XP Power DSL240 Ultra slim design Datasheet

ACDC
240 Watts
xppower.com
DSL240 Series
•
Ultra Slim Design
•
150% Peak Load for 3 seconds
•
Full Power from 40 °C to +60°C
•
High Efficiency – Up to 93%
•
Hazardous Locations Approval
•
Parallel Capability
•
3 Year Warranty
Specification
Input
General
88-264 VAC (120-375 VDC)
47-63 Hz
2.3 A at 115 VAC, 1.15 A at 230 VAC
24/48 A max at 115/230 VAC
0.97 typical at 230 VAC
Conforms to EN61000-3-2 Class A.
Earth Leakage Current • 3.5 mA maximum
Input Protection
• Internal fuse in line, T5.0 A/250 VAC
Input Voltage
Input Frequency
Input Current
Inrush Current
Power Factor
•
•
•
•
•
Efficiency
Isolation
Switching Frequency
DC OK Signal
Output LED
Output
Output Voltage
Output Voltage Trim
Initial Set Accuracy
Minimum Load
Start Up Delay
Start Up Rise Time
Hold Up Time
Line Regulation
Load Regulation
Transient Response
•
•
•
•
•
•
•
•
•
•
Ripple & Noise
•
Overvoltage Protection •
Overload Protection
•
Short Circuit Protection •
Temperature
Coefficient
Thermal Protection
Parallel Operation
Maximum Capacitive
Load
•
See table
See table
+1% at 100% load
No minimum load required
1.0 s max
150 ms max
25 ms minimum at full load and 115 VAC
±1%
±1% (±5% in parallel mode)
10% maximum deviation, recovering to
less than 1% within 2 ms for 50% step
load change at 0.2 A/µs
100 mV pk-pk maximum, measured with
20 MHz bandwidth
12 V output: 15-16.5 V,
24 V output: 30-33 V
120-150% of rated current
(see application note)
Trip and restart (hiccup mode)
auto recovery within 7 s
±0.03%/°C
• 110°C max, measured on internal heatsink
auto recovery
• A maximum of 3 units can be paralleled.
Max power available is 90% of total rated
power. Minimum load of 10% required per
unit
• 7000 µF (start up delay increases to 1.5s
and rise time to 500 ms)
MTBF
• See table
• 3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
• 100 kHz typical PFC & main converter at
230 VAC and full load
• Volt free contacts rated at 60 VDC/ 0.3 A
on 24 V versions only
• Green LED to indicate output on. Red LED
to indicate low output voltage. See
mechanical details for operating range.
• >370 kHrs to BELLCORE Issue 6 at 40 °C,
GB
Environmental
Operating Temperature
Cooling
Operating Humidity
Protection
Storage Temperature
Operating Altitude
Shock
Vibration
•
•
•
•
•
•
•
-40 °C to +70 °C (see derating curves)
Natural convection
20-95% RH, non-condensing
IP20
-40 °C to +85 °C
4850 m
IEC68-2-27, 4 g, 22 ms half sine, 3 times
in each of 6 axes
• IEC68-2-6, 10-500 Hz, 2 g 10 mins/sweep.
60 mins for each of 3 axes
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
•
•
•
•
Radiated Immunity
EFT/Burst
Surge
•
•
•
Conducted Immunity
Magnetic Field
Dips & Interruptions
•
•
•
Safety Approvals
•
EN55022, class B conducted & radiated
EN61000-3-2, class A
EN61000-3-3
EN61000-4-2, 8 KV Contact,
15 KV Air Discharge, Perf Criteria A
EN61000-4-3, 10 V/m Perf Criteria A
EN61000-4-4, level 4 Perf Criteria A
EN61000-4-5, Installation Class 4
Perf Criteria A
EN61000-4-6, 10 V Perf Criteria A
EN61000-4-8, level 4, Perf Criteria A
EN55024, 30% 10 ms, 60% 100 ms,
100% 5000 ms Perf Criteria A, B, B
UL508, UL60950-1, EN60950-1, ANSI/ISA
12.12.01 (Class I, Division 2, Groups A, B,
C and D)
Output Voltage
12 V
24 V
Output Power
192 W
240 W
Output Voltage Trim(4)
11.75-14.5 V
22.5-28.5 V
Output Current
16.0 A
10.0 A
Peak Load(3)
24.0 A
15.0 A
Typical Efficiency(2)
90%
93%
Model Number(1)
DSL240PS12-I
DSL240PS24-I
Notes
1. Add suffix ‘D’ for detachable connector option e.g. DSL240PS24-ID.
2. Typical efficiency at 230 VAC and full load.
3. Peak load is for a maximum of 3 s with 20% duty cycle. Average power is not
to exceed nominal output power.
4. Output current should be limited so that nominal output power is
not exceeded.
Mechanical Details
The green LED is lit if the output voltage is OK (10-11.2 VDC for 12 V units, 17.6-19.4 VDC for 24 V units at start up)
The red LED is lit if the output voltage is low (10-11.2 VDC for 12 V units, 17.6-19.4 VDC for 24 V units after start up)
6
6
4.59 (116.6)
1
0.3
(7.0)
1
Pin Connections
Conn
AC
Input
5.65
(143.5)
4.9
(124.50)
DC
Output
1
Pin
Designation
1
Ground
2
Neutral
3
Line
1
DC OK*
2
DC OK*
3
Positive
4
Positive
5
Negative
6
Negative
3
1
2.52 (64.0)
* 24 V models only.
3
‘-D’ version (detachable connectors)
Notes
1. All dimensions in inches (mm)
2. Weight: 1.916 lbs (860g)
3. Tolerance: ±0.02 in (±0.5 mm)
4. Screw terminal: 10-24 AWG cables size. Detachable connector version: 14-24 AWG cable size.
5. Connection screw maximum torque: Input: 9lbs-in (1.0 Nm), Output: 5.5 lbs-in (0.6 Nm).
Application Notes
Derating Curves
DC OK
100
DCOK
Load (%)
80
Open = Output fail
Closed = Output good
60
40
DCOK
20
0
-40
-20
0
10
20
30
40
50
60
Contact Rating: 0.3 A at 60 VDC
500 VDC isolation
70
Ambient Temp (˚C)
Peak Loading
258 W for 12 V
360 W for 24 V
Peak
3 sec
3 sec
Auto recovery within 7 sec
198 W for 12 V
240W for 24 V
Continuous
OCP
OCP
< 7 sec
< 7 sec
04-Jan-13
ACDC
DSL240
Models and Ratings