Mean Well DRT-480-48 480w three phase industrial din rail power supply Datasheet

480W Three Phase Industrial DIN RAIL Power Supply
D R T- 4 8 0
series
Features :
Three-Phase AC 340 ~ 550V wide range input
High efficiency 89% and low dissipation
Protections:Short circuit/Over load/Over voltage/Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
R
SPECIFICATION
MODEL
OUTPUT
INPUT
DRT-480-24
DRT-480-48
DC VOLTAGE
24V
48V
RATED CURRENT
20A
10A
CURRENT RANGE
0 ~ 20A
0 ~ 10A
RATED POWER
480W
480W
RIPPLE & NOISE (max.) Note.2 80mVp-p
80mVp-p
VOLTAGE ADJ. RANGE
48 ~ 55V
1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
LOAD REGULATION
0.5%
0.5%
0.5%
SETUP, RISE TIME
1200ms, 40ms/400VAC
HOLD TIME (Typ.)
16ms/400VAC
VOLTAGE RANGE
Three-Phase 340 ~ 550VAC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
89%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
1.7A/400VAC
1.3A/500VAC
COLD START 50A
LEAKAGE CURRENT
OVER LOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
800ms, 40ms/500VAC at full load
35ms/500VAC at full load
480 ~ 780VDC
90%
<3.5mA / 530VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
30 ~ 36V
59 ~ 66V
Protection type : Shut down o/p voltage, re-power on to recover
110
5 (TSW) Detect on heatsink of power switch
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-20 ~ +70
(Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85
0.03%/
, 10 ~ 95% RH
(0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 Approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
SAFETY & ISOLATION RESISTANCE
EMI
CONDUCTION
&
RADIATION
Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B
EMC
(Note 4)
OTHERS
HARMONIC CURRENT
Compliance to EN61000-3-2,-3
EMS IMMUNITY
MTBF
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61204-3, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A
DIMENSION
PACKING
NOTE
91.1Khrs min. MIL-HDBK-217F (25
227*125.2*100mm (W*H*D)
2.5Kg; 6pcs/16Kg/1.75CUFT
)
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Dual phase operation: derating of 20% is required.
File Name:DRT-480-SPEC 2005-09-06
D R T- 4 8 0
480W Three Phase Industrial DIN RAIL Power Supply
Mechanical Specification
Case No.930A
100
series
Unit:mm
125.2
227
TB1
4 3 2 1
TB2
4 3 2 1
LED
+V ADJ.
35
Admissible Din Rail: TS35/7.5 or TS35/15
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
4
TB2 Terminal Pin. No Assignment
Pin No.
1,2
3,4
Assignment
AC/L1
AC/L2
AC/L3
FG
Static Characteristics
Derating Curve
100
80
90
85
80
60
70
LOAD (%)
LOAD (%)
100
40
20
-20
Assignment
DC OUTPUT +V
DC OUTPUT -V
Three phase operation
Dual phase operation
60
50
40
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70 (VERTICAL)
340
355
370
385
400
415 430
460 475
490
505 520 550
INPUT VOLTAGE (VAC) 60Hz
File Name:DRT-480-SPEC 2005-09-06