ETC1 K3NR-NB1A High-speed, intelligent interface module Datasheet

Frequency/Rate Meter
K3NR
High-speed, Intelligent Interface Modules
with Seven Operating Modes Convert Single
or Dual Input Pulses to Display Values
• 50-kHz input range and 0.006% accuracy for sophisticated
control.
• A wide selection of outputs: relay, transistor, BCD, linear, or
communications.
• Maximum/Minimum value hold, set value write protection, and
more.
• Banks with four comparative output values and four prescale
values.
• Prescale function available, which displays in units of actual
physical parameters (length, volume, etc.).
• Set value teaching, linear output range teaching, and prescale
teaching are available using actual measured values.
• Displays values in hours, minutes, and seconds in operating
mode 6.
• A startup compensation time parameter keeps the
measurement operation from sending an unnecessary output
for a preset period up to 99.9 s.
• Built-in sensor power supply (12 VDC, 80 mA).
• Compact 1/8 DIN size.
• Conforms to EMC standards, EN61010-1 (IEC61010-1).
• UL/CSA approved.
Model Number Structure
■ Model Number Legend
Base Units and Output Boards can be ordered individually or as sets. Refer to the Output Board Combinations table on page 130.
K3NR -
Output Boards
K31 -
6
7
5
1
2
3 4
1, 2. Input Sensors Codes
NB: NPN inputs/Voltage pulse inputs
PB: PNP inputs
3. Supply Voltage
1:
100 to 240 VAC
2:
12 to 24 VDC
4. Display
A:Basic
C:Set Value LED Display
5, 6, 7, 8. Output Type Codes
C1: 3 comparative relay contact outputs (H, PASS, L: SPDT)
C2: 5 comparative relay contact outputs (HH, H, L, LL: SPSTNO; PASS: SPDT)
C5: 5 comparative relay contact outputs (HH, H, L, LL: SPSTNC; PASS: SPDT)
T1: 5 comparative transistor outputs (NPN open collector)
T2: 5 comparative transistor outputs (PNP open collector)
B2: BCD output (NPN open collector) (see note)
B4: BCD output + 5 transistor outputs (NPN open collector)
L1: Linear output (4 to 20 mA) (see note)
Note: These output types are available on Basic Models only.
Base Units with Output Boards
K3NR 8
1
2 3 4
5 6 7 8
Linear output (1 to 5 VDC) (see note)
Linear output (1 mV/10 digits) (see note)
Linear output, 4 to 20 mA + 5 transistor outputs (NPN open
collector)
L5: Linear output, 1 to 5 V + 5 transistor outputs (NPN open collector)
L6: Linear output, 1 mV/10 digits+ 5 transistor outputs (NPN
open collector)
L7: Linear output, 0 to 5 VDC (see note)
L8: Linear output, 0 to 10 VDC (see note)
L9: Linear output, 0 to 5 VDC + 5 transistor outputs (NPN open
collector)
L10: Linear output, 0 to 10 VDC + 5 transistor outputs (NPN open
collector)
FLK1: Communication RS-232C (see note)
FLK2: Communication RS-485 (see note)
FLK3: Communication RS-422 (see note)
FLK4: RS-232C + 5 transistor outputs (NPN open collector)
FLK5: RS-485 + 5 transistor outputs (NPN open collector)
FLK6: RS-422 + 5 transistor outputs (NPN open collector)
L2:
L3:
L4:
Frequency/Rate Meter
K3NR
K-129
Panel
indicators
Base Units
Ordering Information
■ Base Unit
Input type
NPN/Voltage pulse
Supply voltage
100 to 240 VAC
PNP
12 to 24 VDC
100 to 240 VAC
12 to 24 VDC
Basic Models
These models provide a
present value LED and
front-panel control keys. Can
be connected to any Output
Board, or can be used for
display only without an
Output Board.
K3NR-NB1A
K3NR-NB2A
K3NR-PB1A
K3NR-PB2A
Set Value LED Models
These models provide a
present value LED, set
value LED, and front-panel
control keys. Can be
connected to Relay,
Transistor, or Combination
Output Boards.
K3NR-NB1C
K3NR-NB2C
K3NR-PB1C
K3NR-PB2C
■ Available Output Board Combinations
Output type
Output configuration
Output boards
Base units
Basic
Relay contact
Transistor
Set Value
LED Display
3 outputs: H, PASS, L (SPDT)
K31-C1
Yes
Yes
5 outputs: HH, H, L, LL (SPST-NO), and PASS (SPDT)
K31-C2
Yes
Yes
5 outputs: HH, H, L, LL (SPST-NC), and PASS (SPDT)
K31-C5
Yes
Yes
5 outputs (NPN open collector)
K31-T1
Yes
Yes
5 outputs (PNP open collector)
K31-T2
Yes
Yes
BCD (see note)
5-digit output (NPN open collector)
K31-B2
Yes
---
Linear
4 to 20 mA DC
K31-L1
Yes
---
1 to 5 VDC
K31-L2
Yes
---
1 mV/10 digits
K31-L3
Yes
---
Communication boards
(see note)
Combination output and
communication boards
0 to 5 VDC
K31-L7
Yes
---
0 to 10 VDC
K31-L8
Yes
---
RS-232C
K31-FLK1
Yes
---
RS-485
K31-FLK2
Yes
---
RS-422
K31-FLK3
Yes
---
BCD output + 5 transistor outputs (NPN open collector)
K31-B4
Yes
Yes
4 to 20 mA + 5 transistor outputs (NPN open collector)
K31-L4
Yes
Yes
1 to 5 V + 5 transistor outputs (NPN open collector)
K31-L5
Yes
Yes
1 mV/10 digits + 5 transistor outputs (NPN open collector)
K31-L6
Yes
Yes
0 to 5 VDC + 5 transistor outputs (NPN open collector)
K31-L9
Yes
Yes
0 to 10 VDC + 5 transistor outputs (NPN open collector)
K31-L10
Yes
Yes
RS-232C + 5 transistor outputs (NPN open collector)
K31-FLK4
Yes
Yes
RS-485 + 5 transistor outputs (NPN open collector)
K31-FLK5
Yes
Yes
RS-422 + 5 transistor outputs (NPN open collector)
K31-FLK6
Yes
Yes
Note: For details, refer to the Communication Operation Manual.
K-130
Frequency/Rate Meter K3NR
Specifications
■ Ratings
Supply voltage
100 to 240 VAC (50/60 Hz); 12 to 24 VDC
Operating voltage range
85% to 110% of supply voltage
Power consumption (see note)
15 VA max. (max. AC load with all indicators lit)
10 W max. (max. DC load with all indicators lit)
Sensor power supply
80 mA at 12 VDC±10%
Insulation resistance
20 MΩ min. (at 500 VDC) between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Dielectric strength
2,000 VAC for 1 min between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Noise immunity
±1,500 V on power supply terminals in normal or common mode ±1 µs, 100 ns for square-wave noise
with 1 ns
Vibration resistance
Malfunction: 10 to 55 Hz, 0.5-mm for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 0.75-mm for 2 hrs each in X, Y, and Z directions
Shock resistance
Malfunction: 98 m/s2 for 3 times each in X, Y, and Z directions
Destruction: 294 m/s2 for 3 times each in X, Y, and Z directions
Ambient temperature
Operating:
Storage:
−10°C to 55°C (with no icing)
−20°C to 65°C (with no icing)
Ambient humidity
Operating:
25% to 85% (with no condensation)
EMC
(EMI)
Emission Enclosure:
Emission AC Mains:
(EMS)
Immunity ESD:
Approved standards
UL508, CSA22.2;
Conforms to EN61326+A1, EN61010-1 (IEC61010-1)
Conforms to VDE0106/P100 (finger protection) when the terminal cover is mounted.
Weight
Approx. 400 g
EN61326+A1
Industry
CISPR 11 Group 1 class A: CISRP16-1/-2
CISPR 11 Group 1 class A: CISRP16-1/-2
EN61326+A1
Industry
EN61000-4-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:
EN61000-4-3:
10 V/m (amplitude-modulated,
80 MHz to 1 GHz) (level 3)
Immunity Fast Transient Noise: EN61000-4-4:
2 kV (power line) (level 3)
Immunity Burst Noise:
1 kV line to line (I/O signal line)
Immunity Surge:
EN61000-4-5:
1 kV line to line
2 kV line to ground (power line)
Immunity Conducted Disturbance EN61000-4-6:
3 V (0.15 to 80 MHz) (level 2)
Immunity Voltage Dip/Interrupting EN61000-4-11:
0.5 cycles, 0, 180°, 100% (rated voltage)
Panel
indicators
Note: A K3NR with DC supply voltage requires approximately 1 A DC as control power supply current the moment the K3NR is turned ON. Do not
forget to take this into consideration when using several K3NR units. When the K3NR is not in measuring operation (e.g., the K3NR has
been just turned ON or is operating for startup compensation time), the display will read “00000” and all outputs will be OFF.
Frequency/Rate Meter
K3NR
K-131
■ Characteristics
Input signal
No-voltage contact (30 Hz max., ON/OFF pulse width: 15 ms min.)
Voltage pulse (50 kHz max., ON/OFF pulse width: 9 µs min., ON voltage: 4.5 to 30 V/OFF voltage: −30 to 2 V)
Open collector (50 kHz max., ON/OFF pulse width: 9 µs min.)
Connectable Sensors
ON residual voltage: 3 V max.
OFF leakage current: 1.5 mA max.
Load current:
Must have switching capacity of 20 mA min.
Must be able to dependably switch a load current of 5 mA max.
Measuring accuracy
(at 23±5°C)
Operating modes 1 and 6: ±0.006%rdg±1 digit
Operating modes 2 to 5: ±0.02%rdg±1 digit
Measuring modes and
ranges
(Operating modes 1 to 6 are
for no-contact sensor
models)
Operating mode 1:
Operating mode 2:
Operating mode 3:
Operating mode 4:
Operating mode 5:
Operating mode 6:
Operating mode 7:
Rotational/circumferential speed 0.0005 to 50,000 Hz
Absolute ratio
0.0005 to 50,000 Hz
Error ratio
0.0005 to 50,000 Hz
Rotational difference
0.0005 to 50,000 Hz
Flow rate ratio
0.0005 to 50,000 Hz
Passing time
0.0005 to 50,000 Hz
Pulse counting
0 to 4G count (32-bit counter)
Max. displayed digits
5 digits (−19999 to 99999)
Display
7-segment LED
Polarity display
“−” is displayed automatically with a negative input signal.
Zero display
Leading zeros are not displayed.
Prescale function
Programming via front-panel key inputs. (0.0001 x 10−9 to 9.9999 x 109, decimal point can be set freely)
Can be set using prescale value teaching.
HOLD functions
(see note 2)
Max. value (peak) hold, Min. value (bottom) hold
External control
HOLD (Process value held)
RESET (Maximum/minimum data reset, counting value reset)
BANK (Selection of one bank out of 4 banks of set values)
(Selection of one bank out of 4 banks of prescale values)
Comparative output
hysteresis setting
Programmable with front-panel key inputs (1 to 9999).
Other functions
Variable linear output range (for models with linear outputs only) (note 1)
Remote/Local processing (available for communications output models only)
Maximum/Minimum value data reset with front panel keys
Comparative output pattern selection
Process time for averaging measured values
Startup compensation time (0.0 to 99.9 s)
Time unit display
Security
Memory power failure
Output configuration
Relay contact output (3 or 5 outputs)
Transistor output (NPN and PNP open collector), BCD (NPN open collector)
Parallel BCD (NPN open collector) + transistor output (NPN open collector)
Linear output (4 to 20 mA, 1 to 5 V) + transistor output (NPN open collector)
Communication functions (RS-232C, RS-485, RS-422)
Communication functions (RS-232C, RS-485, RS-422) + transistor output (NPN open collector)
Operating modes 1 to 6: 200 ms max.
Delay in comparative
1 ms max.
outputs (at transistor output) Operating mode 7:
Linear output response time Operating modes 1 to 6: 220 ms max.
Operating mode 7:
20 ms max.
Degree of protection
Front panel: NEMA4X for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Memory protection
Non-volatile memory (EEPROM) (possible to rewrite 100,000 times)
Note: 1. The linear output range cannot be set when connected to a 1 mV/10-digit Linear Output Board.
2. Not effective for operating mode 7.
K-132
Frequency/Rate Meter K3NR
■ Input/Output Ratings
Relay Contact Output
(Incorporating a G6B Relay)
Item
Resistive load (cosφ = 1)
Inductive load (cosφ = 0.4, L/R = 7 ms)
Rated load
5 A at 250 VAC; 5 A at 30 VDC
1.5 A at 250 VAC, 1.5 A at 30 VDC
Rated carry current
5 A max. (at COM terminal)
Max. contact voltage
380 VAC, 125 VDC
Max. contact current
5 A max. (at COM terminal)
Max. switching capacity
1,250 VA, 150 W
Min. permissible load
(P level, reference value)
10 mA at 5 VDC
Mechanical life
50,000,000 times min. (at a switching frequency of 18,000 times/hr)
Electrical life
(at an ambient temperature of 23°C)
100,000 times min. (at a rated load switching frequency of 1,800 times/hr)
375 VA, 80 W
Transistor Output
Rated load voltage
24 VDC max.
Max. load current
50 mA
Leakage current
100 µA max.
BCD Output
I/O signal name
Inputs
Outputs
Item
REQUEST, HOLD, MAX, MIN, RESET
DATA, POLARITY, OVERFLOW,
DATA VALID, RUN
Rating
Input signal
No-voltage contact input
Input current with no-voltage input
10 mA
Signal level
ON voltage: 1.5 V max.
OFF voltage: 3 V min.
Rated load voltage
24 VDC max.
Max. load current
10 mA
Leakage current
100 µA max.
Note: Logic method: negative logic
Linear Output
Item
4 to 20 mA
Resolution
4,096
Output error
±0.5% FS
Permissible load resistance
600 Ω max.
1 to 5 V
1 mV/10 digits (see note)
±1.5% FS
500 Ω min.
1 KΩ min.
Note: For the 1 mV/10-digit output, the output voltage changes for every 40 to 50 increment in the display value.
■ Communications Specifications
RS-232C, RS-422
4-wire, half-duplex
Synchronization method
Start-stop synchronization
Baud rate
1,200/2,400/4,800/9,600/19,200/38,400 bps
ASCII (7-bit)
Transmission code
Communications
RS-485
2-wire, half-duplex
Write
Comparative set value, prescaling value, remote/local programming, reset control of maximum/minimum values, and other setting mode items excluding communications conditions.
Read
Process value, comparative set value, maximum value, minimum value, model data, error code, and
others
For details, refer to Communication Operation Manual.
Frequency/Rate Meter
K3NR
K-133
Panel
indicators
Item
Transmission method
Connections
■ Terminal Arrangement
Terminal Numbers
Output unit
Output
unit
18 19 20 21 22 23 24 25 26
10 11 12 13 14 15 16 17
Input
unit
Input unit
1
2
3
4
5
6
7
8
9
Note: Terminals 7 to 13 are connected internally.
Terminals 7 and 11 are mutually isolated.
Input Unit
12 VDC
80 mA
When inputting the external control signals and input signals
through the open collector:
Transistor Inputs:
ON: Residual voltage must be 3 V max.
OFF: Leakage current must be 1.5 mA max.
The switching capacity must be 20 mA or greater.
When the external signal input is short-circuited, a voltage of
approximately 5 V will be applied to between the terminals 5 to 7
and the COM terminal, and a current of approximately 18 mA
(nominal value) will flow.
−
100 to 240 VAC
or 12 to 24 VDC
Signal input terminal
Note:
Check the power supply specifications of the model used before connecting the power supply.
Voltage Pulse Inputs
NPN Inputs
PNP-Inputs
External
sensor
power
10
supply (+)
+12 V
820 Ω
1
+12 V
590 Ω
+12 V
GND
590 Ω
820 Ω
Input B 2
External
sensor 11
power
supply (−)
Input A
10 k Ω
3
590 Ω
820 Ω
Input A
GND
+12 V
Input B
10 k Ω
4
590 Ω
820 Ω
Input B
1
820 Ω
GND
2
820 Ω
External
sensor
11
power
supply (−)
GND
GND
+12 V
590 Ω
+12 V
Internal circuits
Input A
+12 V
Internal circuits
External
sensor 10
power
supply (+)
11
590 Ω
Internal circuits
+
GND
GND
K3NR-NB
(NPN Input/Voltage Pulse Input)
NPN Open Collector Output
(NPN Linear 2-wire Output)
K3NR-PB (PNP Input)
Contact Output
Voltage Output
PNP Open Collector Output
Input resistance: 10 kΩ
10
10
1
1
+12 V
INA
10
11
10
11
11
2
3
4
2
INA
3
INB
4
+12V
GND
INB
1
2
3
1
4
+12V
INA INB
0V
INA
11
2
3
4
INB
0V
0V
Contact
NPN output sensor
Note: When the contact is shortcircuited, a current of approximately 13 mA will flow at a voltage of approximately 12 V.
Note: Connect the + side of the NPN
linear 2-wire input to terminal 1
and the − side to terminal 11.
K-134
Frequency/Rate Meter K3NR
Voltage pulse output sensor
Note: With voltage pulse input
not from a 3-wire sensor,
connect the + side to terminal 3 and the − side to
terminal 11.
PNP output sensor
Output Units
K31-C1: Relay (3 Outputs)
K31-C2: Relay (5 Outputs)
Outputs (5 A max. at 250 VAC)
H
18
19
PASS
20
21
Outputs (5 A max. at 250 VAC)
H
HH
L
22
23
24
25
26
K31-C5: Relay (5 Outputs)
18
LL
PASS
19
20
21
L
22
23
24
25
26
K31-T1: Transistor (NPN Open Collector)
Outputs (5 A max. at 250 VAC)
H
Outputs (50 mA max. at 24 VDC)
LL
PASS
L
18
19
20
21
22
p
19
20
24
25
26
(
H
PASS
L
LL
COM
21
22
23
24
25
26
4 8
K31-L1, L2, L3,-L4, -L5, -L6, -L7, -L8, -L9,
-L10: Linear
20
Note:
LL
COM
24
25
26
1 2 4 8 1 2 4 8 1 2 4 8 1 2 4 8 1 2
100
COMMON
101
102
HH
H
PASS
L
LL
COM
21
22
23
24
25
26
104
K31-FLK1: RS-232C
14 15 16 17 18 19 20 21 22 23 24 25
1 2 3 4 5 6 7 8 9 10 11 12 13
SG
With K31-L4/-L5/-L6/-L9/-L10 models, terminals 19
and 26 are connected internally.
K31-FLK2, -FLK5: RS-485
(Terminals 21 to 26 are provided only on K31-FLK5.)
K31-FLK3, -FLK6: RS-422
(The right connector is provided only on K31-FLK6)
Output NPN Tr.
(50 mA max. at 24 VDC)
Terminator
Outputs (50 mA max. at 24 VDC)
OFF
HH
H
PASS
L
LL
COM
20
21
22
23
24
25
26
Terminator
ON
6 7 8 9
1 2 3 4 5
OFF
SG
RDB
19
ON
SDB
RS-485
+
−
SDA
RDA
RS-422
18
103
Outputs (50 mA max. at 24 VDC)
SD
RD
19
L
23
20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
(Terminals 21 to 26 are provided only on K31-L4,
-L5, -L6, -L9, -L10.)
18
PASS
22
)
HH
104
L1, L4: 4 to 20 mA
L2, L5: 1 to 5 V
L3, L6: 1 mV/10 digit
L7, L9: 0 to 5 VDC
L8, L10: 0 to 10 VDC
+
−
H
21
LL
18
23
20
6 7 8 9
1 2 3 4 5
HH
H
COM
PASS
L
18
19
HH
DATA OVERFLOW
DATA VALID
RUN
COMMON
REQUEST
MAX. REQ.
MIN. REQ.
HOLD
RESET
POLARITY
HH
H
PASS
L
LL
COMMON
HH
Output NPN Tr.
(50 mA max. at 24 VDC)
LL
RS-232C
Panel
indicators
K31-FLK4: RS-232C + Transistor (NPN Open Collector)
9 8 7 6
5 4 3 2 1
L
PASS
COM
H
HH
SD
RD
9 8 7 6
5 4 3 2 1
SG
• D-sub 37P Connectors for BCD output (attachment)
Plug: XM2A-3701
Hood: XM2S-3711
• D-sub 25P connectors for RS-232C output (K31-FLK1) (order
separately)
Plug: XM2A-2501
Hood: XM2S-2511
• D-sub 9P connectors for RS-422 output (K31-FLK3 and K31FLK6) (order separately)
Plug: XM2A-0901
Hood: XM2S-0911
• D-sub 9P connectors for RS-232C output (K31-FLK4) (order
separately)
Plug: XM2D-0901
Hood: XM2D-0911
Frequency/Rate Meter
K3NR
K-135
■ Block Diagram
Key
switch
LED
Power supply
for sensor
Sensor A
Sensor B
GND
Input circuit
Control input Control input
circuit
Control power
supply
Power supply
circuit
K-136
Frequency/Rate Meter K3NR
Frequency
measurement
circuit
8-bit
microcomputer
Output
circuit
Waveform
adjustment
circuit
Voltage stabilizing
circuit
Power supply for
sensor (input circuit)
Voltage stabilizing
circuit
Frequency measurement circuit
Waveform adjustment circuit
8-bit microcomputer
Voltage stabilizing
circuit
Control input circuit
Operation
■ Main Functions
Output Pattern Selection c-out
Startup Compensation Time stime
The patterns of comparative output are selectable according to the
level change. Select the pattern according to the application.
The startup compensation time parameter keeps the measurement
operation from sending an unnecessary output corresponding to
instantaneous, fluctuating input from the moment the K3NR is turned
ON until the end of the preset period.
Standard Output
Set value HH
The compensation time can be set in a range from 0.0 to 99.9 seconds as the waiting time until the devices subject to measurement
become stable after the startup of the power supply.
Set value H
Set value L
Set value LL
Display
ON
OFF
Comparative output HH
Comparative output H
Startup compensation time
Set value L
PASS
Comparative output L
Comparative output LL
Time
00000 displayed
Zone Output
Set value HH
Power supply
Set value H
Set value L
Comparative
output L
Set value LL
Hysteresis hys
ON
OFF
Comparative output HH
Comparative output H
The hysteresis of comparative outputs can be set to prevent the chattering of comparative outputs. Refer to page 152 for more details.
PASS
Linear Output Range lset
Comparative output L
Comparative output LL
A linear output range can be set as required. A value corresponding
to the maximum output value and that corresponding to the minimum
output value can be set.
Level Output
Set value HH
Set value H
Set value L
Set value LL
Comparative output HH
For the 4- to 20-mA
output type
ON
OFF
Comparative output H
Output
20 mA
4 mA
Comparative output L
PASS
Note: The following setting conditions must be satisfied, otherwise no
zone output will turn ON correctly.
LL < L < H < HH
Lower
limit
Upper
limit
Display
Remote/Local Selection r-l
Select remote programming when performing all settings through the
host devices and select local programming when performing settings
through key operation.
Process Time for Averaging Measured
Value
Process time for averaging measured value is the time over which
the measured values will be averaged. If this time is shorter than the
input pulse interval, processing will be based on the input pulse interval.
Frequency/Rate Meter
K3NR
K-137
Panel
indicators
Comparative output LL
■ BCD Output Timing Chart
A request signal from an external device (such as a Programmable Controller) is required to read BCD data.
Single Sampling Data Output
Pulse with a width of no less than 20 ms.
(no more than 50 ms.)
REQ.
Max.
Min.
DATA
All data "high"
Data
All data "high"
DATA
VALID
40 ms
Approx. 30 ms
16 ms
Approximately 30 ms after the REQ signal rises, a sample is taken and the DATA VALID signal is output. Read the data when the DATA VALID
signal is ON.
The DATA VALID signal will turn OFF in 40 ms, and then in 16 ms, the data will go OFF.
Models with a BCD output have an open collector output configuration so that wired-OR connection is possible.
REQ.
(1)
K3NR (1)
Programmable
controller
REQ.
(1)
REQ.
(1)
K3NR (2)
DATA (incl. POL and OVER)
and DATA VALID are wired-OR
processed.
The RUN, HH, H, PASS, L, and
LL signals are always output
regardless of the status of the
REQ signal. Do not OR-wire
these signals.
K3NR (3)
DATA
(1)
(2)
(3)
DATA
VALID
*
*
*
*The period between the DATA VALID signal and the
REQ signal should be no less than 20 ms max.
Continuous Data Output
REQ.
Max.
Min.
DATA All data "high"
Data 1
Data 2
DATA
VALID
40ms
Approx.
30 ms
64ms
24ms
40ms
64ms
24ms
The K3NR outputs each measurement at an interval of 64 ms when a REQ signal is ON continuously.
If the HOLD signal is ON at the moment the DATA output is switched from Data 1 to Data 2 or vice versa, the output BCD data will be either Data
1 or Data 2 according to the timing of the HOLD signal. However, output data will never be below.
K-138
Frequency/Rate Meter K3NR
Example of Connection to Programmable Controller
K3NR
PC (SYSMAC)
DC Input Unit
1. COMMON
COM
2. 1
IN
3. 2
IN
IN
5. 8
IN
Internal circuit
100
4. 4
23. DATA VALID
24. RUN
IN
IN
25. COMMON
Transistor Output Boards
26. REQUEST
OUT
30. RESET
OUT
240 Ω
240 Ω
31. POLARITY
(Polarity: +, −)
COM
(0 V)
24 VDC
+24 V
DC power supply
0V
Panel
indicators
240 Ω
Internal circuit
240 Ω
Internal circuit
+5 V
Frequency/Rate Meter
K3NR
K-139
Example of Connection to Display Unit
K3NR
1.COMMON
2.1
3.2
100
4.4
5.8
23.DATA VALID
24.RUN
101
102
25.COMMON
26.REQUEST
+5V
Connected
240 Ω
240 Ω
240 Ω
31.POLARITY
(Polarity: +, −)
V
O
D
C
B
A
DP
LE
V
O
D
C
B
A
DP
LE
V
O
D
C
B
A
DP
LE
V
O
30.RESET
240 Ω
8
8
8
M7E-01D@N2 or M7E-01H@N2
M7E Digital Display Unit
K-140
Frequency/Rate Meter K3NR
SEC
Nomenclature
1. SV Display
7. Status Indicators
2. PV Display
3. Comparative Output
Status Indicators
4. SV Display Status
8. Teaching Indicator
5. ESC Key
9. RESET/TEACH Key
6. Mode Key
10. Up Key and Shift Key
Name
Functions
1. SV display
Displays the set value or parameter. Available for Set Value LED Models only.
2. PV display
Displays the process value in addition to the max./min. value or parameter.
3. Comparative output
status indicators
Displays the status of comparative output.
4. SV display status
Indicates which comparative set value is currently on the SV display.
5. ESC Key
Used to return to the RUN mode from the Setting, Protect, or Maintenance mode.
The process value, maximum value, or minimum value to be displayed can be selected.
6. Mode Key
Used to enter the Setting mode.
Used to allow the PV display to indicate set values sequentially. Available for Basic Models only.
Used to indicate set values sequentially on the SV display. Available for Set Value LED Models only.
7. Status indicators
HOLD:
MAX:
MIN:
PROG:
8. Teaching indicator
Lit when the teaching function is enabled and flashes when the K3NR is in teaching operation.
9. RESET/TEACH Key
The maximum value, minimum value, and counting values are reset by pressing this key.
Teaching is available when the teaching function is enabled.
10. Up Key and Shift Key
The digit being set is scrolled by pressing the Shift Key. The set value increases by one whenever the Up Key is
pressed.
Panel
indicators
Lit when HOLD input is ON.
Lit when the maximum value is indicated on the PV display.
Lit when the minimum value is indicated on the PV display.
Lit or flashes while parameters are being set.
Frequency/Rate Meter
K3NR
K-141
Engineering Data
Max. current (mA)
Derating Curve for Sensor Power Supply
Note: The derating curve shown is for standard installation.
The derating curve depends on the mounting direction.
Ambient temperature (°C)
K-142
Frequency/Rate Meter K3NR
Dimensions
Note: All units are in millimeters unless otherwise indicated.
PV Display
14.2
8.2
Panel Cutouts
45+0.8
−0
92+0.8
−0
75 min.
Note: The K3NR uses M3.5 terminals.
A terminal cover is provided.
Panel
indicators
120 min.
Frequency/Rate Meter
K3NR
K-143
Precautions
!WARNING
Do not touch any of the terminals while the power is being supplied. Doing so may result in electric shock.
!Caution
Do not allow metal objects or conductive wire cuttings to enter the
product. Doing so may result in electric shock, fire, or malfunction.
!Caution
Do not attempt to take the product apart or touch any internal parts
while the power is being supplied. Doing so may result in electric
shock.
!Caution
Do not use the product in locations subject to flammable or explosive gases. Doing so may result in explosion.
!Caution
The lifetime of output relays varies greatly with the switching capacity and conditions. Consider the actual operating conditions,
and use the relays within the rated load without exceeding the
number of operations specified as the rated electrical life. Using
relays beyond their rated electrical life may result in contact deposit or burning.
!Caution
Do not use loads exceeding the rated value. Doing so may result
in damage or burning.
!Caution
Use a power supply voltage within the specified range. Not doing
so may result in damage or burning.
!Caution
Use settings that are appropriate for the control system. Discrepancies between the settings and the actual control conditions may
result in unexpected operation leading to damage or accidents.
!Caution
Be sure to tighten terminal screws to the specified torque.
Specified torque for M3.5 screws: 0.74 to 0.90 N·m
Loose screws may result in burning or malfunction.
■ Application Precautions
• Use a power supply voltage within the specified range. Not doing
so may result in damage or burning.
• Be sure to perform wiring correctly, verifying the terminal names.
Incorrect wiring may result in burning.
• Be sure to tighten the screws on the terminal block properly.
• Do not connect anything to unused terminals.
■ Correct Use
Long-term Use
Use all products within the specified ranges. When using inside a
control panel, ensure that the temperature around the product, rather
than the temperature around the control panel, does not exceed the
specified temperature range. Electronic products, such as this product, have a lifetime that is dependent on the lifetime of internal electronic components, as opposed to the lifetime related to the number
of relay switching operations. The lifetime of these components varies with the temperature; the higher the temperature, the shorter the
lifetime. Therefore, the product lifetime can be extended by lowering
the internal temperature of the product.
When several Frequency/Rate Meters are mounted close together
(either horizontally or vertically), the internal temperature of the Frequency/Rate Meters may rise, leading to a reduction in the lifetime. In
this case, take measures to cool the Frequency/Rate Meters, such as
installing fans. Ensure, however, that the terminals are not cooled as
this may lead to incorrect measurement.
Operating Environment
Do not use the product in locations subject to temperatures or humidity levels above the specified ranges, or in locations subject to condensation.
Do not use the product in locations subject to severe shocks or vibrations.
Separate the product from machines that generate high-frequency
noise, such as high-frequency welding machines and high-frequency
sewing machines.
Do not use the product in locations subject to dust or corrosive
gases.
Do not use the product outdoors or in locations subject to direct sunlight.
Operation
When using models with comparative outputs, if an error occurs at
the Frequency/Rate Meter, comparative output may not operate correctly. We therefore recommend that you consider providing an alarm
system separately as a countermeasure.
Parameter settings that allow the functions to operate properly are
made, using the setting menu, at the factory prior to delivery. When
using the product, change the settings as required for the application.
Mounting
Recommended panel thickness is 1 to 3.2 mm.
Panel
K-144
Frequency/Rate Meter K3NR
Attach the mounting bracket on the left and right sides of the Frequency/Rate Meter as shown in the illustration above and gradually
tighten each screw evenly in turn by considering the balance of the
tightening force until the ratchets start slipping without being further
tightened.
Unit Label (Provided)
No product is shipped with the unit label attached. Select a unit label
from the sheet provided and attach it to the Frequency/Rate Meter.
Mount the Frequency/Rate Meter as horizontally as possible.
Waterproof Specifications
Products for which the degree of protection is not specified or models
with IP@0 degree of protection do not have waterproof specifications.
Noise Countermeasures
Separate the product as far as possible from machines that generate
high-frequency noise, such as high-frequency welding machines and
high-frequency sewing machines, and machines that generate
surges.
Attach surge absorbers or noise filters to noise-generating peripheral
devices (in particular, devices with inductance such as motors, transformers, solenoids, and magnet coils).
Signal
input
+
−
K3NR
K3NR
Power input
Power input
Line filter
Surge absorber
In order to prevent inductive noise, wire the lines connected to the
terminal block separately from power lines carrying high voltages or
large currents. Also, do not wire in parallel to, or in the same cable as
power lines. There are other methods that are effective for reducing
noise, such as running wires along ducts and using shield lines.
When using a noise filter for the power supply, check the voltage and
current and install as close to the Frequency/Rate Meter as possible.
Inductive Noise Countermeasure for Input
Line
Analog Input
+
Signal
input
Processor
−
Two-conductor shield wire
Temperature Input
Panel
indicators
In order to prevent the influence of induction, separate the lead wire
joining the temperature sensor and the Frequency/Rate Meter from
power and load lines.
Using the product near radios, television sets, or other wireless
devices may result in reception interference.
Frequency/Rate Meter
K3NR
K-145
Operating Procedures
■ Operation in RUN Mode
Reset (Enabled in operating mode 7
only.)
Bank Selection
BANK1
The incremental display value can be reset using key operations.
BANK2
Display value
COM
• Switch between the comparative set values and the prescaling values for banks 1 to 4 using the BANK 1 and BANK 2 signals.
• The relationship between the BANK 1 and BANK 2 signals and the
bank numbers is shown in the following table.
Incremental value
Incremental value after reset
Bank
number
Reset input
RESET
during incremental display to
• Press the RESET/TEACH Key /TEACH
reset the incremental value and continue incremental counting
operation.
RESET
is not possible if reset of
• Reset using the RESET/TEACH Key /TEACH
counting values was prohibited in Protect Mode.
BANK 1
BANK 2
1
OFF
OFF
2
ON
OFF
3
OFF
ON
4
ON
ON
Comparat Prescaling
ive set
value
value
sU1.**
sU1.
sU2.**
sU2.
ps1.**
ps1.
ps2.**
ps2.
sU3.**
sU3.
sU4.**
sU4.
ps3.**
ps3.
ps4.**
ps4.
Checking the Bank Number
Note: If the prescale value bank is set to OFF, then the prescaling value for each bank is fixed.
Press the Shift Key
for 1 s min. during measurement to display
the bank number in the PV display. (The display will return to the
measurement value if there is no key operation for 5 seconds.)
Confirming Maximum and Minimum
Values
Press the ESC Key
during measurement to display the maximum and minimum values.
Maximum
value
Measurement
value
Minimum
value
RESET
Press the RESET/TEACH Key /TEACH
while the maximum or minimum
value is displayed to reset the value. (This is not possible, however, if
maximum/minimum value reset was prohibited in Protect Mode.)
Confirming and Setting Comparative Set Values
When the measurement value, the maximum value, or the minimum value is displayed, press the Mode Key
repeatedly to display the comparative set values in the order HH, H, L, and LL. (With models that have an SV display, the comparative set values are displayed in the SV display.)
Measurement value
Maximum value
Minimum value
Comparative
set value HH
Comparative
set value H
No key operation for 5 s
Comparative
set value L
No key operation for 5 s
Note: When a comparative set value is displayed, it can be changed using the Up Key
K-146
Frequency/Rate Meter K3NR
Comparative
set value LL
No key operation for 5 s
and Shift Key
No key operation for 5 s
(if key protection is OFF).
■ Setting Procedures
The K3NR has four modes: RUN mode for normal operations, Setting mode for initial parameter input, Protect mode for lock-out configuration, and
Maintenance mode for initializing set values. The parameters that are accessible on any individual K3NR will vary depending on the Output Board
installed. Refer to the K3NR Operation Manual for details.
RUN Mode:
Remains in this mode under normal operation.
The process value or the max./min. value can be monitored.
Using the front panel keys, the comparative set value can be changed and max./min. value and counting value reset can
be performed.
Setting Mode:
Used for making initial settings.
Includes settings for four menus (Set value (sUset
sUset),
pscl),
setup),
opt))
sUset prescaling (pscl
pscl setup (setup
setup option (opt
opt and the output test.
Protect Mode:
Used for locking the front key operation or parameter changes.
Maintenance Mode:
Used for initializing set values.
When power is ON
+
Power ON
Maintenance mode
ESC
RUN mode
ESC
+
1s
1s
ESC
ESC
Protect mode
Setting mode
s.bank Select bank no. of set values
sU*.hh
sU .hh Enter set value HH of bank 1
sU*.
sU . h Enter set value H of bank 1
sU*.
sU . l Enter set value L of bank 1
sU*.
sU . ll Enter set value LL of bank 1
Note: The above is an example when the bank number is set to 1.
prot - Program lock-out configuration
all
sUset
reset
mm.rst
secr
pscl - Display prescaling
p.bank Select bank no. of prescale values
ps*.ax
ps .ax Set the mantissa (X) of the prescale value of input A
ps*.ay
ps .ay Set the exponent (Y) of the prescale value of input A
ps*.bx
ps .bx Set the mantissa (X) of the prescale value of input B
ps*.by
ps .by Set the exponent (Y) of the prescale value of input B
Select decimal point
decp.*
decp.
Note: The above is an example when the bank number is set to 1.
setup - Program operating mode/input sensor/serial communications
Specify operating mode
func
Select a sensor type of input A
ina
Select a sensor type of input B
inb
=ro.ax Set the mantissa (X) of the auto zero time of input A
=ro.ay Set the exponent (Y) of the auto zero time of input A
=ro.bx Set the mantissa (X) of the auto zero time of input B
=ro.by Set the exponent (Y) of the auto zero time of input B
opt - Supplementary settings related to display or control
Set the process time for averaging measured value
aUg
stime Set startup compensation time
Select power failure memory function
memo
Enter hysteresis value
hys
c-out Select the output pattern
lset.h Enter the upper limit (H) of linear output range
lset.l Enter the lower limit (L) of linear output range
Select the remote/local programming
r-l
time
u-no
bps
len
sbit
prty
Enable all key protection
Enable set value change prohibition
Enable prohibition of counting value reset using the front
panel keys
Enable prohibition of max./min. value reset using the
front panel keys
Specify the menus to be protected against setting in the
setting mode
Select the display time unit
Enter the unit no. for the host
Select the baud rate
Select the word bit length
Select the stop bits
Select the parity bits
Panel
indicators
sUset - Program set values
test - Generating simulated input for testing the output function
Frequency/Rate Meter
K3NR
K-147
■ Initial Settings
■ Parameters
Power ON
Press the Mode Key
Mode.
Power ON
for 1 s min. to move to the Setting
Press the ESC Key
for 1 s.
RUN Mode
and Up Key
Refer to Operation in RUN Mode.
Select the setup menu (
) with the Mode Key
and set the operating mode, the input type, and other
settings.
Setting Mode
If required, set a prescale value in the prescaling menu
(
).
1s
Set value menu
Set comparative set values in the set value menu (
).
1s
Comparative set
value bank
Make settings in the option menu (
−
No key operation for 5 s
) as required.
(See note 4.)
Comparative
set value HH
−
No key operation for 5 s
(See note 4.)
If necessary, generate simulated input for testing the output
function in output test (
).
Comparative
set value H
−
No key operation for 5 s
After completing all the settings, press the ESC Key
return to RUN Mode.
to
(See note 4.)
Output test
Comparative
set value L
−
No key operation for 5 s
(See note 4.)
Comparative
set value LL
Measurement starts.
−
No key operation for 5 s
Prescaling
To display rotational speeds, circumferential speeds, or other
values based on input pulse calculations, the rotational speed
must be multiplied by a factor input before the input pulses are
measured. This factor is called
a prescale value.
K3NR
Proximity Sensor
Rotation speed (rpm) = f × 60 × a
Where,
f: Input pulse frequency (p/s)
a: Prescale value
If there are 5 pulses per rotation, then an accurate rotation
speed can be calculated if a = 1/5 (= 0.2 = 2 × 10-1).
In actual application, input as follows:
Mantissa X = 2.0000
Exponent Y = 10-1
Auto-zero Time (Set before use.)
In operation modes 1 to 6, the time to force-zero the frequency if
no pulse is received for a specified period can be set. This time
is called the auto-zero time. Set the auto-zero time to a value
that is somewhat longer than the longest input pulse interval. (If
the time setting is too long or if the factory-set value is used, the
display may not return to zero even if no input pulse is
received.)
Time Unit Setting
Setting
Selecting the Sensor Type
Meaning
Minutes
No-contact or
voltage pulse
input
Minutes and seconds
Contact input
Hours, minutes, and seconds
Note: The time unit can be set
only if operating mode 6
(passing time) is
selected.
K-148
1s
Process time for averaging
measured value
No key operation for 5 s
Startup
compensation time
Note: If there are large
discrepancies in the
display select or .
Note, however, that the
maximum counting
frequency is 30 Hz.
Frequency/Rate Meter K3NR
−
No key operation for 5 s
Power failure memory
No key operation for 5 s
Hysteresis
−
No key operation for 5 s
Output pattern
No key operation for 5 s
Upper limit (H) of
linear output range
−
No key operation for 5 s
Lower limit (L) of
linear output range
NO: Voltage NC: Voltage
pulse H
pulse L
Set in the prescaling menu
Seconds
Option menu
−
No key operation for 5 s
Remote/local programming
No key operation for 5 s
Changing Set Values
By pressing the Shift Key
while a parameter is displayed, the set value can be
changed (setting status). The PROG status indicator will flash. Change the set
value as required, and press the Mode Key
to register the setting and move to
the next parameter.
Setting Status
func
Protect Mode
f1
Change the set value
using the Up Key
and
the Shift Key
.
PROG flashes.
If there is no key operation for
Next parameter 5 seconds, the setting is
registered and the parameter
is displayed again.
Setup menu
Prescaling menu
1s
1s
Prescale value
bank (See note 1.)
−
No key operation for 5 s
No key operation for 5 s
(See note 4.)
−
Operating mode
Input A
sensor type
Input A prescale
value mantissa
−
−
No key operation for 5 s
No key operation for 5 s
Input B sensor
type (See note 2.)
(See note 4.)
No key operation for 5 s
Input A prescale
value exponent
−
−
Input A auto-zero
time mantissa
No key operation for 5 s
(See note 4.)
Input B prescale value
mantissa (See note 2.)
(See note 4.)
−
No key operation for 5 s
−
−
Input A auto-zero
time exponent
No key operation for 5 s
Input B prescale value
exponent (See note 2.)
−
−
No key operation for 5 s
Input B auto-zero
time mantissa
(See note 2.)
−
No key operation for 5 s
−
Decimal point
−
No key operation for 5 s
Input B auto-zero
time exponent
(See note 2.)
−
No key operation for 5 s
No key operation for 5 s
Time unit
(See note 3.)
No key operation for 5 s
Communications
unit number
−
No key operation for 5 s
Note 1: Set a number in the range 2 to 4 to set more than one prescale value
(i.e., to display measurements in more than one unit).
2: These parameters will be displayed if F2, F3, F4, or F5 (i.e., operating
mode 2, 3, 4, or 5) is set.
3: This parameter is displayed if F6 (i.e., operating mode 6) is set. If a
parameter other than 5cal is set, the prescaling menu ( p5cl ) will not be
displayed.
Baud rate
1200/2400/4800/
9600 /19200/38400bps
No key operation for 5 s
Word bit length
7 /8bit
No key operation for 5 s
Stop bits
1/ 2 bit
No key operation for 5 s
Parity bits
/
/
Panel
indicators
• In the Setting Mode, measurement stops and all outputs turn
OFF.
• Depending on the output type of the model used, some parameters (indicated in
) are not displayed (and hence cannot be set).
• If the operating mode is changed, the prescale values and linear output range parameters will be reset to their initial values.
Set the operating mode first.
4. A number in the range 1 to 4 will be displayed.
Settings displayed in reverse colors are defaults.
Frequency/Rate Meter
K3NR
K-149
Power ON
• Measurement stops in Protect Mode.
• Depending on the output type of the model used, some parameters (indicated in
displayed (and hence cannot be set).
RUN Mode
) are not
Press the ESC Key
and Up Key
for 1 s.
Protect Mode
Protect menu
All key protection
prot
Set value change
prohibition
Reset prohibition
sUset
reset
all
Maximum/minimum
value reset prohibition
mm.rst
Menus protected
in Setting Mode
secr
1s
(See
note.)
Key-protection ON: kpon
Key-protection OFF: kpoff
Menu display
Parameter display
all
prot
Press the Mode Key
to display the parameter.
Setting:
Next parameter:
sUset
Setting:
Next parameter:
reset
Press the ESC Key
to return to the menu.
Setting:
Next parameter:
mm.rst
Setting:
Next parameter:
secr
Note: Press the Shift Key
to make it
possible to set or change parameters.
Displayed only for
models with
comparative outputs.
Setting:
Next parameter:
Meaning of parameter
Setting range
All key protection:
All key operations are prohibited in
RUN Mode. (If all key protection is
ON, only the key for going to Protect
Mode is enabled.)
Use the Up Key
to
change the setting.
➤
kpon
➤
kpoff
Use the Mode Key
Set value change prohibition:
to enable the setting and move to the
Changes to comparative set values
next parameter.
are prohibited in RUN Mode. (Displayed only for models with comparative outputs.)
kpon
Key protection ON:
Reset prohibition:
Key protection OFF: kpoff
Resetting using the front panel keys is
prohibited. (Resetting by external signals is not prohibited.)
Maximum/minimum value reset prohibition:
Resetting of maximum and minimum
values using the front panel keys is
prohibited. (Resetting by external signals is not prohibited.)
Use the Up Key
to
change the setting.
Menus protected in Setting Mode:
Setting operations in Setting Mode
are prohibited in the way shown below.
Setting menu
0
1
Option menu
2
×
×
Prescaling menu
Setup menu
×
×
×
Note: If there is no key operation for 5 seconds, the setting is automatically registered.
Frequency/Rate Meter K3NR
➤
Setting
Set value menu
K-150
Setting key
(See note.)
0 /1/2
0
➤
1
➤
2
Use the Mode Key
to enable the setting and move to the
next parameter.
■ Troubleshooting
When an error occurs, error details will be displayed in the PV display. Take the appropriate countermeasures according to the error displayed.
Error display
Error contents
Output status
Comparative
output
BCD output
Countermeasure
Communications
output
Linear
output
m1.err (M1.ERR) Memory error
m2.err (M2.ERR)
OFF
OFF (all outputs
in "H" status)
OFF
OFF
Reset the power. If the same error
occurs, repair is necessary.
m3.err (M3.ERR)
OFF
OFF (all outputs
in "H" status)
OFF
OFF
Reset the power while holding
down the ESC Key, the Up Key, and
the RESET/TEACH Key. The settings will be returned to their initial
values. Redo the settings. If the
same error occurs, repair is necessary.
OFF
OFF (all outputs
in "H" status)
OFF
OFF
(minimum
value)
Reset the power. If the same error
occurs, repair is necessary. If normal operation is restored, it is possible that the original error was
caused by the influence of noise.
Check that there are no sources of
noise in the vicinity.
Continues
Continues
Continues
The OVER signal The OVER or UNturns ON.
DER signal turns
ON.
Take steps to ensure that the input
values and display values are within the allowable ranges.
Continues
If an attempt to change a setting
using key operations is made with
the remote/local selection set to remote, this error will flash for 3 s. To
enable settings to be changed, set
the remote/local selection to local.
Output error
(Display value
flashes.)
The input range and Continues
display range were
exceeded.
The remote/local
rmt (RMT)
(Flashes for 3 s.) section is set to remote.
Continues
Continues
Continues
Panel
indicators
err-o (ERR-O)
chg-o (CHG-O)
Frequency/Rate Meter
K3NR
K-151
Additional Information
■ Output Operation Timing in RUN Mode (Relay or Transistor Outputs)
The following timing chart is for a 5-comparative Output Board when the standard output pattern is selected.
For Operating Mode 1 to 6
Display
Display value
HH set value
HYS
H set value
HYS
HYS
L set value
LL set value
Hysteresis
HYS
HH comparative output
H comparative output
PASS output
L comparative output
LL comparative output
Note: The hysteresis is set in setting mode and the hysteresis value will be applied to all set values.
For Operating Mode 7
INA input
RESET
Display
HH set value
Display value
H set value
L set value
LL set value
HH comparative output
H comparative output
PASS output
L comparative output
LL comparative output
Note: Comparative output L or LL turns ON when the measured value exceeds the set value.
K-152
Frequency/Rate Meter K3NR
■ Operating Modes
The K3NR provides 7 operating modes for converting input pulses to display values. The mode can be selected via key operations on the front
panel.
Basically, the operating modes can be divided into the following two groups.
Operating Modes 1 to 6
Operating Mode 7
Rotational speed and other displays are based on calculations for
continuous pulses (frequency).
The number of pulses is measured. Each pulse is counted as 1 count
up to a maximum of 99,999 counts. Decrementing the count is not
possible. Although the limits of the display enables displaying only up
to 99,999 counts, prescaling can be used to count up to
4 gigacounts.
Example
Processing
Operating mode no.
Conveyor line
Use
Pulse counting
07
The count is reset by shorting terminals 6 and 7 (RESET ON) or by
pressing the RESET/TEACH Key on the front panel
Operating mode no.
Because only incrementing is possible, the L and LL comparative
outputs turn ON when the measured values exceed set values.
Use
01
Rotational/Circumferential speed
02
Absolute ratio
03
Error ratio
04
Rotation difference
05
Flow rate ratio
06
Passing time
Mode No. 1:
Rotational or circumferential speed display for 1
input
Mode No. 2 to 5: Display of calculations for two rotational speeds
Mode No. 6:
Passing time display based on 1 input frequency
and processing length
Basic Principles of Rotational Speed Displays
The ON/OFF time (T) of a sensor input or other input is measured
with the internal system clock to automatically calculate the frequency. This frequency is multiplied by 60 and displayed as a rotational speed.
Input sensor pulse ON/OFF time (T) =
Frequency (f) = 1/T
T
Rotational speed (rpm) = f x 60
Circumferential speed = Circumference x Rotational speed
Passing time = Processing length/Circumferential speed
Automatic measuring by the K3NR is enabled simply by providing an
input pulse.
Operating Mode 1: Rotational/Circumferential Speed
Units: rpm; rps; rph; Hz; kHz; mm/s; m/s; m/min; km/h; l/min; l/h;
etc.
Application Example
Measuring Roller
Winding Speed
Measuring Motor Speed
(for Product Testing)
H
PASS
L
Pass/fail
determination
Frequency/Rate Meter
K3NR
K-153
Panel
indicators
The frequency of input A is calculated and displayed as a rotational
or circumferential speed.
Operating Mode 2: Absolute Ratio
Input B is divided by input A (B/A) and then multiplied by 100 for display as a percentage.
Unit:
Application Example
Measuring Ratio between Rotational Speed of Two Rollers
%
Alarm
HH
H
PASS
L
LL
Operating Mode 3: Error Ratio
The error between input A and input B (B/A − 1) is multiplied by 100
for display as a percentage.
Unit:
Application Example
Measuring Difference between Two Line Speeds
(Two Conveyors)
%
Communication
output (remote
monitoring)
To computer
Operating Mode 4: Rotational Difference
The difference between input B and input A (B − A) is displayed as a
rotational speed error or circumferential speed error.
Application Example
Units: rpm; rps; rph; Hz; kHz; mm/s; m/s; m/min; km/h; l/min; l/h;
etc.
Measuring the Absolute Difference between the Speeds of
Two Conveyors
Alarm
HH
H
PASS
L
LL
Operating Mode 5: Flow Rate Ratio
Input A and input B are used to find the concentration (B/(A+B)) as a
percentage.
Unit:
Application Example
Monitoring the Concentration of a Liquid Mixture
%
Linear output
Recorder
K-154
Frequency/Rate Meter K3NR
Operating Mode 6: Passing Time
The pulse frequency of input A is calculated and is displayed as the
passing time for a preset distance.
Application Example
Passing Time for a Conveyor Line
Units: s; min; h, min, s; min, s, 1/10 s; etc.
The passing time measurement operation in operating mode 6 is
ideal for measuring time corresponding to a frequency change. Operating mode 6 allows the real-time, continuous time measurement of
the revolutions of any rotating object without recovery time.
Distance
Alarm output
Operating Mode 7: Pulse Counting
Application Example
The total number of pulses on input A is displayed.
1 2 3 4
5 6 7 8 9 10
1 2 3 4 5
Counting Workpieces
Input A
Input B
BCD
Hold input
To PC
Reset input
0 1 2 3 4
5
Units: count; mm; cm; m; l; kl; etc.
6
10
0 1 2 3 4 5
Note: The operation of comparative outputs in operating mode 7 is
different to that in other modes. Because only incrementing is
possible, the L and LL comparative outputs turn ON when the
measured values exceed set values.
Panel
indicators
Display
Frequency/Rate Meter
K3NR
K-155
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. N087-E1-02
K-156
In the interest of product improvement, specifications are subject to change without notice.
Frequency/Rate Meter K3NR