Advantech ADAM-5000-485 Distributed da&c system based on rs-485 Datasheet

ADAM-5000/485
ADAM-5000E
Distributed DA&C System
Based on RS-485
Features
 RS-485 Communication for easy installation and networking
 4 or 8 slots for up to 128 points data monitoning card control in one
module
 Extensive Software support, inclucles windows DLL drivers, OCX drivers,
OPC server and popular HMI/SCAPA Software driver.
 Seamlessly inteqrated with easy-to-use ADAMView data acquisition
Software.
Introduction
The ADAM-5000/485 and ADAM-5000E systems use the EIA RS-485 communication protocol. This is the industry's most widely used, balanced, bidirectional transmission line
standard. The RS-485 was specifically developed for industrial applications to transmit and receive data at high rates over long distances.
Processor




CPU
I/O module capacity
Watchdog Timer
Power Consumption
Power Requirements
16-bit microprocessor
4 or 8
Yes
1.0 W (ADAM-5000/485)
4.0 W (ADAM-5000E)
Isolation
 Communication
Isolation
 Communication Power
Isolation
 I/O Module Isolation
2500 VDC (ADAM-5000/485)
3000 VDC (ADAM-5000E)
3000 VDC
3000 VDC
Diagnosis
 Status Display
 Self-test
 Software Diagnosis
Power, CPU, communication
Yes, while on
Yes
Communication
 Network
 Speeds (bps)
 Max. Communication
Distance
 Command Format
 Reliability Check
 Asynchronous
Data Format
 Maximum Nodes
 Protection
RS-232 or RS-485 (2-wire) to host
1200, 2400, 4800, 9600, 19.2 k, 38.4 k, 57.6 k, and
115.2 kbps
4000 feet (1.2 km)
ASCII command/response protocol
Communication error checking with checksum
1 start bit, 8 data bits, 1 stop bit, no parity
Up to 256 multi-drop systems per host serial port
Transient suppression on
RS-485 communication lines
Distributed DA&C Systems
 Unregulated +10 to +30 VDC
 Protected against Power Reversal
 Power Protection
Transient suppression on power input
Mechanical
 Case
 Plug-in Screw
Terminal Block
KJW with captive mounting hardware
Accepts 0.5 mm2 to 2.5 mm2 , 1 - #12 or 2 - #14 to
#22 AWG
Environment
 Operating Temperature -10 ~ 70° C (14 ~ 158° F)
 Storage Temperature -25 ~ 85° C (-13 ~ 185° F)
 Humidity
5 ~ 95%, non-condensing
Ordering Information





ADAM-5000/485
ADAM-5000E
PCLS-OPC/ADM
PCLS-OCX
PCLS-ADAMVIEW32
Distributed DA&C System Based on RS-485 (4 slot)
Distributed DA&C System Based on RS-485 (8 slot)
OPC Server for ADAM-4000/5000 Series (RS-485)
ActiveX Control for Data Acquisition and Control
ADAMView Data Acquisition Software
ADAM-5000/485
ADAM-5000E
Panel/rack
mounting hole
RS-232 port
RS-485 port
RS-485 port
Diagnostic LED
Communication
terminal
(RS-485 port)
Power terminal
Panel/rack
mounting hole
Locking buttons
DIP switch
Industrial connector
Feature Details
Plug-in terminal
Intelligent RS-485 Data Flow Control
Two-wire Communication
The ADAM-5000/485 and ADAM-5000E systems use a single twisted pair of wires to
transmit and receive data. Special circuitry ensures clean, reliable communication and
suppresses communication line noise. This reduces overall network cost by simplifying
installation and minimizing the number of cables, connectors, communication repeaters
and filters required.
Surge Protection
High-speed transient suppressors protect the system from dangerous voltage surges
or power spikes.
The RS-485 communication protocol will support half-duplex communication. Only two
wires are needed for transmitting and receiving data. Handshaking signals such as RTS
(Request to Send) normally control the direction of the data flow. A special I/O circuit in the
ADAM-4510 and ADAM-4520 senses the data flow direction and automatically switches
the transmission direction, making handshaking signals unnecessary. The RS-485 bus
control is completely transparent to the user.
Built-in RS-232 Communication
ADAM-5000/485 and ADAM-5000E systems provide up to 64/128 I/O points and an
RS-232 port. A host PC can be locally connected to the system to control and monitor
simple applications, thereby facilitating local troubleshooting.
ASCII-based Protocol
Network Expansion
The ADAM-4510 repeater simply amplifies or boosts existing signals, enabling them to
travel over longer distances.
Each repeater allows you to add up to 32 ADAM-5000 units to your network, extending
the network by another 4000 feet (1.2 km). Up to 256 ADAM-5000/485, ADAM-5000E
units can be connected to a single RS-485 network.
ADAM-5000 commands are issued in printable ASCII-based format. ADAM applications
can be written in any high-level language that supports ASCII string functions, such as
C, Pascal or BASIC. ASCII support means you can use virtually any computer to manage
your ADAM network.
RS-232 to RS-485 Conversion
RS-232 serial ports are standard with most industrial computer systems. Though widely
accepted, RS-232 has limited transmission speed, range and networking capabilities.
The RS-485 standard overcomes these limitations by using differential voltage lines for
data and control signals.
The ADAM-4520's isolated converter lets you take advantage of an RS-485 on an RS-232
system by converting RS-232 signals to RS-485 signals. Software written for half-duplex
RS-232 may also be used without modification.
The ADAM-4520 helps you build an industrial grade, long distance communication
system with standard PC hardware.
Online Download www.advantech.com/products
All product specifications are subject to change without notice
Last updated : January 2005