Cynergy3 MS20B Direct power switching Datasheet

MS Series
The MS series of cable end float switches are designed for controlling levels in large tanks,
cisterns or reservoirs and can be directly installed on submersible pumps. The casing is
manufactured in blow moulded Polyethylene (HDPE), with 5m PVC cable with protective
earth conductor as standard. The switching element is a microswitch, with UL, VDE and
CENELEC approvals, activated by a moving stainless steel ball and having an electrical life
of 200,000 operations. Non-hygroscopic closed-cell expanded polyurethane is injected
around the switch housing within the outer casing, hermetically sealing the unit. It is
capable of working down to 100 metres depth in water.
The “U” version with polyurethane cable is for use in fuel oils.
Contact
Part No.
Form
Switching Current Max.
(Amps)
Resistive
AC
Power Rating
Switching
Cable
Temp. Range
Max.
Max.
Voltage Max. Cable Length Body
Matl.
Matl.
Pressure
o
o
*
C
F
Inductive AC (VA) DC (W) AC
DC
MS10A
N/O
10
4
1
750
180
250
110
PVC
5m
HDPE 0-55 32-131 10 bar
MS10AU
N/O
10
4
1
750
180
250
110
PUR
5m
HDPE 0-55 32-131 10 bar
MS10B
N/C
10
4
1
750
180
250
110
PVC
5m
HDPE 0-55 32-131 10 bar
MS10BU
N/C
10
4
1
750
180
250
110
PUR
5m
HDPE 0-55 32-131 10 bar
MS10C
C/O
10
4
1
750
180
250
110
PVC
5m
HDPE 0-55 32-131 10 bar
MS10CU
C/O
10
4
1
750
180
250
110
PUR
5m
HDPE 0-55 32-131 10 bar
MS20A
N/O
20
8
2
1500
360
250
110
PVC
5m
HDPE 0-55 32-131 10 bar
MS20AU
N/O
20
8
2
1500
360
250
110
PUR
5m
HDPE 0-55 32-131 10 bar
MS20B
N/C
20
8
2
1500
360
250
110
PVC
5m
HDPE 0-55 32-131 10 bar
MS20BU
N/C
20
8
2
1500
360
250
110
PUR
5m
HDPE 0-55 32-131 10 bar
MS20C
C/O
20
2
1500
360
250
110
PVC
5m
HDPE 0-55 32-131 10 bar
MS20CU
C/O
20
8
8
2
1500
360
250
110
PUR
5m
HDPE 0-55 32-131 10 bar
* = protective earth wire included
• Direct power
switching
• Cable mounting
• 100 metre depth
capability
Cynergy3 Components Ltd
7 Cobham Road
Ferndown Industrial Estate
Wimborne
Dorset BH21 7PE
Tel: +44 (0) 1202 897969
[email protected]
ISO 9001C E R T I F IED
www.cynergy3.com
MS 2015
© 2015 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
MS Series
Part Numbering System
MS
10 A U 10
Cable length in metres:
Series
Max. current
Blank = 5M standard
Cable covering:
Contact Form
Blank = PVC
U = Polyurethane
W = WRC approved (see
MS WRAS.pdf)
A = n/o
B = n/c
C = c/o
Installation
cable
cable entrance
differential
external counterweight
tie
pipe
wiring diagram for filling pump
wiring diagram for emptying pump
brown
brown
brown
blue
brown
black
blue
pump - off
level drop
pump - on
ISO 9001C E R T I F IED
black
pump - on
level drop
pump - off
www.cynergy3.com
© 2011 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.