15W Single Output Industrial DIN Rail Power Supply DR-15 series Features : Universal AC input/Full range Protections: Short circuit / Overload / Over voltage Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 Isolation class LED indicator for power on No load power consumption<0.5W 100% full load burn-in test 3 years warranty SPECIFICATION MODEL DR-15-5 DR-15-12 DR-15-15 DR-15-24 DC VOLTAGE 5V 12V 15V 24V RATED CURRENT 2.4A 1.25A 1A 0.63A CURRENT RANGE 0 ~ 2.4A 0 ~ 1.25A 0 ~ 1A 0 ~ 0.63A RATED POWER 12W RIPPLE & NOISE (max.) Note.2 80mVp-p OUTPUT INPUT 4.75 ~ 5.5V VOLTAGE ADJ. RANGE 21.6 ~ 26.4V 1.0% LINE REGULATION 1.0% 1.0% 1.0% 1.0% LOAD REGULATION 1.0% 1.0% 1.0% 1.0% SETUP, RISE TIME 1000ms, 50ms/230VAC HOLD UP TIME (Typ.) 70ms/230VAC VOLTAGE RANGE 85 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz 1000ms, 50ms/115VAC at full load 16ms/115VAC at full load 120 ~ 370VDC EFFICIENCY (Typ.) 77% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) 0.88A/115VAC 0.48A/230VAC COLD START 35A/115VAC 65A/230VAC TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE Note.5 84% 83.5% 85% 105 ~ 160% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 5.75 ~ 6.75V 13.8 ~ 16.2V 17.25 ~ 20.25V 27.6 ~ 32.4V Protection type : Shut off o/p voltage, clamping by zener diode -20 ~ +60 (Refer to output load derating curve) 20 ~ 90% RH non-condensing -40 ~ +85 , 10 ~ 95% RH 0.03%/ (0 ~ 50 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL60950-1, TUV EN60950-1 approved, design refer to EN50178 I/P-O/P:3KVAC ISOLATION RESISTANCE I/P-O/P:100M Ohms / 500VDC / 25 / 70% RH EMI CONDUCTION & RADIATION Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B Compliance to EN61000-3-2,-3 HARMONIC CURRENT EMS IMMUNITY Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A MTBF 1172.3K hrs min. MIL-HDBK-217F (25 25*93*56mm (W*H*D) 0.1Kg; 140pcs/15Kg/0.92CUFT DIMENSION PACKING NOTE 13.5 ~ 16.5V 1.0% WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY OTHERS 10.8 ~ 13.2V 1.0% OVER VOLTAGE (Note 4) 15.2W 150mVp-p 2.0% PROTECTION EMC 15W 120mVp-p VOLTAGE TOLERANCE Note.3 OVERLOAD SAFETY & 15W 120mVp-p ) 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Constant current operation region is within 60% ~100% rated output voltage. Protection type for short circuit is hiccup mode and will recover automatically after fault condition is removed. File Name:DR-15-SPEC 2009-03-09 DR-15 15W Single Output Industrial DIN Rail Power Supply Mechanical Specification Case No.985A series Unit:mm 67.2 44.2 56 47 26.7 4 46.5 46.5 93 N 5 Vadj. 5 25 35 LED -V L +V ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 Block Diagram RECTIFIERS & FILTER EMI FILTER I/P RECTIFIERS & FILTER POWER SWITCHING +V -V DETECTION CIRCUIT O.L.P. CONTROL O.V.P. Derating Curve Output Derating VS Input Voltage Ta=25 100 100 90 80 80 70 LOAD (%) LOAD (%) 60 40 20 -20 0 10 20 30 40 50 AMBIENT TEMPERATURE ( ) 60 70 (VERTICAL) 60 50 40 85 95 100 115 120 140 160 180 200 220 240 264 INPUT VOLTAGE (VAC) 60Hz File Name:DR-15-SPEC 2009-03-09