500 Series Multiple Input and Output Modules System Sensor multiple input and output modules are designed to meet a range of applications in which numerous single modules are used. Features • Removable 12 to 18 AWG plug-in terminal blocks • Individual LED indicators • Unused addresses may be disabled • Rotary address switches • Class A or B operation • Mount up to two modules in BB-2 enclosure (optional) • Mount up to six modules in BB-6 enclosure with CH-6 chassis (optional) • Mounting hardware included The design of the System Sensor 500 Series multiple input and output modules allows for installation ease and time savings The monitor and control modules can be used to supervise and activate sounders, strobes, door closers, pull stations, waterflow switches, conventional smoke detectors and more. The conventional zone interface module is ideal for retrofit applications to monitor zones of conventional two-wire detectors. Each module has its own address. Modules are addressed with easy-to-use rotary code switches. Provisions are included for disabling unused addresses. Up to two modules mount in a BB-2 enclosure with built-in chassis and up to six modules mount in a BB-6 enclosure with the CH-6 chassis. Wiring terminals are easily accessible for trouble-shooting purposes. CR-6 SIX RELAY CONTROL MODULE The CR-6 Six Relay Control module consists of six Form-C relays. The first address is set from 01 to 94, while the remaining modules are automatically assigned to the next five higher addresses. Provisions are included for disabling a maximum of three unused addresses. A single isolated set of dry relay contacts is provided for each module address which is capable of being wired for either a normally open or normally closed operation. The module allows the control panel to switch these contacts on command. No supervision is provided for the controlled circuit. SC-6 SIX SUPERVISED CONTROL MODULE The SC-6 Six Supervised Control module provides supervised monitoring of wiring to load devices that require an external power supply or amplifier to operate, such as horns, strobes, speakers or bells. Upon command from the control panel, the SC-6 will disconnect the supervision and connect the external power supply across the load device. The first module is addressed from 01 to 94, while the remaining modules are assigned to the next five higher addresses. Provisions are included for disabling a maximum of three unused modules. Each module has terminals for connection to an external supply circuit for powering devices on its notification appliance circuit. One or multiple power supplies or amplifiers may be used. There is a short circuit protection monitor for each module. This is provided to protect the external power supply against short circuit conditions on the NAC. When an alarm condition occurs, the relay which connects the external continued continued supply to the NAC will not be allowed to close if a short circuit condition currently exists on the NAC. In addition, an algorithm is incorporated to find a short when the module is active. The module will close all circuits that are not shorted to find the NAC with the problem. SYNC-1 ACCESSORY CARD The SYNC-1 is an optional accessory to the SC-6 and is designed to provide a means of synchronizing a series of horns, strobes, and horn/strobes. The SYNC-1 is able to synchronize the temporal-coded horns, the one second flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving the strobes active. Each SYNC-1 accessory card has the capability of synchronizing six Class B circuits or three Class A circuits. CZ-6 SIX ZONE INTERFACE MODULE The CZ-6 Six Zone Interface module provides an interface between the intelligent alarm system and a two-wire conventional detection zone. A common SLC input is used for all modules, and the initiating device circuits share a common external supply. Otherwise, each module operates independently from the others. The first module is addressed from 01 to 94 while the remaining modules are assigned to the next five higher addresses. Provisions are included for disabling a maximum of two unused modules. All two-wire detectors being monitored must be two-wire compatibility listed with the modules. The CZ-6 transmits the status of a zone of two-wire detectors to the fire alarm control panel. Status conditions are reported as normal, open or alarm. The interface module supervises the zone of detectors and the connection of the external power supply. IM-10 TEN INPUT MONITOR MODULE The IM-10 Ten Input Monitor module provides an interface between a control panel and normally open contact devices such as pull stations, security contacts, or flow switches. The first address is set from 01 to 90 and the remaining modules are automatically assigned to the next nine higher addresses. Provisions are included for disabling a maximum of two unused addresses. The supervised state (normal, open or short) of the monitored device is sent back to the panel. 500 Series Module Specifications General Specifications Operating Voltage Maximum SLC Wiring Resistance Temperature Range Relative Humidity Wire Gauge Dimensions Specifications: CR-6 Standby Current Alarm Current 15 to 32 VDC 40 Ohms 32°F to 120°F (0° to 49°C) 10% to 85% noncondensing 12 to 18 AWG 6.8˝H × 5.8˝W × 1.25˝D 1.45 mA maximum 32 mA maximum (assumes all six relays have been switched once and all six LEDs solid on) Maximum IDC Wiring Resistance 40 Ohms Relay Current 30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control Relay Contact Ratings 30 VDC; 70.7 VAC Specifications: CZ-6 Standby Current 2 mA maximum Alarm Current 40 mA maximum (assumes all six LEDs solid on) Maximum IDC Wiring Resistance 25 Ohms External Supply Voltage DC Voltage: 18 to 28 volts power limited Ripple Voltage: 0.1 volts RMS maximum Current: 90 mA per circuit Compatible Detectors Contact System Sensor for a current list Specifications: SC-6 Standby Current 2.25 mA maximum Alarm Current 35 mA maximum (assumes all six relays have been switched once and all six LEDs solid on) Maximum NAC Circuit Wiring 40 Ohms Resistance Power Rating Per Circuit 63 W @ 70.7 VAC Relay Contact Ratings 30 VDC; 110 VAC Specifications: IM-10 Standby Current Alarm Current 3.5 mA maximum 60 mA maximum (assumes all ten LEDs solid on) Maximum IDC Wiring Resistance 40 Ohms Maximum IDC Voltage 12 VDC Maximum IDC Current 1 mA Accessories SYNC-1 Accessory Card BB-6 Enclosure with CH-6 Chassis Specifications: SYNC-1 Operating Voltage Maximum Load on a Loop Standby Current Specifications: BB-2 Enclosure Dimensions Specifications: BB-6 Enclosure Dimensions 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 11 to 30 VDC Class A/Style Z: 3A Class A/Style Y: 3A per pair +0 Position: 15 mA +2 or +4 Position if connected to supply: 2.5 mA 12˝H × 9˝W × 3.67˝D 24˝H × 12.55˝W × 6.47˝D ©2008 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-0344-003 • 1/09 • #2088