Omron E53-CK03 Advanced, compact digital controller Datasheet

Digital Controller
E5CK
Advanced, Compact Digital Controllers
• IP66/NEMA4 (indoor use) front face.
• Modular structure, one-stock type.
• Heating/cooling control.
• Serial communications (RS-232C and RS-485).
• Temperature and analog inputs.
• High-accuracy: 100 ms sampling (for analog input).
• Advanced tuning which includes fuzzy self-tuning.
• Conforms to international EMC and safety standards.
• AC/DC24V types are also available.
®
Model Number Structure
■ Model Number Legend
Refer to the following when ordering set models.
E5CK-@@@
1 2 3
2. Auxiliary Output
1:
Auxiliary output (1 point)
3. Option
01: RS-232C serial communication
03: RS-485 serial communication
B:
Event input (1 point)
F:
Transfer output (4 to 20 mA)
1. Control Output 1/Control Output 2
AA: Without Output Unit (field interchangeable)
RR: Relay/Relay
QR: Pulse (NPN)/Relay
CR: Linear (4 to 20 mA)/Relay
VR: Linear (0 to 10 V)/Relay
QQ: Pulse (NPN)/Pulse (NPN)
Temperature
Controller
Note: E5CK-VR1 and E5CK-QQ1 are not available, but with options.
Ordering Information
■ List of Models
Description
Model
E5CK-AA1 AC100-240
Base Unit
Specification
Base Unit
E5CK-AA1-500 AC100-240
Base Unit with terminal cover
E5CK-AA1 AC/DC24
Base Unit
E5CK-AA1-500 AC/DC24
Base Unit with terminal cover
Note: A single Output Unit and Option Unit can be mounted to each Base Unit.
Description
Output Unit
Model
E53-R4R4
Specification
Relay/Relay
E53-Q4R4
Pulse (NPN)/Relay
E53-Q4HR4
Pulse (PNP)/Relay
E53-C4R4
Linear (4 to 20 mA)/Relay
E53-C4DR4
Linear (0 to 20 mA)/Relay
E53-V44R4
Linear (0 to 10 V)/Relay
E53-Q4Q4
Pulse (NPN)/Pulse (NPN)
E53-Q4HQ4H
Pulse (PNP)/Pulse (PNP)
Digital Controller
E5CK
I-63
Description
Model
Specification
E53-CK01
Option Unit
RS-232C
E53-CK03
RS-485
E53-CKB
Event input: 1 point
E53-CKF
Transfer output (4 to 20 mA)
Inspection Report
The Digital Controller can be provided together with an inspection report.
Refer to the following legend with the suffix “K” when ordering a model provided together with an inspection report.
E5CK-AA1-K, E53-CKF-K
■ Accessories (Order Separately)
Name
Model
E53-COV07
Terminal Cover
Specifications
■ Ratings
Item
AC100-240V type
AC/DC24V type
Supply voltage
AC100 to 240V, 50/60 Hz
AC/DC24V, 50/60 Hz
Power consumption
15 VA
6 VA, 3.5 W
Operating voltage range
85% to 110% of rated supply voltage
Input
Thermocouple:
Platinum resistance thermometer:
Current input:
Voltage input:
Input impedance
Current input: 150 Ω
Voltage input: 1 MΩ min.
Control output
According to Output Unit (see “Output Unit Ratings and Characteristics”)
Auxiliary output
SPST-NO, 1 A at 250 VAC (resistive load)
Control method
ON/OFF or 2-PID control (with auto-tuning)
Setting method
Digital setting using front panel keys
Indication method
7-segment digital display and LEDs
Other functions
According to Option Unit (see “Option Unit Ratings and Characteristics”)
■ Input Ranges
Platinum Resistance Thermometer
Input (switch selectable)
Range
Pt100
−199.9 to 650.0
−199.9 to 650.0
°F
−199.9 to 999.9
−199.9 to 999.9
0
1
Resolution (°C/°F)
(main setting and alarm)
I-64
JPt100
°C
Digital Controller E5CK
K, J, T, E, L, U, N, R, S, B, W, PLII
JPt100, Pt100
4 to 20 mA, 0 to 20 mA
1 to 5 V, 0 to 5 V, 1 to 10 V
Thermocouple
Input (switch
selectable)
(see note)
K1
K2
°C
−200
to
1,300
0.0 to
500.0
−100 0.0 to
to 850 400.0
−199.9 0 to
to 400.0 600
−100 0.0 to
to 850 400.0
−199.9 −200
to 400.0 to
1,300
0 to
1,700
0 to
1,700
100 to 0 to
1,800 2,300
0 to
1,300
°F
−300
to
2,300
0.0 to
900.0
−100
to
1,500
0.0 to
750.0
−199.9 0 to
to 700.0 1,100
−100
to
1,500
0.0 to
750.0
−199.9 −300
to 700.0 to
2,300
0 to
3,000
0 to
3,000
300 to 0 to
3,200 4,100
0 to
2,300
3
4
5
6
8
9
10
12
13
14
16
Range
Resolution (°C/ 2
°F) (main setting
and alarm)
J1
J2
T
E
7
L1
L2
U
N
11
R
S
B
W
15
PLII
Note: Setting number is factory-set to 2 (K1).
Thermocouple W is W/Re 5-26 (tungsten rhenium 5, tungsten rhenium 26).
Current/Voltage
Current input
4 to 20 mA
Voltage input
0 to 20 mA
1 to 5 V
0 to 5 V
Range
One of following ranges depending on results of scaling
−1999 to 9999
−199.9 to 999.9
−19.99 to 99.99
−1.999 to 9.999
Resolution (°C/°F)
(main setting and alarm)
17
18
19
20
0 to 10 V
21
Temperature
Controller
Input (switch selectable)
Digital Controller
E5CK
I-65
■ Characteristics
Indication accuracy (see note)
Thermocouple:
(±0.3% of indication value or ±1°C, whichever greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2% of indication value or ±0.8°C, whichever greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
Hysteresis
0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
0.1% to 999.9% FS (in units of 0.1% FS)
Integral (reset) time (I)
0 to 3,999 s (in units of 1 s)
Derivative (rate) time (D)
0 to 3,999 s (in units of 1 s)
Control period
1 to 99 s (in units of 1 s)
Manual reset value
0.0% to 100.0% (in units of 0.1%)
Alarm setting range
−1,999 to 9,999 or −199.9 or 999.9 (decimal point position dependent on input type)
Sampling period
Temperature input:
Current/voltage input:
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Vibration resistance
Malfunction: 10 to 55 Hz, 10 m/s2 (approx. 1G) for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 20 m/s2 (approx. 2G) for 2 hrs each in X, Y, and Z directions
Shock resistance
Malfunction: 200 m/s2 min. (approx. 20G), 3 times each in 6 directions
(100 m/s2 (approx. 10G) applied to the relay)
Destruction: 300 m/s2 min. (30G), 3 times each in 6 directions
Ambient temperature
Operating:
Storage:
−10°C to 55°C (with no icing)/3-year warranty period: –10°C to 50°C
−25°C to 65°C (with no icing)
Ambient humidity
Operating:
35% to 85%
Degree of protection
Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Memory protection
Non-volatile memory (number of writings: 100,000 operations)
Weight
Approx. 170 g;
Adapter: approx. 10 g
EMC
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Approved standards
UL1092, CSA22.2 No. 142, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/ part 100 (Finger Protection), when the separately-ordered terminal cover is
mounted.
250 ms
100 ms
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:
ENV50140:
10 V/m (amplitude modulated, 80 MHz to 1 GHz)
(level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Note: The indication accuracy of the K1, T, and N thermocouples at a temperature of −100°C or less is ±2°C ±1 digit maximum. The indication
accuracy of the U, L1, and L2 thermocouples at any temperature is ±2°C ±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is greater) ±1 digit
maximum.
The indication accuracy of the PLII thermocouple at any temperature is (±0.3% or ±2°C, whichever is greater) ±1 digit maximum.
I-66
Digital Controller E5CK
■ Output Unit Ratings and Characteristics
Relay output
SPST, 250 VAC, 3 A (resistive load)
Mechanical life expectancy: 10,000,000 operations min.
Electrical life expectancy: 100,000 operations min.
Voltage output
NPN: 20 mA at 12 VDC (with short-circuit protection)
PNP: 20 mA at 12 VDC (with short-circuit protection)
Linear voltage output
0 to 10 VDC:
Permissible load impedance: 1 kΩ min.
Resolution: approx. 2,600
Linear current output
4 to 20 mA:
Permissible load impedance: 500 Ω max.
Resolution: approx. 2,600
■ Option Unit Ratings and Characteristics
Event inputs
Contact input:
ON: 1 kΩ max., OFF: 100 kΩ min.
No-contact input:
ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
Communications
Interface:
Transmission method:
Synchronization method:
Baud rate:
Transmission code:
Transfer output
4 to 20 mA:
Permissible load impedance: 500 Ω max.
Resolution: approx. 2,600
Temperature
Controller
RS-232C or RS-485
Half-duplex
Start-stop synchronization (asynchronous method)
1.2/2.4/4.8/9.6/19.2 kbps
ASCII
Digital Controller
E5CK
I-67
Nomenclature
Operation Indicators
• OUT1
Lights when the pulse output
function assigned to control
output 1 turns ON.
• OUT2
Lights when the pulse output
function assigned to control
output 2 turns ON.
• SUB1
Lights when the output function assigned to auxiliary
output 1 turns ON.
• MANU
Lights when the manual operation mode.
• STOP
Lights during operation has
stopped.
• RMT
Lights during remote operation.
• AT
Flashes during auto-tuning.
No. 1 Display
Displays the process value or parameter symbols.
No. 2 Display
Displays the set point, set point during SP ramp, manipulated variable,
or parameter settings.
Up Key/Down Key
Press to increase or decrease the
value on the No.2 display.
A/M Key
Press to select the auto operation or
manual operation.
Display Key
Press for less than 1 s to shift the
display to the next parameter. When
this key is pressed for 1 s or more,
the menu screen will be displayed in
any case.
Dimensions
Note: All units are in millimeters unless otherwise indicated.
E5CK
13
100
44.8 x 44.8
48
58
53 x 53
Panel Cutouts
65 min.
60 min.
45+0.6
0
45+0.6
0
I-68
Digital Controller E5CK
Note: 1. Recommended panel thickness is 1 to 5 mm.
2. Maintain the specified vertical and horizontal mounting space between each Unit. Units must not be
closely mounted vertically or horizontally.
Installation
■ Installation
Setting Up the Output Unit
1. Two rectangular holes are provided on the power board (right side
of Controller). Fit the two protrusions of the Output Unit into these
two holes.
2. With the Output Unit fitted into the power board, fit the Output Unit
into the connector on the control board (left side of Controller).
Main Parts
Terminals
Output Unit
1
Rear case
2
Input type jumper connector
Option Unit
Front panel
First, draw out the internal mechanism from the housing.
Pull out the internal mechanism while pressing the hooks on the left
and right sides of the front panel.
Setting Up the Option Unit
1. Place the Controller with its bottom facing up, and fit the board
horizontally into the Connector on the power board (right side of
controller).
2. With the power board connected, fit the board vertically into the
Connector on the control board (left side of controller).
1
2
Temperature
Controller
Draw-out
Digital Controller
E5CK
I-69
■ Mounting
1. Insert the E5CK Controller into the panel’s mounting hole at the
position shown in the figure below.
2. Push the adapter along the Controller body from the terminals up
to the panel, and fasten temporarily.
3. Tighten the two fixing screws on the adapter. When tightening
screws, tighten the two screws alternately keeping the torque to
approximately 0.29 to 0.39 N·m, or 3 to 4 kgf·cm.
Adapter
Panel
Watertight
packing
Terminal Cover
The E5CK-AA1-500 Controller is provided with a Terminal Cover
(E53-COV07). Fasten the Terminal Cover as follows by using the
snap pin.
I-70
Digital Controller E5CK
Wiring
Terminal Arrangement
Solderless terminals are recommended when wiring the Controller.
Tighten the terminal screws using a torque no greater than 0.78 N·m,
or 8 kgf·cm max. Take care not to tighten the terminal screws too
tightly.
OUT1
AC100−240V~
(AC/DC24V~)
Power Blocks
5
SOURCE
11
12
10
The E5CK has independent power supplies for each of the terminal
blocks shown below. However, note that the power supplies for
blocks C (exclude relay output) and D are shared for the following
option unit.
OUT2
SUB1
4
9
3
8
1
IN
7
2
13
14
• Option unit: E53-CKB or E53-CKF
6
A
OPTION
C
Precautions
Use ducts to separate input leads and power lines in order to protect
the Controller and its lines from external noise.
C
5 11 12 10
4
9
3
8
2
7
1 13 14 6
B
D
Wiring
Power Supply
Input 100 to 240 VAC or AC/DC 24 V to terminal numbers 4 and 5 according to the specification.
5
11
12
10
4
9
3
8
2
7
1
13
14
6
Input
Connect the input to terminal numbers 6 to 8 as follows according to the input type.
11
12
10
4
9
3
8
2
7
1
13
14
−
8
8
7
7
6
6
8
−
8
−
7
6
6
+
Thermocouple
Platinum resistance
thermometer
6
7
mA
V
+
Temperature
Controller
5
+
Voltage input
TC⋅PT
Current input
I
V
Match the inputs with the internal jumper settings for each input type. For thermocouple or platinum resistance thermometer inputs, set the inputs
to a common position (TC/PT) as the temperature input.
Control Output
Terminal numbers 11 and 12 are for control output 1 (OUT1). The five output types and internal equalizing circuits are available according to the
Output Unit.
5
11
12
10
4
9
3
8
2
1
7
13
14
6
11
+v
11
+
+v
+
12
E53-R4R4
GND
12
−
NPN
E53-Q4R4
E53-Q4Q4
L
GND
12
+
11
11
L
Relay
+
11
−
PNP
E53-Q4HR4
E53-Q4HQ4H
L
V
12
−
0 to 10 V
E53-V44R4
mA
L
12
−
4 to 20mA
E53-C4R4
E53-C4DR4
Digital Controller
E5CK
I-71
Terminal numbers 9 and 10 are for control output 2 (OUT2). The three output types and internal equalizing circuits are available according to the
Output Unit.
+
+V
10
+
+V
10
10
L
GND
9
9
−
Relay
NPN
E53-R4R4/E53-V44R4
E53-Q4R4/E53-C4R4
E53-Q4HR4/E53-C4DR4
E53-Q4Q4
L
GND
9
−
PNP
E53-Q4HQ4H
The following table shows the specifications for each output type.
Output type
Specifications
Relay
Voltage (NPN)
Voltage (PNP)
3 A at 250 VAC
20 mA at 12 VDC (with short-circuit protection)
20 mA at 12 VDC (with short-circuit protection)
0 to 10 V
4 to 20 mA
0 to 10 VDC, permissible load impedance: 1 kΩ min., resolution: approx. 2,600
4 to 20 mA, permissible load impedance: 500 Ω max., resolution: approx. 2,600
Auxiliary Output 1
Terminal numbers 2 and 3 are for auxiliary output 1 (SUB1).
The internal equalizing circuit for auxiliary output 1 is as follows:
5
11
12
10
4
9
3
8
2
7
1
13
14
3
2
6
Relay specifications are as follows:
SPST-NO, 250 VAC, 1 A
Option
Terminal numbers 1, 13, and 14 are valid only when the Option Unit is set in the Controller.
The following four connections are possible depending on the model of the Option Unit.
5
11
12
10
13
9
4
3
8
2
7
1
13
14
6
14
1
+
A
SD
13
RD
14
SG
B
1
13
13
14
14
1
1
4 to 20mA
RS-232C
RS-485
Event input
E53-CK01
E53-CK03
E53-CKB
−
Transfer output
E53-CKF
Use event inputs under the following conditions:
Contact input
ON: 1 kΩ max., OFF: 100 kΩ min.
No-contact input
ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
The polarity for no-contact input is as follows:
13
14
+
−
1
Transfer output specifications are as follows:
4 to 20 mA, load: 500 Ω max., resolution approx. 2600
I-72
Digital Controller E5CK
Operation
■ Parameter Operation List
Switching to modes other than manual or protect mode is carried out using mode selection in the menu display.
The figure below shows all parameters in the order that they are displayed. Some parameters are not displayed depending on the protect mode
setting and conditions of use.
Power ON
A/M
1 second min.
1 second min.
Level 0 mode
Manual mode
1 second min.
A/M
Level 1 mode
1 second min.
1 second min.
Level 2 mode
A/M
+
A/M
1 second min.
+
1 second min.
1 second min.
Setup mode
Protect mode
1 second min.
Expansion mode
A/M
+
1 second min.
1 second min.
Option mode
1 second min.
Calibration mode
Parameters in a mode can be
switched by the Display Key. The
parameter following the last parameter is the top parameter.
■ Parameters and Menus
Protect Mode
Limits use of the menu and A/M Keys. The protect function prevents unwanted modification of parameters and
switching between the auto and manual operation.
Manual Mode
The Controller can be switched to manual operation. The manipulated variable can be manipulated manually only
in this mode.
Level 0 Mode
Set the Controller to this mode during normal operation. In this mode, change the set point during operation, and
start or stop Controller operation. The process value, SP ramp, and manipulated variable can only be monitored
in this mode.
Level 1 Mode
The main mode for adjusting control. In this mode, execute AT (auto-tuning), and set alarm values, the control period, and PID parameters.
Level 2 Mode
The auxiliary mode for adjusting control. In this mode, set the parameters for limiting the manipulated variable and
set point, switch between the remote and local modes, and set the loop break alarm (LBA), alarm hysteresis, and
the digital filter value of inputs.
Setup Mode
The mode for setting the basic specifications. In this mode, set parameters that must be checked or set before
operation such as the input type, scaling, output assignments and direct/reverse operation.
Expansion Mode
The mode for setting expanded functions. In this mode, set ST (self-tuning), SP setting limiter, select advanced
PID or ON/OFF control, specify the standby sequence resetting method, initialize parameters, and set the time for
automatic return to the monitoring display.
Option Mode
The mode for setting option functions. Select this mode only when the Option Unit is set in the Controller. In this
mode, set the communications conditions, transfer output and event input parameters to match the type of Option
Unit set in the Controller.
Calibration Mode
The mode for calibrating inputs and transfer output.
When calibrating input, the selected input type is calibrated. Whereas, transfer output can be calibrated only when
the Communications Unit (E53-CKF) is set in the Controller.
Digital Controller
E5CK
I-73
Temperature
Controller
Note: For more details on the functions of each part and display contents, refer to the E5CK User’s Manual (H78).
■ Parameters Operation
Level 0 Mode
PV/SV
The process value is displayed on the No.1 display and the set point is displayed on the No.2 display.
When the multi-SP function is in use, the value of whichever is set, set point 0 or 1, is linked.
1300
0
Set Point During SP Ramp
Monitors the set point when the SP ramp function is used.
sp-m
0
MV Monitor (Heat)
o
50.0
MV Monitor (Cool)
Used when the Unit is in heating and cooling control operation.
c-o
50.0
Run/Stop
r-5
run
Security
Any mode marked with "X" in the following table is not displayed on the menu when this parameter is set to
"0" to "3."
secr
1
Mode
Set value
0
1
2
3
4
x
x
x
x
Option
x
x
x
Expansion
x
x
x
Setup
x
x
x
x
x
Calibration
Level 2
Level 1, 0
x
The Unit will be in only level 0 mode and the menu will not be available when this parameter is set to "4" to
"6."
Only the "PV/SP monitor" and "set point" parameter can be used when this parameter is set to "5."
Only the "PV/SP monitor" parameter can be used when this parameter is set to "6."
A/M Key Protect
Invalidate the function of the A/M Key.
keyp
off
MV Manual
3 8. 8
16.0
Process value
Manipulated variable
MANU indicator
I-74
Digital Controller E5CK
Level 1 Mode
at
AT Execute/Cancel
off
sp-0
Set Point 0
Used with multi-SP function.
0
sp-1
Set Point 1
Used with multi-SP function.
0
al-1
Alarm Value 1
Available only when the alarm output function of the Controller is selected.
0
al-2
Alarm Value 2
Available only when the alarm output function of the Controller is selected.
0
p
Proportional Band
10.0
i
Integral Time
233
d
Derivative Time
40
c-sc
Cooling Coefficient
Used when the Controller is in heating and cooling control.
1.00
0.0
of-r
50.0
hys
Dead Band
Used when the Controller is in heating and cooling control.
Temperature
Controller
c-db
Manual Reset Value
Available when the integral time parameter of the Controller in standard control is "0."
Hysteresis (Heat)
Available when the Controller is in ON/OFF control.
0.10
chys
0.10
cp
20
c-cp
20
Hysteresis (Cool)
Available when the Controller is in ON/OFF control in heating and cooling control.
Control Period (Heat)
Available when the Controller has a relay or voltage output, or is in advanced PID control.
Control Period (Cool)
Available when the Controller has a relay or voltage output, or is in advanced PID control in heating and
cooling control.
Digital Controller
E5CK
I-75
Level 2 Mode
r-l
lcl
spru
Remote/Local
Used for the communications function.
SP Ramp Time Unit
m
sprt
SP Ramp Set Value
0
lba
0
mU-s
LBA Detection Time
Available only when the LBA (loop break alarm) function of the Controller is selected.
MV at Stop
0.0
mU-e
MV at PV Error
0.0
ol-h
MV Upper Limit
105.0
MV Lower Limit
ol-l
-5.0
orl
MV Change Rate Limit
0.0
inf
Input Digital Filter
0
alh1
Alarm 1 Hysteresis
Available only when the Controller has an alarm output.
0.02
alh2
Alarm 2 Hysteresis
Available only when the Controller has an alarm output.
0.02
insh
0.0
insl
0.0
I-76
Input Shift Upper Limit
Available if the input type connected to the Controller is a thermocouple or platinum resistance
thermometer.
Input Shift Lower Limit
Available if the input type connected to the Controller is a thermocouple or platinum resistance
thermometer.
Digital Controller E5CK
Setup Mode
in-t
2
in-h
Input Type
Codes are used to determine the input types connected to terminals 6 to 8.
Scaling Upper Limit
Used if the input type connected to the Controller is an analog input (voltage or current input).
100
in-l
0
dp
0
d-u
c
Scaling Lower Limit
Used if the input type connected to the Controller is an analog input (voltage or current input).
Decimal Point
Used if the input type connected to the Controller is an analog input (voltage or current input).
°C/°F Selection
Used if the input type connected to the Controller is a temperature input (thermocouple or platinum
resistance thermometer).
Parameter Initialize
init
no
heat
out2
al-1
sub1
al-2
alt1
Control Output 1 Assignment
Enables the Controller to have heating control, cooling control, alarm 1, alarm 2, alarm 3, and LBA
(loop break alarm) outputs.
Control Output 2 Assignment
Enables the Controller to have heating control, cooling control, alarm 1, alarm 2, alarm 3, and LBA
(loop break alarm) outputs.
Auxiliary Output 1 Assignment
Enables the Controller to have alarm 1, alarm 2, alarm 3, LBA (loop break alarm), error 1, and error 2
outputs.
Alarm 1 Type
Temperature
Controller
out1
Available only when the Controller has an alarm
output (see the table on the next page).
2
al1n
Alarm 1 Open in Alarm
n-o
alt2
Alarm 2 Type
2
Alarm 2 Open in Alarm
al2n
n-o
oreU
Direct/Reverse Operation
or-r
Digital Controller
E5CK
I-77
Switch
setting
1
Alarm operation
Alarm output
When X is positive
Upper- and lower-limit alarm (deviation)
X
X
When X is negative
Always ON
ON
OFF
2
SP
Upper-limit alarm (deviation)
X
ON
OFF
Lower-limit alarm (deviation)
X
ON
X
OFF
SP
3
ON
SP
X
ON
OFF
OFF
SP
4
Upper- and lower-limit range alarm (deviation)
X
ON
OFF
5
Upper- and lower-limit alarm with standby sequence (deviation)
Upper-limit alarm with standby sequence (deviation)
ON
X
ON
SP
Absolute-value upper-limit alarm
X
ON
ON
OFF
X
SP
X
ON
OFF
8
Always OFF
X
ON
SP
Lower-limit alarm with standby sequence (deviation)
X
SP
OFF
7
Always OFF
SP
X
OFF
6
SP
X
OFF
ON
SP
X
OFF
OFF
0
9
Absolute-value lower-limit alarm
0
X
ON
OFF
OFF
0
10
Absolute-value upper-limit alarm with standby sequence
X
ON
ON
X
ON
0
X
OFF
OFF
0
11
Absolute-value lower-limit alarm with standby sequence
ON
OFF
0
I-78
Digital Controller E5CK
0
X
ON
OFF
X
0
Expansion Mode
sl-h
SP Setting Upper Limit
1300
sl-l
SP Setting Lower Limit
-200
cntl
PID/ON/OFF
pid
st
ST
Available if the Controller in standard control or advanced PID control has a temperature input.
off
st-b
15.0
alfa
ST Stable Range
Available if the Controller in standard control or advanced PID control with the ST set to ON has a temperature input.
α
Available if the Controller is in advanced PID control with the ST set to OFF.
0.65
at-g
AT Calculated Gain
Available if the Controller is in advanced PID control with the ST set to OFF.
1.0
rset
Standby Sequence Reset Method
0
ret
Automatic Return of Display Mode
at-h
Temperature
Controller
1
AT Hysteresis
Available if the Controller is in advanced PID control with the ST set to OFF.
0.2
lbab
LBA Detection Width
Available only when the LBA (loop break alarm) function of the Controller is selected.
0.2
Digital Controller
E5CK
I-79
Option Mode
eU-m
0
eU-1
Multi-SP Function
Available for the event input function.
Event Input Assignment 1
Available for the event input function.
stop
sbit
Communication Stop Bit
Used when the communications function is being used.
2
len
Communication Data Length
Used when the communications function is being used.
7
prty
Communication Parity
Used when the communications function is being used.
eUen
bps
Communication Baud Rate
Used when the communications function is being used.
96
u-no
Communication Unit No.
Used when the communications function is being used.
0
tr-t
Transfer Output Type
Set when the transfer output function is being used.
sp
tr-h
1300
tr-l
Transfer Output Upper Limit
Set when the transfer output function is being used.
Transfer Output Lower Limit
Set when the transfer output function is being used.
-200
I-80
Digital Controller E5CK
■ How to Use the Error Display
When an error has occurred, the No.1 display alternately indicates error codes together with the current display item.
This section describes how to check error codes on the display, and the actions that must be taken to remedy the problem.
Input Error
Meaning
Input is in error.
Action
Check the wiring of inputs, disconnections, and shorts, and check the input type and the input type jumper connector.
Operation at Error
For control output functions, output the manipulated variable matched to the setting of the “MV at PV error” parameter (level 2 mode). Alarm output functions are activated when the upper limit is exceeded.
Memory Error
Meaning
Internal memory operation is in error
Action
First, turn the power OFF then back ON again. If the display remains the same, the E5CK Controller must be repaired. If the display is restored to normal, the probable cause may be external noise affecting the control system.
Check for external noise.
Operation at Error
Control output functions turn OFF (2 mA max. at 4 to 20 mA output, and output equivalent to 0% in case of other
outputs). Alarm output functions turn OFF.
A/D Converter Error
Meaning
Internal circuits are in error.
Action
First, turn the power OFF then back ON again. If the display remains the same, the E5CK Controller must be repaired. If the display is restored to normal, the probable cause may be external noise affecting the control system.
Check for external noise.
Operation at Error
Control output functions turn OFF (2 mA max. at 4 to 20 mA output, and output equivalent to 0% in case of other
outputs). Alarm output functions turn OFF.
Calibration Data Error
Calibration data is in error.
Action
Must repair.
Operation at Error
Both control output functions and alarm output functions are active. However, note that the readout accuracy is not
assured.
Display Range Over
Meaning
Though not an error, this is displayed when the process value exceeds the display range when the control range
(setting range ±10%) is larger than the display range (−1999 to 9999).
• When less than “−1999”
Operation
• When greater than “9999”
Control continues, allowing normal operation.
Digital Controller
E5CK
I-81
Temperature
Controller
This error is output only during temperature input and is displayed for two seconds when the power is turned ON.
Meaning
■ Fuzzy Self-tuning
Fuzzy self-tuning is a function that enables the E5CK to calculate the
most suitable PID constants for the controlled object.
Features
• The E5CK determines by itself when to perform fuzzy self-tuning.
Fuzzy Self-tuning Function
The fuzzy self-tuning function has three modes.
PID Constant Refreshing Conditions
If the step control amount is applied before the maximum temperature slope (R) is obtained, SRT will not renew any PID constant. If the
proportional band obtained from the R and L values that were measured before the imposition had been completed is larger than the
present proportional band, the PID constants will be renewed
because the measured value is in the direction towards the suitable
proportional band value, and the set point at that time will be the
SRT-executed set point.
Slope (R)
In SRT (step response tuning) mode, the PID constants are tuned
using a step response method at the time the set point is
changed.
In DT (disturbance tuning) mode, the PID constants are amended
so that the controlled temperature will be within the target range
set in advance when there is external disturbance.
In HT (hunting tuning) mode, when hunting occurs, the PID constants are amended to suppress the hunting.
Note: Be sure to turn on the power supply to the load either before or
simultaneously with the start of Temperature Controller operation.
Dead time will be measured from the time the Temperature
Controller starts operating. If a load such as a heater is turned
on after the Temperature Controller is turned on, dead time
longer than the actual value will be measured and inappropriate PID constants will be obtained. If an extremely large
amount of dead time is measured, the control amount will be
set to 0% for a short period of time before being returned to
100%, and the constants will then be retuned. Retuning is performed only for large amounts of dead time, so be sure to follow
the precaution given above when starting operation.
Temperature
Time
Stable Temperature Status
If the temperature is within the stable range for a certain time, it is
deemed that the temperature is stable. This time is called stability
judgement time. Like PID constants, stability judgement time is
adjusted with fuzzy self-tuning according to the characteristics of the
object to be controlled. Fuzzy self-tuning will not be activated if the
temperature is stable because the Temperature Controller deems
that temperature control is smooth.
Shorter than the stability judgement time
Startup Conditions of SRT
SRT will start if the following conditions are satisfied simultaneously
when the E5CK is turned on or the set point is changed.
At the time the E5CK starts
operating
Stable range
SP
Stable
range
Stable
range
Set
point
At the time set point is
changed
1. The set point at the time the 1. The new set point is different
from the set point used at the
E5CK starts operating is diftime SRT was last executed
ferent from the set point used
(see note).
at the time SRT was last executed (see note).
2. The process value is in stable
condition before the set point
2. The process value at the time
is changed.
the E5CK starts operating is
smaller than the set point in 3. A larger set point value is set
reverse operation and larger
in reverse operation and a
than the set point in normal
smaller set point is set in noroperation.
mal operation.
Note: The last SRT-executed set point is set to 0 before shipping and
when changing from advanced PID control to advanced PID
control with fuzzy self-tuning.
Stable
Stable
Balanced Status
If the process value is within the stable range for 60 s when there is
no output, it is deemed that the temperature is balanced.
Startup Conditions of DT
1. DT will start if the temperature that has been stable varies due to
external disturbance and the deflection of the temperature
exceeds the stable range, and then the temperature becomes
stable, provided that the number of maximum temperature values
is less than four.
2. DT will start if the set point is changed under the condition that
SRT does not start and the temperature becomes stable, provided that the number of maximum temperature values is less
than four.
If there are four or more maximum temperature values, HT will
start.
Extreme value 2
Set point change
Temperature
SP
Extreme value 1
Time
I-82
Digital Controller E5CK
(Set to
15.0°C
before
shipping)
Stability judgement time
Startup Conditions of HT
HT will be ON when there is hunting with four or more maximum temperature values (extreme values) while SRT is not being executed.
Extreme value 2
Extreme value 4
Temperature
SP
Extreme
value 1
Extreme
value 3
Time
Temperature
Controller
Note: In specific applications where temperature varies periodically
due to disturbance, internal parameters need to be adjusted.
For details, refer to the E5CK User’s Manual.
Digital Controller
E5CK
I-83
Precautions
■ Period and Scope of Guarantee
Unit with Standard Specifications
Three-year Guarantee
Scope of Guarantee
Period of Guarantee
Should the Unit malfunction during the guarantee period, OMRON
shall repair the Unit or replace any parts of the Unit at the expense of
OMRON.
The above does not apply in the following cases.
The guarantee period of the Unit is three years starting from the date
the Unit is shipped from the factory.
1. Any malfunction of the Unit due to the incorrect use or improper
handling of the Unit.
2. Any malfunction of the Unit not originating from the Unit.
3. Any malfunction of the Unit due to a modification of the Unit or
repairs to the Unit carried out by any person not authorized by
OMRON.
4. Any malfunction of the Unit due to any natural disaster.
The Unit is guaranteed under the following operating conditions.
Scope of Guarantee
1. Average Operating Temperature (see note): −10°C to 50°C
2. Mounting Method: Standard mounting
Top
OMRON shall not be responsible for any damage or loss induced by
any malfunction of the Unit.
Bottom
Note: Average Operating Temperature
Refer to the process temperature of the Unit mounted to a control panel and connected to peripheral devices on condition that
the Unit is in stable operation, sensor input type K is selected
for the Unit, the positive and negative thermocouple input terminals of the Unit are short-circuited, and the ambient temperature is stable.
Should the Unit malfunction during the guarantee period, OMRON
shall repair the Unit or replace any parts of the Unit at the expense of
OMRON.
The above does not apply in the following cases.
1. Any malfunction of the Unit due to the incorrect use or improper
handling of the Unit.
2. Any malfunction of the Unit not originating from the Unit.
3. Any malfunction of the Unit due to a modification of the Unit or
repairs to the Unit carried out by any person not authorized by
OMRON.
4. Any malfunction of the Unit due to any natural disaster.
OMRON shall not be responsible for any damage or loss induced by
any malfunction of the Unit.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. H079-E1-05
I-84
In the interest of product improvement, specifications are subject to change without notice.
Digital Controller E5CK
Similar pages