Gamewell-FCI M500X Isolator module Datasheet

System Sensor
M500X
Description
Style 7
Isolator Module
The System Sensor M500X Fault Isolator modules enable
part of the communications signaling line circuit to continue operating when a short circuit occurs. The System
Sensor M500X Isolator Module is an automatic switch that
opens when the line voltage drops below four volts. This
module is rigorously designed and tested for electromagnetic compatibility and environmental reliability, in many
cases exceeding industry standards.
When installing Isolator Modules, the modules should be
spaced between groups of sensors or modules in a signaling line circuit to protect the remainder of the signaling line
circuit. If a short occurs between any two isolators, then
both isolators immediately switch to an open circuit state
and isolate the devices between them. The remaining
units on the signaling line circuit continue to operate. No
more than 20 devices are recommended for each group.
An LED indicator flashes in the normal condition and
lights during a short circuit condition. When the short circuit is removed, the module will automatically restore the
entire signaling line circuit.
Specifications
Standby Current:
Operating Temperature
Range:
Humidity Range:
Voltage Range:
Communication Line
Impedance:
Isolation Current:
Fault Detection Delay:
Fault Detection
Threshold:
Line Restoration
Threshold:
Dimensions:
.00045 amps. max.
32° F to 120° F (0° C to 49° C)
10% to 93% non-condensing
15 - 32 VDC
40 Ohms
5 mA max.
250 ms min.
M500X
Features
• Up to 20 addressable devices may be grouped
between isolator modules
• Panel controlled status LED
• Low standby current
• Mounts in standard 4” junction box
• Wiring terminals are easily manageable for
troubleshooting purposes
Ordering Information
Model
Description
M500X
Isolator Module
4 volts
7 volts
4.5” H x 4” W .25” D
11.4 H x 10.2 W x .6 D cm)
Mounts to a 4” square by 2.8”D
(10. 2 x 7.1 cm) deep box)
*Normal operating current. During power failure, current
drops to 0.045 amp, since the back light is extinguished.
E3 Series® and NetSOLO® are registered trademarks of Honeywell International Inc.
S1949
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0677 Rev. A2 page 1 of 1
©2008 Honeywell International Inc. All rights reserved.