DKLP-3
Suppression Chokes
www.schurter.com/pg81_82
Compensated High Inductance Choke, 3-phase
Description
-
Applications
Current compensated choke
3-phase choke
Flexible wire
Flange for mounting onto printed circuit board
Fully potted resign
-
References
Standards
-
Placed in front of frequency converter
Stepper motor drives
UPS-systems
Inverter
General Product Information
EN 60938
IEC 60950
EN 55011/55014
VDE 0871/0875
Weblinks
Approvals, RoHS, CHINA-RoHS, e-Store, Distributor-Stock-Check
Technical Data
Rated voltage
Rated voltage
Rated Current
Rated inductance
Power Operating Frequency
Terminal technic
Weight
Material: Housing
Sealing Compound
up to 540 VAC
up to 760 VDC
8 - 16 A @ Ta 40 °C
4.0 - 50 mH, Tol. -30% +50%
50 - 400 Hz
Flexible wire
145 - 1840 g
UL 94V-0
UL 94V-0
Dimensions
Case 29-3W
50.8
80
150
10...20
65
80
5.8
6.8
230
10...20
65
30.8
48
48
Climatic Category
Allowable Operation Temp.
2.5 kV, 50 Hz, 2 sec, winding to winding
2.5 kV eff., 50 Hz, 2 sec, winding to
ambient
25/100/21 acc. to IEC 60068-1
-25 °C to 100 °C
Case 31-3W
38.2
38.2
Test Voltage
Isolation Voltage
4.3
4.3
EMC Products
DKLP-3
Suppression Chokes
www.schurter.com/pg81_82
Case 33-3W
70
120
230
10...20
8
100
120
100
5.25
Variants
In [A]
Ln [mH]
Rcu
[mΩ]
Tripped Power Dissipation [W]
fRES
[MHz]
Copper ø
[mm]
Weight [g]
Housing
Packing unit [pcs.]
Order Number
3
30
130
3.5
0.13
0.71
145
29-3W
6
DKLP-0329-0330
5
10
48
3.6
0.15
0.9
145
29-3W
6
DKLP-0329-0510
8
4
22
4.2
0.4
1.12
145
29-3W
6
DKLP-0329-0804
3
50
260
7
0.055
0.71
509
31-3W
2
DKLP-0331-0350
4
30
155
7.5
0.075
0.8
512
31-3W
2
DKLP-0331-0430
5
20
100
7.5
0.145
0.9
514
31-3W
2
DKLP-0331-0520
8
40
110
21
0.05
1.12
1726
33-3W
1
DKLP-0333-0840
16
10
30
23
0.14
1.6
1840
33-3W
1
DKLP-0333-1610