Gamewell-FCI NY-PLATE Addressable xp95 manual pull station Datasheet

MS95-L Series
Addressable XP95
Manual Pull Stations
Description
The Gamewell-FCI MS95-L Series is a state-of-the-art, single- or dual-action XP95 pull station that includes an XP95
addressable interface for any Gamewell-FCI 600 Series
Fire Alarm Control Panel (FACP). Because the MS95-L
Series is addressable, the FACP can display the exact
location of the activated manual station. This display leads
fire personnel quickly to the location of the alarm.
Operation
Pushing in, then pulling down on the handle causes it to
latch in the down/activated position. Once latched, the
word “ACTIVATED” (appears in bright yellow) at the top of
the handle, while a portion of the handle protrudes from the
bottom of the station. To reset the station, simply unlock the
station with the key and pull the door open. This action
resets the handle; closing the door automatically resets the
switch. Each manual station, on command from the control
panel, sends data to the panel representing the state of the
manual switch. The DIP switch is used to set addresses.
Construction
MS95-L
Features
•
•
•
•
®
Shell, door, and handle are molded of durable LEXAN (or
polycarbonate equivalent) with a textured finish.
•
Installation
The MS95-L Series will mount semi-flush into a singlegang, double-gang, or standard 4" (10.16 cm) square electrical outlet box, or will surface mount to the Model SB-IO
surface backbox. If the MS95-L Series is being semi-flush
mounted, then the optional trim ring (BG-TR) may be used.
The BG-TR is usually needed for semi-flush mounting with
4" (10.16 cm) or double-gang boxes (not with single-gang
boxes).
Engineer’s Specifications
•
•
•
•
•
•
•
•
Manual Fire Alarm Stations shall be non-coded, with a keyoperated reset lock so that they may be tested, and are
Lexan® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
Meets UL Standard 38, for manually actuated
signaling boxes
Maintenance personnel can open the station without
causing an alarm condition
Built- in bicolor LED, which is visible through the
handle of the station, flashes in normal operation and
latches steady red when in alarm
Handle latches in down position and the word
“Activated” appears to clearly indicate the station has
been operated
Captive screw terminals wire-ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm²
wire)
Semi-flush, mounts to a standard single gang (2.125”
[5.3975] minimum depth), double gang, or 4” (10.16 cm)
square electrical box
Smooth dual-action design with key reset
Within ADA 5 lb. pull force
Highly visible, attractive shape and textured finish
NYC backplate provided for manual pull station
Braille text imprinted on the station handle
Optional trim ring (BG-TR)
Up to 126 stations per XP95 loop
An ISO 9000-2000 Company
SIGNALING
S281
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
CS-2487 Rev. A2 page 1 of 2
©2008 Honeywell International Inc. All rights reserved.
Specifications
Engineer’s Specifications (Continued)
designed so that after actual Emergency Operation, a key
can be used to restore it to “Normal.”
An operated station shall automatically condition itself so
as to be visually detected as activated. Manual stations
shall be constructed of red-colored LEXAN® (or polycarbonate equivalent) with clearly visible operating instructions provided on the cover. The word FIRE shall appear
on the front of the stations in white letters, 1.00 inches
(25.4 mm) or larger. Stations shall be suitable for surface
mounting on matching backbox SB-I/O; or semi-flush
mounting on a standard single-gang, double-gang, or 4"
(10.16 cm) square electrical box, and shall be installed within
the limits defined by the Americans with Disabilities Act
(ADA) or per national/local requirements. Manual Stations
shall be Underwriters’ Laboratories Listed.
Normal Operating
Voltage:
Maximum SLC
Circuit Voltage:
Maximum SLC
Circuit Current:
Standby Current:
Alarm Current:
24 VDC
28.0 VDC
170 mA
0.0005 A
0.0015 A
Ordering Information
Model
Description
MS95-SL
MS95-DL
SB-I/O
BG-TR
NY-PLATE
XP-95 pull station, single with key
XP-95 pull station, dual with key
Surface box
Optional trim ring
NYC backplate for manual pull station
Manual stations shall connect with two wires to one of the
control panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations
shall provide address setting by use of rotary decimal
switches.
The loop poll LED shall be clearly visible through the front
of the station. The LED shall flash while in the “Normal”
condition, and remain steadily illuminated when in alarm.
NYC-Plate
The NYC-Plate provides the backplate for the manual pull
station. (See Figure 1).
Figure 1 NY-Plate
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2487 Rev. A2 page 2 of 2
www.gamewell-fci.com