NI NICFP-2020 8 or 16 digital outputs/fused outputs for short circuit protection cfp-do-410 Datasheet

Digital Output Modules for Compact FieldPoint
NI cFP-DO-400, NI cFP-DO-401,
NI cFP-DO-403, NI cFP-DO-410
• 8 or 16 digital outputs
• 5 VDC
• 12 VDC
• 24 VDC
• Fused outputs for short circuit
protection cFP-DO-410
• 2,300 Vrms bank isolation for transient
overvoltage protection
• Hot-swappable with autoconfiguration
• -40 to 70 °C operating range
Module
cFP-DO-400
cFP-DO-401
cFP-DO-403
cFP-DO-410
Output Channels
8
16
16
8
Output Ranges
10 to 30 VDC, sourcing
10 to 30 VDC, sourcing
5 to 30 VDC, sinking
5 to 30 VDC, sourcing
Output Current Rating
(see Specifications for More Details)
1.5 A
1.5 A
2A
1A
Overview
The National Instruments cFP-DO-4xx devices are versatile digital output
modules for Compact FieldPoint that you can use to control digital signals
ranging from 5 to 30 V. These modules are commonly used to control
indicator lights, external relays, and CMOS and TTL devices. All the
modules include onboard diagnostics to ensure trouble-free installation
and maintenance.
Digital Output Modules
The cFP-DO-4xx modules provide built-in module-to-module isolation to
protect your Compact FieldPoint system and controller or communication
interface from high voltage levels. All the digital output modules use a
common ground plane for the digital output channels.
The cFP-DO-400 and cFP-DO-401 sourcing digital output modules are
capable of providing up to 2 A per channel, with a maximum power limit
across the entire module as explained in the specifications section.
Compatibility
Examples
12 and 24 VDC
12 and 24 VDC
5, 12, and 24 VDC
5, 12, and 24 VDC
Electronically
Fused Outputs
–
–
–
3
All Channel
Update Rate
20 KHz
20 KHz
20 KHz
20 KHz
The cFP-DO-403 sinking digital output module is capable of providing
up to 2 A per channel, with a maximum power limit across the entire
module as explained in the specifications section.
The cFP-DO-410 sourcing digital output module is capable of providing
up to 1 A per channel. It also features an electronic fuse that prevents
damage to the module due to short circuits or other overcurrent situations.
The fuses automatically reset when the output returns to a normal state.
An LED indicates an overcurrent fault.
All the channels on the cFP-DO-4xx modules feature LEDs that indicate
the output state of each channel. The modules feature an all-channel
update rate of 20 kHz. Overall data throughput depends on software loop
speeds and network speeds.
Isolation
The cFP-DO-4xx modules feature optical bank isolation with 2,300 Vrms
of breakdown isolation. These Compact FieldPoint modules do not have
channel-to-channel isolation.
Digital Output Modules for Compact FieldPoint
Field I/O Connections
Compact FieldPoint modules include a built-in power distribution bus that offers multiple power connections on the module. A field-wired power
supply connected to the voltage (V) and common (C) terminals is internally connected to a power distribution bus that provides additional breakout
terminals for voltage supply (VSUP) and common (COM). These terminals deliver a convenient way to distribute power to field devices that require
external power.
Each cFP-DO-400 and cFP-DO-410 has: . . . . . . . . . . . . . . . . . . . . . . . .
• 8 digital output terminals (VOUT) . . . . . . . . . . . . . . . . . . . . . . . . . . .
• 16 common terminals (COM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• 8 power connections to power field devices (VSUP) . . . . . . . . . . . . .
Each cFP-DO-401 and cFP-DO-403 has:
• 16 digital output terminals (VOUT)
• 8 common terminals (COM)
• 8 power connections to power field devices (VSUP)
2 A Max
User Supplied
Fuse
V
V
5 to 30 VDC
External Power
Supply
SUP
V
OUT
5 to 30 VDC
External Power
Supply
Load
+
V
+
V
SUP
VOUT
Load
–
2 A Max
User Supplied
Fuse
–
COM
VOUT
1.5 A Max
User Supplied
Fuse
C
Load
cFP-DO-403
COM
Figure 1. Wiring Schematics for Digital Output Modules
cFP-DO-400/401/410
C
To next channel
Ordering Information
NI cFP-DO-400
NI cFP-DO-401
NI cFP-DO-403
NI cFP-DO-410
....................................................................777318-400
....................................................................777318-401
....................................................................777318-403
....................................................................777318-410
Recommended Compact FieldPoint System Products
NI cFP-2020 ......................................................................777317-2020
NI cFP-BP-4 ............................................................................778617-04
NI cFP-CB-1............................................................................778618-01
NI PS-4 power supply............................................................778805-90
NI Developer Suite Professional Control Edition..................777906-03
BUY NOW!
For complete product specifications, pricing, and accessory
information, call 800 813 3693 (U.S.) or go to ni.com/info and
enter cfpdo400, cfpdo401, cfpdo403, and/or cfpdo410.
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)
2
Digital Output Modules for Compact FieldPoint
Specifications
Typical for -40 to 70 °C unless otherwise noted.
Digital Output Channels
Number of output channels
cFP-DO-400, cFP-DO-410 ................ 8
cFP-DO-401, cFP-DO-403 ................ 16
Voltage range...................................... 5 to 30 VDC
Output impedance at 10 to 30 V ........ 0.3 (0.3 V drop at 1 A)
cFP-DO-403 ..................................... 0.12 Ω
Output impedance at 5 to 10 V .......... 2 Ω
Maximum output current per channel at 10 to 30 V range
cFP-DO-400, cFP-DO-401 ................ 1.5 A
cFP-DO-403 ..................................... 2.0 A
cFP-DO-410 ..................................... 1 A
Maximum output current on all channels
cFP-DO-400 ..................................... 8 A2
cFP-DO-401 ..................................... 8 A2
cFP-DO-403 ..................................... 16 A2 at -40 to 60 °C
12 A2 at 60 to 70 °C
cFP-DO-410 ..................................... 8 A
Maximum output current at 5 to 10 V range
Per channel ..................................... 0.67 A
All channels, cFP-DO-4001 .............. 1.35 A2
All channels, cFP-DO-4011 .............. 1.2 A2
Output delay time
Turn ON........................................... 20 µs
Turn OFF .......................................... 50 µs
Protection
Flyback diode to COM for inductive loads
Leakage, overcurrent condition
Power-on state.................................... Off, until set to power-on state
stored in local network module
1The
sum of the squares of the output currents on every channel must be less than or equal
to this value.
Power Requirements
Power from network module
cFP-DO-400 ..................................... 300 mW
cFP-DO-401 and cFP-DO-403 .......... 600 mW
cFP-DO-410 ..................................... 400 mW
Isolation Voltage
Channel-to-channel isolation.............. No isolation between channels
Transient overvoltage.......................... 2,300 Vrms
Physical Characteristics
LED indicators
POWER (green) ...............................
READY (green) ................................
<0...15> or <0...7> (green) ..............
Dimensions (including terminal base)
Power on and self-test passed
Module configured and ready
On/off state of each channel
10.7 by 10.9 by 9.1 cm
(4.2 by 4.3 by 3.6 in.)
Weight................................................. 136 g (4.8 oz)
Environment
Operating temperature ....................... -40 to 70 °C
Storage temperature........................... -55 to 85 °C
Relative humidity ................................ 10 to 90%, noncondensing
Shock and Vibration
Operating vibration, random
(IEC 60068-2-64) ............................. 10 to 500 Hz, 5 grms
Operating vibration, sinusoidal
(IEC 60068-2-6) ............................... 10 to 500 Hz, 5 g
Operating shock
(IEC 60068-2-27) ............................. 50 g, 3 ms half sine,
18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations
Safety and Compliance
Safety
This product is designed to meet the requirements of the following
standards of safety for electrical equipment for measurement, control,
and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 61010-1, CSA 61010-1
Note: For UL and other safety certifications, refer to the product label or
visit ni.com/certification, search by model number or product line, and
click the appropriate link in the Certification column.
Electromagnetic Compatibility
This product is designed to meet the requirements of the following
standards of EMC for electrical equipment for measurement, control,
and laboratory use:
• EN 61326 EMC requirements; Minimum Immunity
• EN 55011 Emissions; Group 1, Class A
• CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A
Note: For EMC compliance, operate this device according to
product documentation.
CE Compliance
This product meets the essential requirements of applicable European
Directives, as amended for CE marking, as follows:
• 2006/95/EC; Low-Voltage Directive (safety)
• 2004/108/EC; Electromagnetic Compatibility Directive (EMC)
Note: Refer to the Declaration of Conformity (DoC) for this product for
any additional regulatory compliance information. To obtain the DoC for
this product, visit ni.com/certification, search by model number or
product line, and click the appropriate link in the Certification column.
Waste Electrical and Electronic Equipment (WEEE)
EU Customers: At the end of their life cycle, all products must be
sent to a WEEE recycling center. For more information about WEEE
recycling centers and National Instruments WEEE initiatives,
visit ni.com/environment/weee.htm.
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)
3
IN
TA
PL
AN
MA
IN
NI Services and Support
P
DE
LO
Y
EL
OP
SERVICE
NEEDS
V
DE
NI has the services and support to meet
your needs around the globe and through
the application life cycle – from planning
and development through deployment
and ongoing maintenance. We offer
services and service levels to meet
customer requirements in research,
design, validation, and manufacturing.
Visit ni.com/services.
Training and Certification
NI training is the fastest, most certain route to productivity with our
products. NI training can shorten your learning curve, save development
time, and reduce maintenance costs over the application life cycle. We
schedule instructor-led courses in cities worldwide, or we can hold a
course at your facility. We also offer a professional certification program
that identifies individuals who have high levels of skill and knowledge on
using NI products. Visit ni.com/training.
Professional Services
Our NI Professional Services team is composed of NI applications
and systems engineers and a worldwide National Instruments Alliance
Partner program of more than 600 independent consultants and
integrators. Services range
from start-up assistance to
turnkey system integration.
Visit ni.com/alliance.
OEM Support
We offer design-in consulting and product integration assistance if you
want to use our products for OEM applications. For information about
special pricing and services for OEM customers, visit ni.com/oem.
ni.com • 800 813 3693
National Instruments • [email protected]
Local Sales and Technical Support
In offices worldwide, our staff is local to the country, giving you access
to engineers who speak your language. NI delivers industry-leading
technical support through online knowledge bases, our applications
engineers, and access to 14,000 measurement and automation
professionals within NI Developer Exchange forums. Find immediate
answers to your questions at ni.com/support.
We also offer service programs that provide automatic upgrades to
your application development environment and higher levels of technical
support. Visit ni.com/ssp.
Hardware Services
NI Factory Installation Services
NI Factory Installation Services (FIS) is the fastest and easiest way to
use your PXI or PXI/SCXI combination systems right out of the box.
Trained NI technicians install the software and hardware and configure
the system to your specifications. NI extends the standard warranty by
one year on hardware components (controllers, chassis, modules)
purchased with FIS. To use FIS, simply configure your system online
with ni.com/pxiadvisor.
Calibration Services
NI recognizes the need to maintain properly calibrated devices for
high-accuracy measurements. We provide manual calibration
procedures, services to recalibrate your products, and automated
calibration software specifically designed for use by metrology
laboratories. Visit ni.com/calibration.
Repair and Extended Warranty
NI provides complete repair services for our products. Express repair
and advance replacement services are also available. We offer
extended warranties to help you meet project life-cycle requirements.
Visit ni.com/services.
*351564B-01*
351564B-01
2008-9484-161-101-D
©2008 National Instruments Corporation. All rights reserved. FieldPoint, National Instruments, National Instruments Alliance Partner, NI, ni.com, NI Developer Suite, and SCXI are
trademarks of National Instruments. Other product and company names listed are trademarks or trade names of their respective companies. A National Instruments Alliance Partner
is a business entity independent from NI and has no agency, partnership, or joint-venture relationship with NI.
Similar pages