxiadvisor.
Calibration Services
NI recognizes the need to maintain properly calibrated devices for
high-accuracy measurements. We provide manual calibration
procedures, services to recalibrate your products, and automated
calibration software specifically designed for use by metrology
laboratories. Visit ni.com/calibration.
Repair and Extended Warranty
NI provides complete repair services for our products. Express repair
and advance replacement services are also available. We offer
extended warranties to help you meet project life-cycle requirements.
Visit ni.com/services.
*351577A-01*
351577A-01
2007-9290-161-101-D
©2008 National Instruments Corporation. All rights reserved. FieldPoint, National Instruments, National Instruments Alliance Partner, NI, ni.com, NI Developer Suite, and SCXI are
trademarks of National Instruments. Other product and company names listed are trademarks or trade names of their respective companies. A National Instruments Alliance Partner is a
business entity independent from NI and has no agency, partnership, or joint-venture relationship with NI.