MTU DS180D6S Diesel generator set Datasheet

DIESEL GENERATOR SET
DS180D6S
180 kWe /60 Hz /Standby
208 - 600V
(Reference DP180D6S for Prime Rating Technical Data)
SYSTEM RATINGS
Standby
DS180D6SGA
DS180D6SDA
DS180D6SPA
DS180D6SJA
DS180D6SRA
DS180D6SNA
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
240V**
1
1.0
60
180
180
750
240V**
1
1.0
60
180
180
750
208V**
3
0.8
60
180
225
625
240V**
3
0.8
60
180
225
541
480V**
3
0.8
60
180
225
271
600V**
3
0.8
60
180
225
217
267
432CSL6210
130 °C/40 °C
370
432PSL6228
130 °C/40 °C
4 LEAD
433
431CSL6206
130 °C/40 °C
433
431CSL6206
130 °C/40 °C
12 LEAD LOW WYE
12 LEAD HI DELTA
451
431CSL6204
130 °C/40 °C
12 LEAD HI WYE
510
431PSL6243
130 °C/40 °C
4 LEAD WYE
12 LEAD ZIG-ZAG
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
//
Emissions – EPA Tier 3 Certified
//
Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//
Seismic Certification – Optional
– IBC Certification
– OSHPD Pre-Approval
//
UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
//
Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//
Power Rating
- Accepts Rated Load in One Step Per NFPA 110
2
/ // /
DS180D6S
STANDARD FEATURES*
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
6068HFG85 Diesel Engine
- 6.8 Liter Displacement
- Electronic Unit Pump Injection
- 4-Cycle
// Engine-generator resilient mounted
// Complete Range of Accessories
//
//
//
//
Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- 300% Short Circuit Capability with Optional PMG
// Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine Driven Fan
//
STANDARD EQUIPMENT*
//
Engine
Air Cleaners
Oil Pump
Oil Drain Extension & S/O Valve
Full Flow Oil Filter
Fuel Filter with Water Separator
Jacket Water Pump
Thermostat
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 12V
Governor – Electronic Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 12V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
//
Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Solid State, Volts-per-Hertz Regulator
±1% Voltage Regulation No Load to Full Load
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130 °C Maximum Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
100% of Rated Load - One Step
5% Maximum Total Harmonic Distortion
//
Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows®-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
16 Programmable Contact Inputs
Up to 11 Contact Outputs
UL Recognized, CSA Certified, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
3
/ // /
DS180D6S
APPLICATION DATA
//
Engine
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Maximum Power: kWm (bhp)
Speed Regulation
Air Cleaner
//
32.2 (8.5)
11.9 (3.3)
29.3 (7.75)
Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
//
John Deere
6068HFG85
4-Cycle
6-Inline
6.8 (415)
10.6 (4.2)
12.7 (5)
17:1
1,800
JDEC
235 (315)
±0.25%
Dry
Liquid Capacity (Lubrication)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
//
//
12
925
Fuel Consumption
At 100% of Power Rating: L/hr (gal/hr)
At 75% of Power Rating: L/hr (gal/hr)
At 50% of Power Rating: L/hr (gal/hr)
//
Cooling - Radiator System
Ambient Capacity of Radiator: °C (°F)
Maximum Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM )
Heat Rejection to Air to Air: kW (BTUM )
Heat Radiated to Ambient: kW (BTUM )
Fan Power: kW (hp)
//
STANDBY
51.9 (13.5)
40.5 (10.7)
27.6 (7.3)
STANDBY
50 (122)
0.12 (0.5)
265 (70)
83.7 (4,766)
40 (2,298)
24.2 (1,378)
8.6 (11.5)
Air Requirements
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat for a
Max of 25 °F Rise: *m3/min (SCFM)
STANDBY
14.7 (520)
412 (14,537)
89 (3,108)
Fuel System
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: m (ft)
Recommended Fuel
Total Fuel Flow: L/hr (gal/hr)
3/8” NPT
3/8” NPT
2 (6.7)
Diesel #2
93 (24.5)
//
Exhaust System
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
Maximum Allowable
Back Pressure: kPa (in. H20)
STANDBY
528 (982)
38.8 (1,371)
10 (40)
4
/ // /
DS180D6S
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
System
OPU
Dimensions (L x W x H)
2,845 x 1,219 x 1,346 mm (112 x 48 x 53 in)
Weight (less tank)
1,720 kg (3,755 lb)
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Standby Full Load
87.2
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
NOx + NMHC
2.8
CO
0.4
RATING DEFINITIONS AND CONDITIONS
PM
0.04
All units are in g/hp-hr and are EPA D2 cycle values.
Emission levels of the engine may vary as a function of ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation,
etc. The data provided are laboratory results from one
engine representing this rating. The data was obtained
under controlled environmental conditions with calibrated
instrumentation traceable to the United States National Bureau
of Standards and in compliance with US EPA regulations found
within 40 CFR Part 89. The weighted cycle value from each
engine is guaranteed to be below the US EPA Standards at the
US EPA defined conditions.
Materials and specifications subject to change without notice.
C/F = Consult Factory/MTU Onsite Energy Distributor
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload
capability for this rating. Ratings are in accordance with
ISO 3046-1, BS 5514, AS 2789, and DIN 6271.
// Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
//
© MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 465 (77 3E) 2014-01
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
Similar pages