AD ADM1034 Thermal monitor and fan speed (rpm) controller Datasheet

Thermal Monitor and
Fan Speed (RPM) Controller
ADM1034
Look-up table for temperature-to-fan-speed control
Linear and discrete options for look-up table
FAN_FAULToutput
THERM input, used to time PROCHOT assertions
REF input, used as reference for THERM (PROCHOT)
3 V to 5.5 V supply
Small 16-lead QSOP package
FEATURES
1 local and 2 remote temperature channels
±1°C accuracy on local and remote channels
Automatic remote temperature channels, up to 1 kΩ
Fast (up to 64 measurements per second)
SMBus 2.0, 1.1, and 1.0 compliant
SMBus address input/LOCATION input to UDID
Programmable over-/undertemperature limits
Programmable fault queue
SMBusALERT output
Fail-safe overtemperature comparator output
Fan speed (RPM) controller
APPLICATIONS
Desktop and notebook PCs
Embedded systems
Telecommunications equipment
LCD projectors
FUNCTIONAL BLOCK DIAGRAM
VCC
6
ADM1034
SMBUS
ADDRESS
SERIAL BUS
INTERFACE
MANUAL FAN
SPEED CONTROL
REGISTERS
ADDRESS
POINTER
REGISTER
TEMPERATURE-TOFAN-SPEED
LOOK-UP TABLE
DRIVE1 1
TACH1 2
TACH2 4
FAN SPEED
CONTROLLER
FAN RESPONSE
TACH SIGNAL
CONDITIONING
THERM
FAULT
QUEUE
15
SDA
8
FAN_FAULT
14
ALERT
7
THERM
LIMIT
COMPARATOR
VALUE AND
LIMIT
REGISTERS
FAN
SPEED
COUNTER
THERM PERCENT
TIMER
FAULT
QUEUE
REF 8
HYSTERESIS
REGISTERS
LOCATION 13
D1–
MASK
REGISTERS
SCL
9
D1+ 10
D2– 11
ANALOG
MULTIPLEXER
ADC
OFFSET
REGISTERS
SRC
BLOCK
CONVERSION
RATE REGISTER
BAND GAP
REFERENCE
D2+ 12
BAND GAP
TEMPERATURE
SENSOR
CONFIGURATION
REGISTERS
5
04918-0-001
DRIVE2
3
ALERT
STATUS
REGISTER
16
GND
Figure 1.
Rev. 0
Information furnished by Analog Devices is believed to be accurate and reliable.
However, no responsibility is assumed by Analog Devices for its use, nor for any
infringements of patents or other rights of third parties that may result from its use.
Specifications subject to change without notice. No license is granted by implication
or otherwise under any patent or patent rights of Analog Devices. Trademarks and
registered trademarks are the property of their respective owners.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.
Tel: 781.329.4700
www.analog.com
Fax: 781.326.8703
© 2004 Analog Devices, Inc. All rights reserved.
ADM1034
TABLE OF CONTENTS
Specifications..................................................................................... 4
ALERT Interrupt Behavior ....................................................... 21
Absolute Maximum Ratings............................................................ 6
Handling SMBUSALERT Interrupts ....................................... 22
Thermal Characteristics .............................................................. 6
Interrupt Masking Register ....................................................... 22
ESD Caution.................................................................................. 6
FAN_FAULT Output ................................................................. 23
Pin Configuration and Function Descriptions............................. 7
Fault Queue ................................................................................. 23
Typical Performance Characteristics ............................................. 8
Conversion Rate Register .......................................................... 23
Functional Description .................................................................. 10
THERM I/O Timer and Limits ................................................ 23
Internal Registers........................................................................ 10
Serial Bus Interface..................................................................... 10
Location Input............................................................................. 10
SMBus 2.0 ARP-Capable Mode ................................................ 10
SMBus 2.0 Fixed-and-Discoverable Mode.............................. 12
SMBus 2.0 Read and Write Operations ................................... 12
Register Addresses for Single/Block Byte Modes ................... 14
Write Operations ........................................................................ 14
Read Operations ......................................................................... 15
SMBus Timeout .......................................................................... 15
Packet Error Checking (PEC) ................................................... 15
Alert Response Address (ARA) ................................................ 15
Temperature Measurement System.............................................. 16
Internal Temperature Measurement ........................................ 16
Remote Temperature Measurement......................................... 16
THERM % Limit Register ......................................................... 24
Fan Drive Signal ......................................................................... 25
Synchronous Speed Control ..................................................... 25
Fan Inputs.................................................................................... 26
Fan Speed Measurement ........................................................... 26
Fan Speed Measurement Registers........................................... 27
Reading Fan Speed ..................................................................... 27
Calculating Fan Speed ............................................................... 27
Alarm Speed................................................................................ 27
Look-Up Table: Modes of Operation....................................... 28
Setting Up the Size of the Look-Up Table............................... 29
Setting Up the Look-Up Table in Linear Mode...................... 29
Setting Which Temperature Channel Controls a Fan ........... 29
Look-Up Table Hysteresis ......................................................... 29
Additional Functions ................................................................. 18
Programming the THERM Limit for Each Temperature
Channel........................................................................................ 30
Layout Considerations ................................................................... 19
XOR Tree Test Mode.................................................................. 30
Limits, Status Registers, and Interrupts ....................................... 20
Lock Bit........................................................................................ 30
8-Bit Limits.................................................................................. 20
SW Reset...................................................................................... 30
Out-of-Limit Comparisons ....................................................... 20
Outline Dimensions ....................................................................... 40
Analog Monitoring Cycle Time................................................ 20
Ordering Guide .......................................................................... 40
Status Registers ........................................................................... 20
REVISION HISTORY
8/04—Revision 0: Initial Version
Rev. 0 | Page 2 of 40
ADM1034
GENERAL DESCRIPTION
The ADM1034 is a dual-channel remote- and local-temperature
sensor and fan controller. The remote channels monitor the
temperature of two remote thermal diodes, which may be
discrete 2N3904/6s or may be located on a microprocessor die.
The device also monitors its own ambient temperature.
The ADM1034 can monitor and control the speed of two
cooling fans. The user can program a target fan speed, or else
use the look-up table to input a temperature-to-fan-speed
profile. The look-up table can be configured to run the fans at
discrete speeds (discrete mode) or to ramp the fan speed with
temperature (linear mode).
The ADM1034 communicates over a 2-wire SMBus 2.0
interface. An 8-level LOCATION input allows the user to
choose between SMBus 1.1 and SMBus 2.0. An ALERT output
indicates error conditions. The THERM I/O signals overtemperature as an output and times THERM assertions as
an input. Pin 8 can be configured as a reference for the
THERM (PROCHOT) input.
Rev. 0 | Page 3 of 40
ADM1034
SPECIFICATIONS
TA = TMIN to TMAX, VCC = VMIN to VMAX, unless otherwise noted.1
Table 1.
Parameter
POWER SUPPLY
Supply Voltage, VCC2
Supply Current, ICC
Undervoltage Lockout Threshold
Power-On Reset Threshold
TEMPERATURE-TO-DIGITAL CONVERTER
Internal Sensor Accuracy
Min
Typ
Max
Unit
3.0
3.30
3.6
3
900
V
mA
µA
V
V
2.5
1
2.4
±1
−4
Resolution
External Diode Sensor Accuracy
0.03125
±0.5
±1
Series Resistance Cancellation
Power Supply Sensitivity
Conversion Time (Local Temperature)
Conversion Time (Remote Temperature)
Total Conversion Time
OPEN-DRAIN DIGITAL OUTPUTS
(ALERT, THERM, FAN_FAULT, DRIVE1, DRIVE2)3
Output Low Voltage, VOL
High Level Output Leakage Current, IOH
DIGITAL INPUT LEAKAGE CURRENT
(TACH1, TACH2)
Input High Current, IIH
Input Low Current, IIL
Input Capacitance, CIN
DIGITAL INPUT LOGIC LEVELS
(TACH1, TACH2)
Input High Voltage, VIH
Input Low Voltage, VIL
Hysteresis
OPEN-DRAIN SERIAL DATA
BUS OUTPUT (SDA)
Output Low Voltage, VOL
High Level Output Leakage Current, IOH
SERIAL BUS DIGITAL INPUTS
(SCL, SDA)
Input High Voltage, VIH
Input Low Voltage, VIL
Hysteresis
±1
+2
−3
Resolution
Remote Sensor Source Current
±2
+2
0.03125
85
34
5
1000
±1
11
32
75
0.1
20°C ≤ TA ≤ 60°C
−40°C ≤ TA ≤ +100°C
−40°C ≤ TD ≤ +100°C; TA = +40°C
−40°C ≤ TD ≤ +100°C; +20°C ≤ TA ≤ +60°C
−40°C ≤ TD ≤ +100°C; −40°C ≤ TA ≤ +100°C
High level
Mid level
Low level
Averaging enabled
Averaging enabled
Averaging enabled
V
µA
IOUT = −6.0 mA; VCC = +3 V
VOUT = VCC; VCC = 3 V
1
µA
µA
pF
−VIN = VCC
VIN = 0
5.5
+0.8
V
V
7
500
0.1
Interface inactive, ADC active
Standby mode
0.4
1
−1
2.0
−0.3
°C
°C
°C
°C
°C
°C
°C
µA
µΑ
µΑ
Ω
%/V
ms
ms
ms
Test Conditions/Comments
mV p−p
0.4
1
V
µA
0.8
V
V
mV
2.1
500
Rev. 0 | Page 4 of 40
IOUT = −6.0 mA; VCC
VOUT = VCC
ADM1034
Parameter
ANALOG INPUTS
(LOCATION, REF)
Input Resistance
AGTL + INPUT
(THERM)
Input High Level
Min
Typ
Max
Unit
80
125
160
kΩ
V
0.75 ×
REF
Input Low Level
TACHOMETER ACCURACY
Fan Speed Measurement Accuracy
SERIAL BUS TIMING4
Clock Frequency, fSCLK
Glitch Immunity, tSW
Bus Free Time, tBUF
Start Setup Time, tSU:STA
Start Hold Time, tHD:STA
Stop Condition Setup Time tSU:STO
SCL Low Time, tLOW
SCL High Time, tHIGH
SCL, SDA Rise Time, tr
SCL, SDA Fall Time, tf
Data Setup Time, tSU:DAT
Detect Clock Low Timeout, tTIMEOUT
0.4
V
±4
%
400
kHz
ns
µs
µs
µs
µs
µs
µs
ns
ns
ns
ms
50
1.3
0.6
0.6
0.6
1.3
0.6
1000
300
100
25
Test Conditions/Comments
35
See Figure 2
See Figure 2
See Figure 2
See Figure 2
See Figure 2
See Figure 2
See Figure 2
See Figure 2
See Figure 2
See Figure 2
See Figure 2
See Note 5
1
Typicals are at TA = 25°C and represent most likely parametric norm. Standby current typ is measured with VCC = 3.3 V. Timing specifications are tested at logic levels of
VIL = 0.8 V for a falling edge and VIH = 2.1 V for a rising edge.
2
Operation at 5.5 V is guaranteed by design, not production tested.
3
Recommend use of 100 kΩ pull-up resistors for all open-drain outputs from the ADM1034.
4
Guaranteed by design, not production tested.
5
SMBus timeout disabled by default. See the SMBUS section for more information.
tLOW
tR
tF
tHD:STA
SCL
tHD:DAT
tHIGH
tSU:STA
tSU:DAT
tSU:STO
SDA
tBUF
P
S
S
Figure 2. Serial Bus Timing Diagram
Rev. 0 | Page 5 of 40
P
04918-0-002
tHD:STA
ADM1034
ABSOLUTE MAXIMUM RATINGS
Table 2.
Parameter
Positive Supply Voltage (VCC)
Rating
−0.3 V to +6.5 V
Voltage on Any Input or Output Pin except
FAN_FAULT and LOCATION
Voltage on FAN_FAULT1
Voltage on LOCATION
Input Current at Any Pin
Maximum Junction Temperature (TJ max)
Storage Temperature Range
Lead Temperature, Soldering (10 s)
IR Reflow Peak Temperature
ESD Rating—All Pins
−0.3 V to +6.5 V
1
VCC
VCC + 0.3 V
±20 mA
150°C
−65°C to +150°C
300°C
220°C
1500 V
Stresses above those listed under Absolute Maximum Ratings
may cause permanent damage to the device. This is a stress
rating only; functional operation of the device at these or any
other conditions above those indicated in the operational
section of this specification is not implied. Exposure to Absolute
Maximum Rating conditions for extended periods may affect
device reliability.
THERMAL CHARACTERISTICS
16-Lead QSOP Package:
θJA = 150°C/W, θJC = 39°C/W
During power-up the voltage on FAN_FAULT should not be higher than VCC.
ESD CAUTION
ESD (electrostatic discharge) sensitive device. Electrostatic charges as high as 4000 V readily accumulate on
the human body and test equipment and can discharge without detection. Although this product features
proprietary ESD protection circuitry, permanent damage may occur on devices subjected to high energy
electrostatic discharges. Therefore, proper ESD precautions are recommended to avoid performance
degradation or loss of functionality.
Rev. 0 | Page 6 of 40
ADM1034
PIN CONFIGURATION AND FUNCTION DESCRIPTIONS
DRIVE1
1
16 SCL
TACH1
2
15 SDA
DRIVE2
3
ADM1034
TACH2
4
TOP VIEW
(Not to Scale)
GND
5
12 D2+
VCC
6
11 D2–
THERM
7
10 D1+
FAN_FAULT/REF
8
14 ALERT
9
D1–
04918-0-003
13 LOCATION
Figure 3. Pin Configuration
Table 3. Pin Function Descriptions
Pin No.
1
2
3
4
5
6
7
Mnemonic
DRIVE1
TACH1
DRIVE2
TACH2
GND
VCC
THERM
8
FAN_FAULT/REF
9
10
11
12
13
D1−
D1+
D2−
D2+
LOCATION
14
ALERT
15
SDA
16
SCL
Description
DRIVE1 Pin Drives Fan 1. Open-drain output. Requires a pull-up resistor.
Fan 1 Fan Speed Measurement Input. Connects to the fan’s TACH output to measure the fan speed.
DRIVE2 Pin Drives Fan 2. Open-drain output. Requires a pull-up resistor.
Fan 2 Fan Speed Measurement Input. Connects to the fan’s TACH output to measure the fan speed.
Ground for Analog and Digital Circuitry.
Power. Can be powered by 3.3 V standby power if monitoring in low power states is required.
Can be configured as an overtemperature interrupt output, or as an input (to monitor PROCHOT output of
an INTEL CPU). A timer measures assertion times on the THERM pin (either input or output).
FAN_FAULT: Open-Drain Output. Asserted low when one or both fans stall. Requires a pull-up resistor to VCC.
REF: Analog Input Reference for the THERM Input.
Cathode Connection for the First Thermal Diode or Diode-Connected Transistor.
Anode Connection for the First Thermal Diode or Diode-Connected Transistor.
Cathode Connection for the Second Thermal Diode or Diode-Connected Transistor.
Anode Connection for the Second Thermal Diode or Diode-Connected Transistor.
8-Level Analog Input. Used to determine the correct SMBus version and the SMBus address (in
fixed-and-discoverable mode) and to set the LLL bits in the UDID (in ARP-capable mode).
Open-Drain Output. SMBusALERT pin. Alerts the system in the case of out-of-limit events, such as over
temperature. Can be configured as sticky SMBus mode or comparator mode.
Serial Bus Bidirectional Data. Connects to the SMBus master’s data line. Requires pull-up resistor if not
provided elsewhere in the system.
Serial SMBus Clock Input. Connects to the SMBus master’s clock line. Requires pull-up resistor if not already
provided in the system.
Rev. 0 | Page 7 of 40
ADM1034
TYPICAL PERFORMANCE CHARACTERISTICS
20
40
EXT 100mVpp
EXT 250mVpp
TEMPERATURE ERROR (°C)
15
D+ TO GND
D+ TO VCC
–20
–40
–60
–80
–100
0
10
20
30
40
50
60
70
LEAKAGE RESISTANCE (MΩ)
80
90
5
0
–5
–10
0
100
Figure 4. Temperature Error vs. PCB Track Resistance DXP to GND and VCC
1M
2M
3M
4M
5M
6M
Figure 7. Remote Temperature Error vs. Power Supply Noise Frequency
50
0
45
TEMPERATURE ERROR (°C)
–10
DEV 33 (°C)
–20
–30
–40
DEV 31 (°C)
–50
DEV 32 (°C)
–60
40
35
30
25
100mV
20
15
20mV
–70
–80
0
2
4
6
8
CAPACITANCE (nF)
10
04918-0-008
10
50mV
04918-0-005
TEMPERATURE ERROR (°C)
10
04918-0-007
0
04918-0-004
TEMPERATURE ERROR (°C)
20
5
00
0
12
1M
2M
3M
4M
NOISE FREQUENCY (Hz)
5M
6M
Figure 8. Remote Temperature Error vs. Common-Mode Noise Frequency
Coupled on D+ and D−
Figure 5. Remote Temperature Error vs. D+, D− Capacitance
4.0
100
90
3.5
DEV 33
70
60
50
DEV 31
40
30
20
DEV 32
04918-0-006
10
0
–10
1
2
3
4
5
SERIES RESISTANCE IN D+/D– LINES (kΩ)
3.0
2.5
2.0
20mV
1.5
1.0
0.5
04918-0-009
TEMPERATURE ERROR (°C)
TEMPERATURE ERROR (°C)
80
10mV
0
6
0
Figure 6. Remote Temperature Error vs. Series Resistance on D+ and D−
1M
2M
3M
4M
NOISE FREQUENCY
5M
6M
Figure 9. Remote Temperature Error vs. Differential Mode Noise Frequency
Coupled on D+ and D−
Rev. 0 | Page 8 of 40
ADM1034
0.7
2
1
0.6
STANDBY SUPPLY CURRENT
HIGH 4 SIGMA
0
–2
–3
MEAN
S1
S2
S3
S4
S5
–5
–6
–7
–60
–40
V1
V2
V3
V4
V5
–20
0
LOW 4 SIGMA
20
40
60
80
TEMPERATURE (°C)
100
120
0.5
0.4
0.3
0.2
0.1
04918-0-013
–4
04918-0-010
ERROR (°C)
–1
0
0
140
1
2
3
4
SUPPLY VOLTAGE (V)
5
6
Figure 13. Standby Supply Current vs. Supply Voltage
Figure 10. Remote Temperature Error vs. Actual Diode Temperature
1200
2
1
HIGH 4 SIGMA
1000
0
800
ICC (µA)
–2
–3
MEAN
S1
S2
S3
S4
S5
–5
–6
–7
–50
V1
V2
V3
V4
V5
0
DEV 31
400
DEV 32
DEV 33
200
04918-0-011
–4
600
LOW 4 SIGMA
50
TEMPERATURE (°C)
100
04918-0-014
ERROR (°C)
–1
0
0.01
150
0.1
1
10
CONVERSION RATE (Hz)
100
Figure 14. Supply Current vs. Conversion Rate
Figure 11. Local Temperature Error vs. Actual Temperature
1.55
430
420
1.50
DEV 31
SUPPLY CURRENT
400
DEV 33
390
1.45
1.40
1.35
380
DEV 32
1.30
360
1
10
100
1.25
–60
1000
FSCL (kHz)
04918-0-015
370
04918-0-012
ICC (µA)
410
–40
–20
0
20
40
TEMPERATURE (°C)
60
80
Figure 15. Supply Current vs. ADM1034 Temperature
Figure 12. Standby Supply Current vs. SCLK Frequency
Rev. 0 | Page 9 of 40
100
ADM1034
FUNCTIONAL DESCRIPTION
VCC
The ADM1034 is a local- and remote-temperature monitor and
fan controller for use in a variety of applications, including
microprocessor-based systems. The device accurately monitors
remote and ambient temperature and uses that information to
quietly control the speed of a cooling fan. Whenever one of the
fans stalls, the device asserts a FAN_FAULT output.
LOCATION
04918-0-016
PIN 13
R2
GND
Figure 16. Bootstrapping the LOCATION Input
SMBus 2.0 ARP-CAPABLE MODE
In ARP-capable mode, the ADM1034 supports features such as
address resolution protocol (ARP) and unique device identifier
(UDID). The UDID is a 128-bit message that describes the
ADM1034’s capabilities to the master. The UDID also includes a
vendor-specific ID for functionally equivalent devices.
VCC
INTERNAL REGISTERS
Table 4 gives a brief description of the ADM1034’s principal
internal registers. For more detailed information on the
function of each register, refer to Table 34.
SERIAL BUS INTERFACE
The ADM1034 communicates with the master via the 2-wire
SMBus 2.0 interface. It supports two versions of SMBus 2.0,
determined by the value of the LOCATION input’s resistors.
The first version is fully ARP-capable. This means that it
supports address resolution protocol (ARP), allowing the
master to dynamically address the device on power-up. It
responds to ARP commands such as “Prepare to ARP.”
ADM1034 NO. 1
ARP
LOCATION = 111
1.5kΩ
ARP
LOCATION = 110
1kΩ
ARP
LOCATION = 101
1kΩ
ARP
LOCATION = 100
1kΩ
FD
ADDRESS = 53h
1kΩ
FD
ADDRESS = 52h
1kΩ
FD
ADDRESS = 51h
1.5kΩ
ADM1034 NO. 2
ADM1034 NO. 3
ADM1034 NO. 4
ADM1034 NO. 5
ADM1034 NO. 6
ADM1034 NO. 7
FD
ADDRESS = 50h
ADM1034 NO. 8
GND
04918-0-017
The ADM1034 features a THERM I/O. As an input, this
measures assertions on the THERM pin. As an output, it asserts
a low signal to indicate when the measured temperature exceeds
the programmed THERM temperature. The ADM1034
communicates over an SMBus 2.0 interface. Its LOCATION
input determines which version of SMBus to use, as well as the
SMBus address (in fixed-and-discoverable mode) and the
LOCATION bits in the UDID (in ARP-capable mode).
ADM1034
R1
Figure 17. Setting Up Multiple ADM1034 Addresses in
SMBus 2.0 ARP-Capable Mode
The second SMBus version, fixed-and-discoverable, is
backwards-compatible with SMBus 1.0 and 1.1. In this mode,
the ADM1034 powers up with a fixed address, which is
determined by the state of the LOCATION pin on power-up.
Note: When using the ADM1034, Addresses 0xC2 and 0xCA
should not be used by any other device on the bus.
LOCATION INPUT
The LOCATION input is a resistor divider input. It has multiple
functions and can specify the SMBus version (in fixed-anddiscoverable or ARP-capable modes); the SMBus address (in
fixed-and-discoverable mode); and the LLL bits (in UDID in
ARP-capable mode).
The voltage of this 8-level input is set by a potential divider. The
voltage on LOCATION is sampled on power-up and digitized
by the on-chip ADC to determine the LOCATION input value.
Because the LOCATION input is sampled only at power-up,
changes made while power is applied have no effect.
In SMBus 2.0 mode, this vendor-specific ID is generated by an
on-chip random number generator. This should enable two
adjacent ADM1034s in the same system to power up with a
different vendor-specific ID, allowing the master to identify the
two separate ADM1034s and assign a different address to each.
The state of the LOCATION input on power-up is also reflected
in the UDID. This is useful when there is more than one
ADM1034 in the system, so the master knows which one it is
communicating with. The complete UDID is listed in Table 6.
The SMBus 2.0 master issues both general and directed ARP
commands. A general command is directed at all ARP devices.
A directed command is targeted at a single device once an
address has been established. The PEC byte must be used for
ARP commands. (Refer to the Packet Error Checking (PEC)
section.) The ADM1034 responds to the following commands:
•
Prepare to ARP (general)
•
Reset device (general and directed)
•
Get UDID (general and directed)
•
Assign address (general)
Rev. 0 | Page 10 of 40
ADM1034
Table 4. Internal Register Descriptions
Register
Configuration
Conversion Rate
Address Pointer
Description
Provides control and configuration of various functions on the device.
Determines the number of measurements per second completed by the ADM1034.
Contains the address that selects one of the other internal registers. When writing to the ADM1034, the
first byte of data is always a register address, written to the address pointer register.
Provides the status of each limit comparison.
Allows the option to mask ALERTs due to particular out-of-limit conditions.
Stores the results of temperature and fan speed measurements, along with their limit values.
Allows the local and remote temperature channel readings to be offset by a twos complement value
written to them. These values are automatically added to the temperature values (or subtracted from them
if negative). This allows the systems designer to optimize the system if required, by adding or subtracting
up to 15.875°C from a temperature reading.
Contains the temperature value at which THERM is asserted and indicates the level of hysteresis.
Used to program the look-up table for the fan-speed-to-temperature profile.
Reflects the state of the THERM input and monitors the duration of the assertion time of the signal as a
percentage of a time window. The user can program the length of the time window.
Status
Interrupt Mask
Value and Limit
Offset
THERM Limit and Hysteresis
Look-Up Table
THERM % Ontime and
THERM % Limit
Table 5. Resistor Ratios for Setting LOCATION Bits
Ideal Ratio R2/(R1 + R2)
N/A
0.8125
0.6875
0.5625
0.4375
0.3125
0.1875
N/A
1
R1 kΩ
0
18
22
12
15
47
82
O/C
R2 Ω
O/C
82
47
15
12
22
18
0
Actual R2/(R1 + R2)
1
0.82
0.6812
0.5556
0.4444
0.3188
0.18
0
Error %
0
+0.75
−0.63
−0.69
+0.69
+0.63
−0.75
0
SMBus Ver
ARP1
ARP1
ARP1
ARP1
FD1
FD1
FD1
FD1
SMBus Address
N/A
N/A
N/A
N/A
0x53
0x52
0x51
0x50
UDID LLL
111
110
101
100
N/A
N/A
N/A
N/A
FD denotes fixed-and-discoverable mode, ARP denotes ARP-capable mode.
Table 6. UDID Values
Bit No.
<127:120>
Name
Device Capabilities
Function
Describes the ADM1034’s capabilities (for instance, that it supports PEC and uses a
random number address device).
UDID version number (Version 1) and silicon revision identification
Analog Devices vendor ID number, as assigned by the SBS Implementer’s Forum or
the PCI SIG.
Device ID.
<119:112>
<111:96>
Version/Revision
Vendor ID
<95:80>
Device ID
<79:64>
Interface
<63:48>
Subsystem Vendor ID
Identifies the protocol layer interfaces supported by the ADM1034. This represents
SMBus 2.0 as the Interface version..
Subsystem Vendor ID = 0 (subsystem fields are unsupported).
<47:32>
Subsystem Device ID
Subsystem Device ID = 0 (subsystem fields are unsupported).
<31:0>
Vendor Specific ID
A unique number per device. Contains LOCATION information (LL) and a 16-bit
random number (x). See Table 5 for information on setting the LLL bits.
Rev. 0 | Page 11 of 40
Value
11000001
00001010
00010001
11010100
00010000
00110100
00000000
00000100
00000000
00000000
00000000
00000000
00000000
00000LLL
xxxxxxxx
xxxxxxxx
ADM1034
SMBus 2.0 FIXED-AND-DISCOVERABLE MODE
The ADM1034 also supports fixed-and-discoverable mode,
which is backwards-compatible with SMBus 1.0 and 1.1. Fixedand-discoverable mode supports all the same functionality as
ARP-capable mode, except for assign address—in which case it
powers up with a fixed address and is not changed by the assign
address call. The fixed address is determined by the state of the
LOCATION pin on power-up.
SMBus 2.0 READ AND WRITE OPERATIONS
The master initiates data transfer by establishing a start
condition, defined as a high-to-low transition on the serial data
line (SDA) while the serial clock line (SCL) remains high. This
indicates that an address/data stream is to follow. All slave
peripherals connected to the serial bus respond to the start
condition and shift in the next 8 bits, which consist of a 7-bit
address (MSB first) plus an R/W bit. This last bit determines the
direction of the data transfer (whether data is written to or read
from the slave device).
It is not possible to mix read and write in one operation,
because the type of operation is determined at the beginning
and cannot be changed without starting a new operation.
To write data to one of the device data registers or to read data
from it, the address pointer register (APR) must be set so that
the correct data register is addressed; then data can be written
into that register or read from it. The first byte of a write
operation always contains an address that is stored in the APR.
If data is to be written to the device, then the write operation
contains a second data byte, which is written to the register
selected by the APR.
As illustrated in Figure 18, the device address is sent over the
bus, followed by R/W set to 0. This is followed by two data
bytes. The first data byte is the address of the internal data
register to be written to, which is stored in the APR. The second
data byte is the data to be written to the internal data register.
When reading data from a register there are two possibilities.
1.
The peripheral that corresponds to the transmitted address
responds by pulling the data line low during the low period
before the 9th clock pulse, which is known as the
acknowledge bit. All other devices on the bus remain idle
while the selected device waits for data to be read from or
written to it. If the R/W bit is a 0, the master writes to the
slave device. If the R/W bit is a 1, the master reads from it.
If the ADM1034’s APR value is unknown or incorrect, it must
be set to the correct value before data can be read from the
desired data register. To do this, perform a write to the ADM1034
as before, but send only the data byte containing the register.
(See Figure 19.) A read operation is then performed, using the
serial bus address and the R/W bit set to 1, followed by the data
byte read from the data register. (See Figure 20.)
2.
Data is sent over the serial bus in sequences of 9 clock
pulses—8 bits of data followed by an acknowledge bit from
the slave device. Transitions on the data line must occur
during the low period of the clock signal and remain stable
during the high period, because a low-to-high transition
when the clock is high may be interpreted as a stop signal.
The number of data bytes that can be transmitted over the
serial bus in a single read or write operation is limited only
by what the master and slave devices can handle.
However, if the APR is already at the desired address, data can
be read from the corresponding data register without first
writing to the APR. In this case, Figure 19 can be omitted.
3.
In Figure 18 to Figure 20, the serial bus address is determined
by the state of the LOCATION pin on power-up.
When all data bytes have been read or written, stop
conditions are established. In write mode, the master pulls
the data line high during the 10th clock pulse to assert a
stop condition. In read mode, the master device overrides
the acknowledge bit by pulling the data line high during
the low period before the 9th clock pulse. This is known as
no acknowledge. The master takes the data line low during
the low period before the 10th clock pulse, then high
during the 10th clock pulse to assert a stop condition.
Rev. 0 | Page 12 of 40
ADM1034
1
9
1
9
SCL
A6
SDA
A5
A4
A3
A2
A1
A0
R/W
START BY
MASTER
D6
D7
D5
D4
D3
D2
D1
D0
ACK. BY
ADM1034
ACK. BY
ADM1034
FRAME 2
ADDRESS POINTER REGISTER BYTE
FRAME 1
SERIAL BUS ADDRESS BYTE
1
9
SCL (CONTINUED)
D6
D5
D4
D2
D3
D1
D0
ACK. BY
ADM1034
STOP BY
MASTER
FRAME 3
DATA BYTE
04918-0-021
D7
SDA (CONTINUED)
Figure 18. Writing a Register Address to the Address Pointer Register, then Writing Data to the Selected Register
1
9
1
9
SCL
A6
A5
A4
A3
A2
A1
A0
R/W
D7
D6
D5
D4
D3
D2
D1
D0
ACK. BY
ADM1034
START BY
MASTER
ACK. BY
ADM1034
FRAME 1
SERIAL BUS ADDRESS BYTE
STOP BY
MASTER
04918-0-022
SDA
FRAME 2
ADDRESS POINTER REGISTER BYTE
Figure 19. Writing to the Address Pointer Register Only (Send Byte)
1
9
1
9
SCL
A6
A5
A4
A3
A2
A1
A0
R/W
D7
D6
D5
D4
D3
D2
D1
ACK. BY
ADM1034
START BY
MASTER
FRAME 1
SERIAL BUS ADDRESS BYTE
NO ACK. BY STOP BY
ADM1034 MASTER
FRAME 2
DATA BYTE FROM ADM1034
Figure 20. Reading Data from a Previously Selected Register
Rev. 0 | Page 13 of 40
D0
04918-0-023
SDA
ADM1034
Write Byte
The ADM1034 supports single-byte as well as block read and
write operations. The register address determines whether a
single-byte or multiple-byte (block) operation is run. For a
single-byte operation, the MSB of the register address is set to 0;
for a multiple-byte operation, it is set to 1. The number of bytes
read in a multiple-byte operation is set in the #Bytes/Block Read
Register at Address 0x00. The number of bytes written to the
ADM1034 is specified during the block-write operation. The
addresses quoted in the register map and throughout this data
sheet assume single-byte operation. For multiple-byte
operations, set the MSB of each register address to 1.
WRITE OPERATIONS
The SMBus specifications define protocols for read and write
operations. The ADM1034 supports send-byte, write-byte, and
block-byte SMBus write protocols. The following abbreviations
are used in the diagrams:
In this operation, the master device sends a register address and
one data byte to the slave device as follows:
1.
The master asserts a start condition on SDA.
2.
The master sends the 7-bit slave address followed by a
write bit (low).
3.
The addressed slave device asserts ACK on SDA.
4.
The master sends the register address. The MSB of the
register address should equal 0 for a write-byte operation.
If the MSB equals 1, a block-write operation takes place.
5.
The slave asserts ACK on SDA.
6.
The master sends a data byte.
7.
The slave asserts ACK on SDA.
8.
The master asserts a stop condition on SDA to end the
transaction.
S
S—START
SLAVE
REG
W A
A
ADDRESS
ADDRESS
DATA
A P
04918-0-019
REGISTER ADDRESSES FOR
SINGLE/BLOCK BYTE MODES
Figure 22. Write Byte Operation
P—STOP
Block Write
R—READ
In this operation, the master device writes a block of data to a
slave address as follows. A maximum of 32 bytes can be written.
W—WRITE
A—ACKNOWLEDGE
A—NO ACKNOWLEDGE
Send Byte
In this operation, the master device sends a single-command
byte to a slave device as follows:
1.
The master asserts a start condition on SDA.
2.
The master sends the 7-bit slave address followed by a
write bit (low).
3.
The addressed slave device asserts ACK on SDA.
4.
The master sends the register address. The register address
sets up the address pointer register and determines
whether a block-write (MSB = 1) or a byte-write (MSB = 0)
takes place.
The master device asserts a start condition on SDA.
2.
The master sends a 7-bit address followed by the write bit
(low).
3.
The addressed slave device asserts ACK on SDA.
5.
The slave asserts ACK on SDA.
4.
The master sends the register address.
6.
The master sends the byte count.
5.
The slave asserts ACK on SDA.
7.
The slave asserts ACK on SDA.
6.
The master asserts a stop condition on SDA, and the
transaction ends.
8.
The master sends N data bytes.
9.
The slave asserts ACK on SDA after each byte.
REG
SLAVE
A P
W A
ADDRESS
ADDRESS
10. The master asserts a stop condition on SDA to end the
transaction.
Figure 21. Send Byte
S
The ADM1034 uses the send-byte operation to write a register
address to the APR for a subsequent read from the same
address. (See Figure 24.) The user may be required to read data
from the register immediately after setting up the address. If so,
the master can assert a repeat start condition immediately after
the final ACK and carry out a single-byte read without asserting
an intermediate stop condition.
SLAVE
W A
ADDRESS
Rev. 0 | Page 14 of 40
REGISTER
ADDRESS
A
BYTE
A DATA 1 A DATA 2 A DATA N A P
COUNT
Figure 23. Block Write to RAM
04918-0-020
S
04918-0-018
1.
READ OPERATIONS
S
Receive Byte
This is useful when repeatedly reading a single register. The
register address must be set up prior to this, with the MSB at 0
to read a single byte. In this operation, the master device
receives a single byte from a slave device as follows:
1.
The master device asserts a start condition on SDA.
2.
The master sends the 7-bit slave address followed by the
read bit (high).
3.
The addressed slave device asserts ACK on SDA.
4.
The master receives a data byte.
5.
The master sends NO ACK on SDA.
6.
The master asserts a stop condition on SDA, and the
transaction ends.
A P
SMBus TIMEOUT
The ADM1034 has a programmable SMBus timeout feature.
When this is enabled, the SMBus typically times out after 25 ms
of no activity. The timeout is disabled by default. It prevents
hangups by releasing the bus after a period of inactivity.
To enable the SDA timeout, set the SDA timeout bit (Bit 5) of
Configuration Register 1 (Address 0x01) to 1.
PACKET ERROR CHECKING (PEC)
The ADM1034 also supports packet error checking (PEC). This
optional feature is triggered by the extra clock for the PEC byte.
The PEC byte is calculated using CRC-8. The frame check
sequence (FCS) conforms to CRC-8 by the following:
C (x ) = x8 + x 2 + x + 1
For more information, consult www.SMBus.org.
Figure 24. Receive Byte
ALERT RESPONSE ADDRESS (ARA)
Block Read
In this operation, the master reads a block of data from a slave
device. The number of bytes to be read must be set in advance.
To do this, use a write-byte operation to the #Bytes/Block Read
Register at Address 0x00. The register address determines
whether a block-read or a read-byte operation is to be completed
(set MSB to 1 to specify a block-read operation). A maximum of
32 bytes can be read.
1. The master asserts a start condition on SDA.
2.
The master sends the 7-bit slave address followed by the
write bit (low).
3.
The addressed slave device asserts ACK on SDA.
4.
The master sends the register address (MSB = 1).
5.
The slave asserts ACK on SDA.
6.
The master asserts a repeated start on SDA.
7.
The master sends the 7-bit slave address followed by the
read bit (high).
8.
The slave asserts ACK on SDA.
9.
The slave sends the byte count.
S
ALERT RESPONSE
DEVICE
R A
A P
ADDRESS
ADDRESS
04918-0-043
DATA
BYTE
SLAVE
A DATA 1 A DATA N A P
R A
COUNT
ADDRESS
Figure 25. Block Read from RAM
04918-0-024
SLAVE
R A
ADDRESS
A S
To enable the SCL timeout, set the SCL timeout bit (Bit 4) of
Configuration Register 1 (Address 0x01) to 1.
In the ADM1034, the receive-byte protocol is used to read a
single byte from a register whose address has previously been
set by a send-byte or write-byte operation.
S
REGISTER
ADDRESS
SLAVE
W A
ADDRESS
04918-0-025
ADM1034
Figure 26. ALERT Response Address
When multiple devices exist on the same bus, the ARA feature
allows an interrupting device to identify itself to the host.
The ALERT output can be used as an interrupt output or as an
SMBusALERT. One or more ALERT outputs can be connected
to a common SMBusALERT line, connected to the master.
If a device’s ALERT line goes low, the following occurs:
10. The master asserts ACK on SDA.
1.
SMBusALERT is pulled low.
2.
The master initiates a receive-byte operation and sends the
alert response address (ARA 0001 100). This is a general
call address that must not be used as a specific address.
3.
The device with the low ALERT output responds to the
ARA, and the master reads its device address. Once the
address is known, it can be interrogated in the usual way.
4.
If low ALERT output is detected in more than one device,
the one with the lowest device address has priority, in
accordance with normal SMBus arbitration.
5.
Once the ADM1034 has responded to the ARA, it resets its
ALERT output. However, if the error persists, the ALERT is
re-asserted on the next monitoring cycle.
11. The slave sends N data bytes.
12. The master asserts ACK on SDA after each data byte.
13. The master does not acknowledge after the Nth data byte.
14. The master asserts a stop condition on SDA to end the
transaction.
Rev. 0 | Page 15 of 40
ADM1034
TEMPERATURE MEASUREMENT SYSTEM
Table 8. Local and Remote Sensor Extended Resolution
INTERNAL TEMPERATURE MEASUREMENT
The ADM1034 contains an on-chip band gap temperature
sensor. The on-chip ADC performs conversions on the sensor’s
output, outputting the data in 13-bit format. The resolution of
the local temperature sensor is 0.03125°C.
Table 7 shows the format of the temperature data MSBs. Table 8
shows the same for the LSBs. To ensure accurate readings, read
the LSBs first. This locks the current LSBs and MSBs until the
MSBs are read. They then start to update again. (Reading only
the MSBs does not lock the registers.) Temperature updates to
the look-up table take place in parallel; so fan speeds may be
updated even if the MSBs are locked.
Extended Resolution (°C)
0.0000
0.03125
0.0625
0.125
0.250
0.375
0.500
0.625
0.750
0.875
Temperature (°C) = (MSB − 64°C) + (LSB × 0.03125)
Table 7. Temperature Data Format
(Local Temperature and Remote Temperature High Bytes)
Digital Output
0000 0000
0001 1000
0010 0000
0011 1110
0011 1111
0100 0000
0100 0001
0100 0010
0100 1010
0101 0100
0111 0010
1000 1011
1010 0100
1011 1101
1101 0110
1111 1111
Example: MSB = 0101 0100 = 84d
LSB = 11100 = 28
Temperature °C = (84 – 64) + (28 × 0.03125) = 20.875
REMOTE TEMPERATURE MEASUREMENT
The ADM1034 can measure the temperature of two external
diode sensors or diode-connected transistors, which are
connected to Pins 9 and 10 and Pins 11 and 12. These pins are
dedicated temperature input channels. The series resistance
cancellation (SRC) feature can automatically cancel out the
effect of up to 1 kΩ of resistance in series with the remote
thermal diode.
The forward voltage of a diode or diode-connected transistor,
operated at a constant current, exhibits a negative temperature
coefficient of about −2 mV/°C. Unfortunately, the absolute
value of Vbe varies from device to device, and individual
calibration is required to null this out. Therefore, the technique
is unsuitable for mass production.
ADM1034
D+
ADM1034
2N3904
D+
2N3906
D–
D–
Figure 27. Measuring Temperature by Using Discreet Transistors
Rev. 0 | Page 16 of 40
04918-0-026
Temperature (°C)
−64°C
−40°C
−32°C
−2°C
−1°C
0°C
1°C
2°C
10°C
20°C
50°C
75°C
100°C
125°C
150°C
191°C
Temperature Low Bits
00000
00001
00010
00100
01000
01100
10000
10100
11000
11100
ADM1034
The ADM1034 operates at three different currents to measure
the change in Vbe. Figure 28 shows the input signal conditioning
used to measure the output of an external temperature sensor. It
also shows the external sensor as a substrate transistor, provided
for temperature monitoring on some microprocessors. The
external sensor could work equally well as a discrete transistor.
One LSB of the ADC corresponds to 0.03125°C. The ADM1034
can theoretically measure temperatures from −64°C to
+191.96875°C, although these are outside its operating range.
The extended temperature resolution data format is shown in
Table 8. The data for the local and remote channels is stored in
the extended temperature resolution registers (Reg. 0x40 =
Local, Reg. 0x42 = Remote 1, and Reg. 0x44 = Remote 2).
If a discrete transistor is used, the collector is not grounded, and
should be linked to the base. If a PNP transistor is used, the base
is connected to the D− input and the emitter to the D+ input. If
an NPN transistor is used, the emitter is connected to the D−
input and the base to the D+ input.
Table 9.Temperature Measurement Registers
Register
0x40
0x41
0x42
0x43
0x44
0x45
If the sensor is used in a very noisy environment, a capacitor
value up to 1000 pF may be placed between the D+ and D−
inputs to filter the noise. However, additional parasitic
capacitance on the lines between D+, D−, and the thermal diode
should also be considered. The total capacitance should never
be greater than 1000 pF.
Description
Local Temperature, LSBs
Local Temperature, MSBs
Remote 1 Temperature, LSBs
Remote 1 Temperature, MSBs
Remote 2 Temperature, LSBs
Remote 2 Temperature, MSBs
High and low temperature limit registers are associated with
each temperature measurement channel. Exceeding the
programmed high and low limits sets the appropriate status bit.
Exceeding either limit can cause an SMBusALERT interrupt.
To measure each ∆Vbe, the sensor is switched between operating
currents of I, (N1 × I), and (N2 × I). The resulting waveform is
passed through a 65 kHz low-pass filter to remove noise, then to
a chopper-stabilized amplifier that amplifies and rectifies the
waveform. This produces a dc voltage proportional to ∆Vbe.
These voltage measurements determine the temperature of the
thermal diode, while automatically compensating for any series
resistance on the D+ and/or D− lines. The temperature is stored
in two registers as a 13-bit word.
Table 10. Temperature Measurement Limit Registers
Register
0x0B
0x0C
0x0D
0x0E
0x0F
0x10
0x11
0x12
0x13
To further reduce the effects of noise, digital filtering is
performed by averaging the results of 16 measurement cycles at
conversion rates of less than or equal to 8 Hz. An external
temperature measurement takes nominally 32 ms when
averaging is enabled and 6 ms when averaging is disabled.
Description
Local High Limit
Local Low Limit
Local THERM Limit
Remote 1 High Limit
Remote 1 Low Limit
Remote 1 THERM Limit
Remote 2 High Limit
Remote 2 Low Limit
Remote 2 THERM Limit
VDD
I
N2 × I
N1 × I
IBIAS
D+
VOUT+
TO ADC
D–
LOW-PASS FILTER
fC = 65kHz
VOUT–
04918-0-027
REMOTE
SENSING
TRANSISTOR
Default
0x00
0x00
0x00
0x00
0x00
0x00
Figure 28. ADM1034 Signal Conditioning
Rev. 0 | Page 17 of 40
Default
0x8B (75°C)
0x54 (20°C)
0x95 (85°C)
0x8B (75°C)
0x54 (20°C)
0x95 (85°C)
0x8B (75°C)
0x54 (20°C)
0x95 (85°C)
ADM1034
ADDITIONAL FUNCTIONS
Removing Temperature Errors
Several other temperature measurement functions available on
the ADM1034 offer the systems designer added flexibility.
As CPUs run faster and faster, it gets more difficult to avoid
high frequency clocks when routing the D+ and D− traces
around a system board. Even when the recommended layout
guidelines are followed, temperature errors attributed to noise
coupled onto the D+ and D− lines remain. High frequency
noise generally gives temperature measurements that are
consistently too high. The ADM1034 has Local, Remote 1, and
Remote 2 temperature offset registers at 0x16, 0x17, and 0x18—
one for each channel. By completing a one-time calibration, the
user can determine the offset caused by the system board noise
and remove it using the offset registers. The registers
automatically add a twos compliment word to the remote
temperature measurements, ensuring correct readings in the
value registers.
Turn-off Averaging
The ADM1034 performs averaging at conversion rates of less
than or equal to 8 conversions per second. This means that the
value in the measurement register is the average of 16 measurements. For faster measurements, set the conversion rate to 16
conversions per second or greater. (Averaging is not carried out
at these conversion rates.) Alternatively, switch off averaging at
the slower conversion rates by setting Bit 1 (AVG) of
Configuration 1 Register (Address 0x01).
Single-Channel ADC Conversions
In normal operating mode, the ADM1034 converts on three
temperature channels: the local temperature channel, and the
remote 1 and remote 2 channels. However, the user has the
option to set up the ADM1034 to convert on one channel only.
To enable single-channel mode, the user sets the round-robin
bit (Bit 7) in Configuration Register 2 (Address 0x02) to 0.
When the round-robin bit equals 1, the ADM1034 converts on
all three temperature channels. In single-channel mode, it
converts on one channel only, to be determined by the state of
the channel selector bits (Bits 5 and 4) of the Configuration
Register 2 (Address 0x02).
Table 11. Channel Selector
Bits 5:4
00
01
10
11
Channel Selector (Configuration 2)
Local Channel = Default
Remote 1 Channel
Remote 2 Channel
Reserved
Table 12. Offset Registers
Registration
0x16
0x17
0x18
Description
Local Offset
Remote 1 Offset
Remote 2 Offset
Table 13. Offset Register Values
Code
0 0000 000
0 0000 001
0 0000 111
0 0001 111
0 0111 111
0 1111 111
1 0000 000
1 1111 000
Rev. 0 | Page 18 of 40
Offset Value
0°C (Default Value)
0.125°C
0.875°C
1.875°C
7.875°C
15.875°C
−16°C
−0.875°C
Default
0x00
0x00
0x00
ADM1034
LAYOUT CONSIDERATIONS
Digital boards can be electrically noisy environments. Try
to protect the analog inputs from noise, particularly when
measuring the very small voltages from a remote diode sensor.
Take the following precautions:
•
Place the ADM1034 as close as possible to the remote
sensing diode. A distance of 4 inches to 8 inches is
adequate, provided that the worst noise sources such
as clock generators, data/address buses, and CRTs are
avoided.
•
Route the D+ and D− tracks close together, in parallel, with
grounded guard tracks on each side. Provide a ground
plane under the tracks if possible.
•
Use wide tracks to minimize inductance and reduce noise
pickup. At least 5 mil track width and spacing are
recommended.
5MIL
GND
5MIL
D+
5MIL
5MIL
•
For very long distances (up to 100 feet), use shielded
twisted pair such as Belden #8451 microphone cable.
Connect the twisted pair to D+ and D− and the shield to
GND, close to the ADM1034. Leave the remote end of the
shield unconnected to avoid ground loops.
Because the measurement technique uses switched current
sources, excessive cable and/or filter capacitance can affect the
measurement. When using long cables, the filter capacitor C1
may be reduced or removed. In any case, the total shunt
capacitance should never exceed 1000 pF.
Noise Filtering
For temperature sensors operating in noisy environments,
common practice is to place a capacitor across the D+ and D−
pins to help combat the effects of noise. However, large
capacitances affect the accuracy of the temperature measurement,
leading to a recommended maximum capacitor value of 1000 pF.
While this capacitor reduces the noise, it does not eliminate it,
making it difficult to use the sensor in a very noisy environment.
5MIL
Figure 29. Arrangement of Signal Tracks
Try to minimize the number of copper/solder joints,
because they can cause thermocouple effects. Where
copper/solder joints are used, make sure that they are in
both the D+ and D− paths and at the same temperature.
Thermocouple effects are not a major problem because
1°C corresponds to approximately 200 µV, and thermocouple voltages are approximately 3 µV/°C of temperature
difference. Unless there are two thermocouples with a big
temperature differential between them, the voltages should
be much less than 200 µV.
The ADM1034 has a major advantage over other devices when
it comes to eliminating the effects of noise on the external
sensor. The series resistance cancellation feature allows a filter
to be constructed between the external temperature sensor and
the part. The effect of any filter resistance seen in series with the
remote sensor is automatically cancelled from the temperature.
The construction of a filter allows the ADM1034 and the
remote temperature sensor to operate in noisy environments.
Figure 30 shows a low-pass R-C-R filter with the following
values: R = 100 Ω and C = 1 nF. This filtering reduces both
common-mode noise and differential noise.
100Ω
D+
REMOTE
TEMPERATURE
SENSOR
1nF
100Ω
D–
Place a 0.1 µF bypass capacitor close to the ADM1034.
04110-0-009
GND
04918-0-028
5MIL
•
If the distance to the remote sensor is more than 8 inches,
twisted pair cable is recommended. This works up to about
6 feet to 12 feet.
5MIL
D–
•
•
Figure 30. Filter between Remote Sensor and ADM1034
Rev. 0 | Page 19 of 40
ADM1034
LIMITS, STATUS REGISTERS, AND INTERRUPTS
High and low limits are associated with each measurement
channel on the ADM1034. These can form the basis of system
status monitoring. A status bit can be set for any out-of-limit
condition and detected by polling the device. Alternatively,
SMBusALERTs can be generated to flag a processor or
microcontroller of an out-of-limit condition.
The ADC performs round-robin conversions and takes 11 ms
for the local temperature measurement and 32 ms for each
remote temperature measurement with averaging enabled.
The total monitoring cycle time for the average temperatures is
therefore nominally
(2 × 32) + 11 = 75 ms
8-BIT LIMITS
The following is a list of all the 8-bit limits on the ADM1034:
Table 14. Temperature Limit Registers
Register
0x0B
0x0C
0x0D
0x0E
0x0F
0x10
0x11
0x12
0x13
Description
Local High Limit
Local Low Limit
Local THERM Limit
Remote 1 High Limit
Remote 1 Low Limit
Remote 1 THERM Limit
Remote 2 High Limit
Remote 2 Low Limit
Remote 2 THERM Limit
Default
0x8B (75°C)
0x54 (20°C)
0x95 (85°C)
0x8B (75°C)
0x54 (20°C)
0x95 (85°C)
0x8B (75°C)
0x54 (20°C)
0x95 (85°C)
Fan TACH measurements take place in parallel and are not
synchronized with the temperature measurements in any way.
STATUS REGISTERS
The results of limit comparisons are stored in the status
registers. A 1 represents an out-of-limit measurement; a
0 represents an in-limit measurement. The status registers are
located at Addresses 0x4F to 0x51.
If the measurement is outside its limits, the corresponding
status register bit is set to 1. It remains set at 1 until the
measurement falls back within its limits and it is read or until
an ARA is completed.
Table 15. THERM Limit Register
Register
0x19
Description
THERM % Limit
Once the conversion time elapses, the round robin starts again.
For more information, refer to the Conversion Rate Register
section.
Default
0xFF default
OUT-OF-LIMIT COMPARISONS
The ADM1034 measures all parameters in a round-robin
format and sets the appropriate status bit for out-of limit
conditions. Comparisons are made differently, depending on
whether the measured value is compared to a high or low limit.
High Limit: ≥ Comparison Performed
Low Limit: < Comparison Performed
ANALOG MONITORING CYCLE TIME
The analog monitoring cycle time begins on power-up, or, if
monitoring has been disabled, by writing a 1 to the monitor/
STBY bit of Configuration Register 1, (Address 0x01). The ADC
measures each one of the analog inputs in turn; as each
measurement is completed, the result is automatically stored in
the appropriate value register. The round-robin monitoring
cycle continues unless it is disabled by writing a 0 to the
monitor/STBY bit (Bit 0) of Configuration Register 1
(Address 0x01).
Poll the state of the various measurements by reading the status
registers over the serial bus. If Bit 0 (ALERT low) of Status
Register 3 (Address 0x51) is set, this means that the ALERT
output has been pulled low by the ADM1034.
Pin 14 can be configured as a SMBusALERT output. This
automatically notifies the system supervisor of an out-of-limit
condition. Reading the status register clears the status bit as long
as the error condition is gone.
Status register bits are sticky. Whenever a status bit is set due to
an out-of-limit condition, it remains set—even after the
triggering event has gone. The only way to clear the status bit is
to read the status register (after the event has gone). Interrupt
mask registers (Reg. 0x08, Reg. 0x09, Reg. 0x0A) allow
individual interrupt sources to be masked from causing an
ALERT. However, if one of these masked interrupt sources goes
out of limit, its associated status bit is set in the status register.
Rev. 0 | Page 20 of 40
ADM1034
ALERT INTERRUPT BEHAVIOR
Table 16. Interrupt Status Register 1 (Reg. 0x4F)
Bit No.
7
Name
LH
6
LL
5
R1H
4
R1L
3
R1D
2
R2H
1
R2L
0
R2D
Description
1 = Local high temperature limit has been
exceeded.
1 = Local low temperature limit has been
exceeded.
1 = Remote 1 high temperature limit has
been exceeded.
1 = Remote 1 low temperature limit has
been exceeded.
1 = Remote 1 diode error; indicates an open
or short on the D1+/D1− pins.
1 = Remote 2 high temperature limit has
been exceeded.
1 = Remote 2 low temperature limit has
been exceeded.
1 = Remote 2 diode error; indicates an open
or short on the D2+/D2− pins.
The ADM1034 generates an ALERT whenever an out-of-limit
measurement is made (if it is not masked out). The user can
also detect out-of-limit conditions by polling the ADM1034
status registers. It is important to note how the SMBus ALERT
output behaves when writing interrupt handler software.
The ALERT output on the ADM1034 can be programmed to
operate in either SMBusALERT mode or in comp mode.
In SMBusALERT mode, the ALERT output remains low until
the measurement falls back within its programmed limits and
either the status register is read or an ARA is completed. In
comp mode, the ALERT output automatically resets once the
temperature measurement falls back within the programmed
limits.
Configuring the ALERT Output
Bit No.
7
Name
LT
6
R1T
5
R2T
4
T%
3
TA
2
TS
1
0
Res
Res
Description
1 = Local THERM temperature limit has
been exceeded.
1 = Remote 1 THERM temperature limit has
been exceeded.
1 = Remote 2 THERM temperature limit has
been exceeded.
1 = THERM % ontime limit has been
exceeded.
1 = One of the THERM limits has been
exceeded; and the THERM output signal
has been asserted.
1 = THERM state. Indicates the THERM pin is
active; clears on a read if THERM is not
active. Does not generate an ALERT in
ALERT comp mode.
Reserved.
Reserved.
Table 18. Status Register 3 (Reg. 0x51)
Bit No.
7
6
Name
F1S
FA
5
4
3
2
1
0
F2S
Res
Res
Res
Res
ALERT
Description
1 = Fan 1 has stalled.
1 = Fan alarm speed. Fan1 and Fan 2 are
running at alarm speed.
1 = Fan 2 has stalled.
Reserved.
Reserved.
Reserved.
Reserved.
1 = ALERT low; indicates the ALERT line has
been pulled low.
For SMBusALERT mode, set the ALERT configuration bit
(Bit 3) of the Configuration Register 1 (Address 0x01) to 0.
In SMBusALERT mode, a status bit is set when a measurement
goes outside of its programmed limit. If the corresponding
mask bit is not set, the ALERT output is pulled low. If the
measured value falls back within the limits, the ALERT output
remains low until the corresponding status register is read or
until an ARA is completed (as long as no other measurement is
outside its limits).
For comp mode, set the ALERT configuration bit (Bit 3) of
Configuration Register 1 (Address 0x01) to1.
In comp mode, the ALERT output is automatically pulled low
when a measurement goes outside its programmed limits. Once
the measurement falls back within its limits (and assuming no
other measurement channel is outside its limits), the ALERT
output is automatically pulled high again.
The main difference between the two modes is that the
SMBusALERT does not reset without software intervention,
whereas the comp mode ALERT output automatically resets.
TEMPERATURE
LIMITS
ALERT, 70°C
TIME
SMBusALERT
ALERT COMP
CLEARED
ON READ
Figure 31. ALERT Comparator and SMBusALERT Outputs
Rev. 0 | Page 21 of 40
04918-0-029
Table 17. Status Register 2 (Reg. 0x50)
ADM1034
HANDLING SMBusALERT INTERRUPTS
Table 19. Mask Register 1 (Reg. 0x08)
Bit No.
7
Name
LH
6
LL
5
R1H
4
R1L
3
R1D
2
R2H
1
R2L
0
R2D
HIGH LIMIT
TEMPERATURE
CLEARED ON READ
(TEMP BELOW LIMIT)
TEMP BACK IN LIMIT
(STATUS BIT STAYS SET)
SMBusALERT
INTERRUPT
MASK BIT SET
INTERRUPT MASK BIT
CLEARED
(SMBusALERT REARMED)
04918-0-030
"STICKY"
STATUS BIT
Figure 32. Handling SMBusALERT
To prevent tie-ups due to service interrupts, follow these steps:
1.
Detect an SMBus assertion.
2.
Enter the interrupt handler.
3.
Read the status register to identify the interrupt source.
4.
Mask the interrupt source by setting the appropriate mask
bit in the interrupt mask registers (from Reg. 0x08 to
Reg. 0x0A).
5.
Take the appropriate action for a given interrupt source.
6.
Exit the interrupt handler.
7.
Periodically poll the status register. If the interrupt status
bit clears, reset the corresponding interrupt mask bit to 0.
The SMBusALERT output and status bits then behave as
shown in Figure 32.
Description
1 masks the ALERT for the local high
temperature.
1 masks the ALERT for the local low
temperature.
1 masks the ALERT for the Remote 1 high
temperature.
1 masks the ALERT for the Remote 1 low
temperature.
1 masks the ALERT for the Remote 1 diode
errors.
1 masks the ALERT for the Remote 2 high
temperature.
1 masks the ALERT for the Remote 2 low
temperature.
1 masks the ALERT for the Remote 2 diode
errors.
Table 20. Mask Register 2 (Reg. 0x09)
Bit No.
7
6
5
4
Name
Res
Res
Res
T%
3
TA
2
TS
1
0
Res
Res
Description
Reserved.
Reserved.
Reserved.
1 masks the ALERT for the THERM % ontime
limit.
1 masks the ALERT for the THERM limit
being exceeded and the THERM output
signal being asserted.
1 masks the ALERT for the THERM state; has
no effect on ALERT in ALERT comp mode.
Reserved.
Reserved.
INTERRUPT MASKING REGISTER
Table 21. Mask Register 3 (Reg. 0x0A)
Mask Registers 1, 2, and 3 are located at Addresses 0x08, 0x09,
and 0x0A. These allow individual interrupt sources to be
masked out to prevent the SMBusALERT interrupts. Masking
the interrupt source prevents only the SMBusALERT from
being asserted; the appropriate status bit is still set as normal.
Bit No.
7
6
5
4
3
2
1
0
Rev. 0 | Page 22 of 40
Name
F1S
FA
F2S
Res
Res
Res
Res
Res
Description
1 masks the ALERT for Fan 1 stalling.
1 masks the ALERT for fans at ALARM speed.
1 masks the ALERT for Fan 2 stalling.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
ADM1034
CONVERSION RATE REGISTER
FAN_FAULT OUTPUT
The FAN_FAULT output signals when one or both of the fans
stall. Pin 8, the FAN_FAULT output, is a dual-function pin. It
defaults to being a FAN_FAULT output but can be reconfigured
as an analog input reference for the THERM input. To do this,
set the FAN_FAULT/REF (Bit 7) in Configuration Register 4
(Address 0x04) to 1.
FAULT QUEUE
The ADM1034 has a programmable fault queue option that lets
the user program the number of out-of-limit measurements
allowable before generating an ALERT. The fault queue affects
only temperature measurement channels and is only operational
in SMBusALERT mode. It performs some simple filtering,
which is particularly useful at the higher conversion rates (16,
32, and 64 conversions/second), where averaging is not carried
out.
There is a queue for each of the temperature channels. If L (the
number programmed to the fault queue) or more consecutive
out-of-limit readings are made on the same temperature
channel, the fault queue fills, and the SMBusALERT output
triggers. To fill the fault queue, one needs L or more consecutive
out of limits on the internal temperature channel; L or more
consecutive out-of-limits on the external 1 temperature channel;
or L or more consecutive out-of-limits on the external 2 temperature channel. The fault queue is independent of the state of
the bits in the ALERT status registers.
Table 22. Fault Queue Address 0x06
Table 23 lists the available conversion rates. Note that the
current round-robin loop must be finished for conversion rates
changes to take effect.
The conversion rate register is located at Address 0x05.
Table 23. Conversion Rates
Code
0x00
0x01
0x02
0x03
0x04
0x05
0x06
0x07
0x08
0x09
0x0A
0x0B to 0xFF
THERM I/O TIMER AND LIMITS
Pin 7 can be configured as either an input or output. As an
output it is asserted low to signal that the measured temperature
has exceeded preprogrammed temperature limits. The output is
automatically pulled high again when the temperature falls
below the THERM – Hys limit. The value of hysteresis is
programmable in Register 0x1A. THERM is enabled as an
output by default on power-up.
Fault Queue
1
2
3
4
To reset the fault queue, do one of the following:
•
SMBus ARA Command
•
Read Status Register 1
•
Power-On Reset
Conversion Rate
0.0625
0.125
0.25
0.5
1
2
4
8
16
32
64
Reserved
TEMPERATURE
LIMITS
THERM, 85°C
THERM-HYST,
80°C
The SMBusALERT clears, even if the condition that caused the
SMBusALERT remains. The SMBusALERT is reasserted if the
fault queue fills up.
TIME
THERM
Figure 33. THERM Behavior
Rev. 0 | Page 23 of 40
04918-0-031
Bits <3:0>
000X
001X
01XX
1XXX
The ADM1034 makes up to 64 measurements per second.
However, for the sake of reduced power consumption and better
noise immunity, users may run the ADM1034 at a slower
conversion rate. Better noise immunity results from the
averaging that occurs at the slower conversion rates. Averaging
does not occur at rates of 16, 32, or 64 conversions per second.
ADM1034
Once the THERM limits are exceeded, the fans are boosted to
full speed—that is, as long as the Boost Disable Bit (Bit 1) is not
set in Configuration Register 2 (Address 0x02).
When THERM is configured as an input only, setting the Enable
THERM Events bits in Configuration Register 4 allows Pin 7 to
operate as an I/O.
To configure THERM as an input, the user must set the
THERM timer bit (Bit 2) of Configuration Register 1 (Address
0x01) to 1. (It no longer operates as an output.) The ADM1034
can then detect when the THERM input is asserted low. This
may be connected to a trip point temperature sensor or to the
FAN_FAULT PROCHOT output of a CPU. With processor core
voltages reducing all the time, the threshold for the AGTL +
PROCHOT output also reduces down as new processors
become available. The default threshold on the input is the
normal CMOS threshold. However, Pin 8 (FAN_FAULT/REF)
can also be reconfigured as a REF input. This is done by setting
Bit 7 (FAN_FAULT/REF) in Configuration Register 4 (Address
0x04). Connect the processor VCCP to this input to provide a
reference for the THERM input. The resulting THERM
threshold is 0.75×VCCP, which is the correct threshold for an
AGTL+ signal.
The user can configure the THERM pin to be pulled low as an
output whenever the local temperature exceeds the local
THERM limit. To do this, set the Enable Local THERM events
bit (Bit 0) of Configuration Register 4 (Address 0x04).
The ADM1034 also measures assertion times on the THERM
input as a percentage of a time window. This time window is
programmable in Configuration Register 4 (Address 0x04) by
using Bits <6:4> (THERM % Time Window). Values between
0.25 seconds and 8 seconds are programmable. The assertion
time as a percentage of the time window is stored in the
THERM % On-Time Register (Address 0x4E).
A THERM % limit is also associated with this register. Once the
measured percentage exceeds the percentage limit, the THERM
% Exceeded Bit (Bit 4) in Status Register 2 (Address 0x50) is
asserted and an ALERT is generated, that is, if the mask bit is
not set. If the limit is set to 0x00, an ALERT is generated on the
first assertion. If the limit is set to 0xFF, an ALERT is never
generated. This is because 0xFF corresponds to the THERM
input, which is asserted continuously.
The user can also configure the THERM pin to be pulled low as
an output whenever the Remote 1 temperature exceeds the
Remote 1 THERM limit. Set the Enable Remote 1 THERM
events bit (Bit 1) of Configuration Register 4 (Address 0x04).
The last option is to configure the THERM pin to be pulled low
as an output whenever the Remote 2 temperature exceeds the
Remote 2 THERM limit. Set the Enable Remote 2 THERM
events bit (Bit 2) of Configuration Register 4 (Address 0x04).
THERM % LIMIT REGISTER
The THERM % limit is programmed to Register 0x19. An
ALERT is generated, if THERM is asserted for longer than the
programmed percentage limit. The limit is programmed as a
percentage of the chosen time window.
THERM % limit register is an 8-bit register.
0x00 = 0%
0xFF = 100%
Therefore, 1 LSB = 0.39%.
Example
If a time window of 8 seconds is chosen, and an ALERT is to be
generated if THERM is asserted for more than 1 second,
program the following value to the limit register:
% Limit = 1/8 × 100 = 12.5%
Table 24. THERM % On-Time Window
Code
THERM % On-Time Window
000
001
010
011
100
101
110
111
0.25 s
0.5 s
1s
2s
4s
8s
8s
8s
12.5% / 0.39% = 32d = 0x20 = 0010 0000
An ALERT is generated if the THERM limit is exceeded after
the time window has elapsed, assuming it is not masked.
Rev. 0 | Page 24 of 40
ADM1034
FAN DRIVE SIGNAL
The ADM1034 controls the speed of up to two cooling fans.
Varying the duty cycle (on/off time) of a square wave applied to
the fan varies the speed of the fan. The ADM1034 uses a control
method called synchronous speed control, in which the PWM
drive signal applied to the fan is synchronized with the fan’s
TACH signal. See the Synchronous Speed Control section for
more information.
The external circuitry required to drive the fan is very simple. A
single N-channel MOSFET is the only drive device required.
The specifications of the MOSFET depend on the maximum
current required by the fan and the gate voltage drive (VGS < 3 V
for direct interfacing to the drive pin). VGS can be greater than
3 V, as long as the pull-up on the gate is tied to 5 V. The MOSFET
should also have a low on-resistance to ensure that there is no
significant voltage drop across the FET. A high on-resistance
reduces the voltage applied across the fan and therefore the
maximum operating speed of the fan. Figure 34 shows a scheme
for driving a 3-wire fan.
12V
10kΩ
10kΩ
TACH
4.7kΩ
ADM1034
TACH
12V
12V
FAN
When designing drive circuits with transistors and FETs, make
sure that the drive pins are not required to source current and
that they sink less than the maximum current specified here.
SYNCHRONOUS SPEED CONTROL
The ADM1034 drives the fan by using a control scheme called
synchronous speed control. In this scheme, the PWM drive
signal applied to the fan is synchronized with the TACH signal.
Accurate and repeatable fan speed measurements are the main
benefits. The fan is allowed to run reliably at speeds as low as
30 percent of the full capability.
The drive signal applied to the fan is synchronized with the
TACH signal. The ADM1034 switches on the drive signal and
waits for a transition on the TACH signal. When a transition
takes place on the TACH signal, the PWM drive is switched off
for a period of time called toff. The drive signal is then switched
on again. The toff time is varied in order to vary the fan speed.
If the fan is running too fast, the toff time is increased. If the fan
is running too slow, the toff time is decreased.
1N4148
Since the drive signal is synchronized with the TACH signal, the
frequency with which the fan is driven depends on the current
speed of the fan and the number of poles in it.
3.3V
04918-0-032
100kΩ
Q1
NDT3055L
DRIVE
If in doubt as to whether a fan has an open-collector or totempole TACH output, use one of the input signal conditioning
circuits shown in the Fan Inputs section.
Figure 34. Interfacing a 3-Wire Fan to the ADM1034 by Using an
N-Channel MOSFET
Figure 34 uses a 10 kΩ pull-up resistor for the TACH signal.
This assumes that the TACH signal is an open collector from
the fan. In all cases, the fan’s TACH signal must be kept below
5 V maximum to prevent damaging the ADM1034.
Figure 35 shows how the synchronous speed drive signal works.
The ideal TACH signal is the TACH signal that would be output
from the fan if power were applied 100 percent of the time. It is
representative of the actual speed of the fan. The actual TACH
signal is the signal the user would see on the TACH output from
the fan if the user were to put a scope on it. In effect, the actual
TACH signal is the ideal TACH signal chopped with the drive
signal.
POLE TRANSITION POINTS
IDEAL TACH
tPOLE
DRIVE
tOFF
DASH = TACH FLOATS HIGH BY PULL-UP RESISTOR
SOLID = TRUE TACH WHEN FAN IS POWERED
Figure 35. Drive Signal by Using Synchronous Control
Rev. 0 | Page 25 of 40
04918-0-033
ACTUAL TACH
ADM1034
The fan inputs have an input resistance of nominally 160 kΩ to
ground. This should be taken into account when calculating
resistor values.
Pin 2 and Pin 4 are TACH inputs intended for fan speed
measurement. These inputs are open-drain.
Signal conditioning on the ADM1034 accommodates the slow
rise and fall time of typical tachometer outputs. The maximum
input signal range is from 0 V to 5 V, even when VCC is less than
5 V. In the event that these inputs are supplied from fan outputs
exceeding 0 V to 5 V, either resistive attenuation of the fan
signal or diode clamping must be used to keep the fan inputs
within an acceptable range.
With a pull-up voltage of 12 V and pull-up resistor less than
1 kΩ, suitable values for R1 and R2 would be 100 kΩ and 47 kΩ.
This gives a high input voltage of 3.83 V.
12V
VCC
TACH
OUTPUT FAN(0–7)
Figure 36 to Figure 39 show examples of possible fan input
circuits. If the fan TACH has a resistive pull-up to VCC, it can
be connected directly to the fan output.
PULL-UP TYP
<1 kΩ OR
TOTEM POLE
R1
10kΩ
ZD1
ZENER*
ADM1034
FAN SPEED
COUNTER
* CHOOSE ZD1 VOLTAGE APPROXIMATELY 0.8 × VCC
5V OR 12V
FAN
04918-0-036
FAN INPUTS
VCC
Figure 38. Fan with Strong TACH. Pull-Up to >VCC or Totem-Pole Output,
Clamped with Zener and Resistor.
ADM1034
TACH X
VCC
100kΩ
TYP
12V
FAN SPEED
COUNTER
DRIVE X
R1*
TACH
OUTPUT
If the fan output has a resistive pull-up to 12 V (or another
voltage greater than 5 V), the fan output can be clamped with a
Zener diode, as shown in Figure 37. The Zener voltage should
be chosen so that it is greater than VIH but less than 5 V.
Allowing for the voltage tolerance of the Zener, a value of
between 3 V and 5 V is suitable.
5V OR 12V
FAN
VCC
ADM1034
TACH
OUTPUT
FAN SPEED
COUNTER
ZD1*
100kΩ
TYP
DRIVE X
*CHOOSE ZD1 VOLTAGE APPROXIMATELY 0.8 × VCC
04918-0-035
VCC
TACH X
ADM1034
<1 kΩ
Figure 36. Fan with TACH Pull-Up to +VCC
PULL-UP
4.7kΩ
TYP
VCC
Figure 37. Fan with TACH Pull-Up to Voltage > 5 V, Clamped with Zener Diode
If the fan has a strong pull-up (less than 1 kΩ to +12 V) or a
totem-pole output, a series resistor can be added to limit the
Zener current, as shown in Figure 38. Alternatively, a resistive
attenuator may be used, as shown in Figure 39.
FAN(0–7)
FAN SPEED
COUNTER
R2
*SEE TEXT
04918-0-037
TACH
OUTPUT
04918-0-034
PULL-UP
4.7kΩ
TYP
Figure 39. Fan with Strong TACH. Pull-Up to >VCC or Totem-Pole Output,
Attenuated with R1/R2.
FAN SPEED MEASUREMENT
The fan counter does not count the fan TACH output pulses
directly. This is because the fan may be spinning at less than
1000 rpm and it would take several seconds to accumulate a
reasonably large and accurate count. Instead, the period of the
fan revolution is measured by gating an on-chip 81.92 kHz
oscillator into the input of a 16-bit counter for one complete
revolution of the fan. Therefore, the accumulated count is
actually proportional to the fan tachometer period and inversely
proportional to the fan speed.
The number of poles in the fan must be programmed in
Configuration Register 3 (Address 0x03). Bits <3:0> set the
number of poles for Fan 1, and Bits <7:4> set the number of
poles for Fan 2. This number must be an even number only,
because there cannot be an uneven number of poles in a fan. A
TACH period is output for every two poles. Therefore, the
number of poles must be known so that the ADM1034 can
measure for a full revolution.
R1 and R2 should be chosen such that
2 V < VPULLUP × R2/(RPULLUP + R1 + R2) < 5 V
Rev. 0 | Page 26 of 40
ADM1034
Figure 40 shows the fan speed measurement period, assuming
that the fan outputs an ideal TACH signal. In reality, the TACH
signal output by the fan is chopped by the drive signal. However,
since the drive and the TACH signal are synchronized, there is
enough information available for the ADM1034 to measure the
fan speed accurately.
Example
TACH1 High Byte (Reg. 0x28) = 0x17
TACH1 Low Byte (Reg. 0x29) = 0xFF
What is Fan 1 speed in rpm?
Fan 1 TACH Reading = 0x17FF = 6143d
CLOCK
RPM = (f × 60) / Fan 1 TACH reading
IDEAL
TACH
Figure 40. Fan Speed Measurement for a 4-Pole Fan
The fan ALARM speed (Bit 6) in Status Register 3 (Address 0x51)
is set whenever the fan runs at alarm speed. This occurs if the
device is programmed to run the fan at full speed whenever the
THERM temperature limits are exceeded. The device runs at
alarm speed, for example, if the Boost Disable bit (Bit 1) of the
Configuration 2 Register (Address 0x02) is not set to 1.
These 16-bit measurements are stored in the TACH value
registers.
Table 25. TACH Value Registers
Description
TACH1 Period, LSB
TACH1 Period, MSB
TACH2 Period, LSB
TACH2 Period, MSB
Default
0xFF
0xFF
0xFF
0xFF
Fan Response Register
READING FAN SPEED
Reading back fan speeds involves a 2-register read for each
measurement. The low byte should be read first. This freezes the
high byte until both high and low byte registers have been read,
preventing erroneous fan speed measurement readings.
The fan tachometer reading registers report back the number of
12.2 µs period clocks (81.92 kHz oscillator) gated to the fan
speed counter, for one full rotation of the fan, assuming the
correct number of poles is programmed. Since the ADM1034
essentially measures the fan TACH period, the higher the count
value, the slower the actual fan speed. A 16-bit fan TACH
reading of 0xFFFF indicates that the fan has stalled or is
running very slowly (< 75 rpm).
CALCULATING FAN SPEED
Fan speed in rpm is calculated as follows. This assumes that the
number of poles programmed in the Configuration Register 3
(Address 0x03) is correct for both fans.
Fan Speed (RPM) = (81920 × 60)/Fan TACH Reading
where:
Fan TACH Reading = 16-bit Fan TACHometer Reading
Fan Speed = 800 RPM
ALARM SPEED
FAN SPEED MEASUREMENT REGISTERS
Register
0x4A
0x4B
0x4C
0x4D
RPM = (81920 × 60) / 6143
04918-0-038
FAN
MEASUREMENT
PERIOD
The ADM1034 fan speed controller operates by reading the
current fan speed, comparing it with the programmed fan
speed, and then updating the drive signal applied to the fan. The
rate at which the ADM1034 looks at and updates the drive
signal is determined by the fan response register. Different fans
have different inertias and respond to a changing drive signal
more or less quickly than others. The fan response register
allows the user to tailor the ADM1034 to a particular fan to
prevent situations like overshoot.
The user programs the number of updates the ADM1034 can
make to the drive signal per second. Table 26 lists the available
options.
Table 26. Fan Response Codes
Code
000
001
010
011
100
101
110
111
Update Rate
1.25 updates/second
2.5 updates/second = default
5 updates/second
10 updates/second
20 updates/second
40 updates/second
80 updates/second
160 updates/second
Table 27. Fan Response Register (Address 0x3C)
Bit No.
7
<6:4>
3
<2:0>
Rev. 0 | Page 27 of 40
Function
Reserved
Fan 2 Response
Reserved
Fan 1 Response
ADM1034
LOOK-UP TABLE: MODES OF OPERATION
Look-Up Table
The ADM1034 look-up table has two different modes of
operation used to determine the behavior of the system:
The ADM1034 allows the user to program a temperature-tofan-speed profile. There are 24 registers in the look-up table—
eight for temperature and 16 for target fan speed (each target
fan speed is two registers). In total, there are eight available
points. In the default configuration, four of these are for Fan 1
and four are for Fan 2. However, it can be configured such that
eight points are available and both fans run from the same table.
•
Manual mode
•
Look-up table
Manual Mode
In manual mode, the ADM1034 is under software control. The
software can program the required fan speed value or the target
fan speed to the ADM1034, which then outputs that fan speed.
Programming Target Fan Speed
In this mode, the user programs the target fan speed as a TACH
count for N poles or a TACH count for one full rotation of the
fan, assuming the number of poles is programmed correctly in
the Configuration 3 Register (Address 0x03).
Use the following steps to program the target fan speed:
1.
2.
Place the ADM1034 into manual mode. Set Bit 7
(Table/SW) of Configuration Register 1 (Address 0x01) = 0.
There are two options when programming the look-up table.
The ADM1034 can be programmed to make the fan speed run
at discrete speeds and jump to the new fan speed once the
temperature threshold is crossed. Or, it can linearly ramp the
TACH count between the two temperature thresholds.
Figure 41 and Figure 42 show what the look-up table looks like
if all eight points are used on the one curve for both fans.
Figure 41 shows the transfer curve when the fan is programmed
to run at discrete speeds. The ADM1034 spins the fan at its new
speed once a threshold is crossed.
FAN SPEED
TACH COUNT 8
TACH COUNT 7
Program the target TACH count (fan speed) using the
following equation:
TACH COUNT 6
TACH COUNT 5
TACH COUNT 4
TACH Count = (f × 60)/R
TACH COUNT 3
where:
TACH COUNT 2
f = clock frequency = 81.92 kHz
R = required RPM value
T1
Example 1: If the desired speed for Fan 1 is 5000 rpm, program
the following value to the TACH count registers:
TACH Count = (f × 60)/5000
TACH Count = 983d = 0x03D7
Example 2: If the desired speed for Fan 2 is 3500 rpm, program
the following value to the TACH pulse period registers:
T5
T6
T7
T8
TEMPERATURE
FAN SPEED
TACH Count = 1404d = 0x057C
TACH COUNT 6
TACH COUNT 5
TACH COUNT 4
TACH COUNT 3
Address
0x2A
0x2B
0x2C
0x2D
Value
0xD7
0x03
0x7C
0x05
TACH COUNT 2
TACH COUNT 1
T1
T2
T3
T4
T5
T6
T7
T8
TEMPERATURE
Figure 42. Programming the Look-Up Table in Linear Fan Speeds Mode
Rev. 0 | Page 28 of 40
04918-0-040
Description
Look-Up Table FS1, LSB
Look-Up Table FS1, MSB
Look-Up Table FS2, LSB
Look-Up Table FS2, MSB
T4
Figure 42 shows the transfer curve if the Linear Fan Speeds
option is chosen. At temperature T1, the fan runs at Fan Speed 1.
As the temperature increases, the fan speed increases until it
reaches Fan Speed 2 at T2.
TACH COUNT 8
TACH COUNT 7
Fan
Fan 1
Fan 1
Fan 2
Fan 2
T3
Figure 41. Programming the Look-Up Table in Discreet Fan Speeds Mode
TACH Count = (f × 60)/3500
Table 28. Registers to be Programmed
T2
04918-0-039
TACH COUNT 1
ADM1034
Once the temperature exceeds the highest temperature point in
the look-up table, the fan speed remains at the highest speed
until the temperature drops below the T7 temperature value.
When the look-up table is split in two, the same applies.
SETTING UP THE SIZE OF THE LOOK-UP TABLE
If the temperatures in T1 to T8 are not programmed in
succession, the fan speed moves to the next highest programmed temperature as the temperature increases. Similarly,
when the temperature decreases, it ignores programmed higher
temperatures and jumps to the next lower temperature. Therefore, the temperature-to-fan-speed profile for increasing and
decreasing temperature can be different.
When 4:8 Look-Up (Bit 3) is set to 1, all eight points on the
table are used for both fans.
When programming the look-up table, the user has the option
to use between two and eight points for each fan (eight points
only if the same curve is to be used for both fans). If the user
just wants to program a transfer curve (and knows the starting
temperature, minimum speed, maximum temperature, and
maximum speed), then all the user needs to program are four
parameters—T1, T2, FS1, and FS2. The remainder of the lookup temperature thresholds should remain at their default values
of +191°C. If required, the FS3 should be programmed with the
same value as FS2 to give the flat curve, if required. Or, the fan
speeds can be left at the default value of 0. However, it is normal
to program a THERM limit as well. Once this temperature is
exceeded and the boost bit is set, the fans run to full speed. This
overrides the look-up table.
When 4:8 Look-Up (Bit 3)is set to 0 (default), four points are
used for each fan.
SETTING UP THE LOOK-UP TABLE IN
LINEAR MODE
When Discrete/Linear Speed (Bit 2) is set to 1 (default), the
TACH count decreases linearly (and therefore the fan speed
increases) with temperature.
Example: At temperature TX, the fans run at FSX and fan speed
increases with temperature to FSX+1 at temperature TX+1.
Alternatively, the fan can be run at discrete fan speeds. When
Discrete/Linear Speed (Bit 2) is set to 0, the fan runs at a new
speed once the temperature threshold is exceeded.
SETTING WHICH TEMPERATURE
CHANNEL CONTROLS A FAN
Fan Behavior Register (Address 0x07)
Bits <1:0> = DRIVE1 Behavior (D1B)
Bits <3:2> = DRIVE2 Behavior (D2B)
The ADM1034 can be configured so that Fan 1 or Fan 2 can be
controlled by either the local temperature, or by the Remote 1
or Remote 2 temperatures.
FAN SPEED
TACH COUNT 2 TO 8
Table 30. Drive X BHVR Bits
Bits
00
01
10
11
T1
T2
T (3 TO 8) = °C
TEMPERATURE
Figure 43. Programming Two Points on the Look-Up Table
Table 29. Look-Up Table Register Addresses
x
1
2
3
4
5
6
7
8
Temperature, x
0x22
0x23
0x24
0x25
0x26
0x27
0x28
0x29
FSx, LSB
0x2A
0x2C
0x2E
0x30
0x32
0x34
0x36
0x38
FSx, MSB
0x2B
0x2D
0x2F
0x31
0x33
0x35
0x37
0x39
04918-0-041
TACH COUNT 1
DRIVE x BHVR
Local Temperature Controls Fan x
Remote 1 Temperature Controls Fan x
Remote 2 Temperature Controls Fan x
Fan x Runs at Full Speed
By default, Remote 1 controls Fan 1, and Remote 2 controls
Fan 2. If the ADM1034 is in single-channel mode and one of the
fans is set up to run from a temperature channel that is not being
measured, the drive X BHVR bits are set to 11 and the fan is run
at full speed.
LOOK-UP TABLE HYSTERESIS
The user can program a hysteresis to be applied to the look-up
table. The advantage of this is apparent if the temperature is
cycling around one of the threshold temperatures and causing
the fan speed to switch between the two speeds, particularly
when the look-up table is configured in discrete mode. It would
not be as important in the linear mode.
Rev. 0 | Page 29 of 40
ADM1034
Programming the Look-Up Table Hysteresis
Table 33. Programming THERM Hysteresis
The look-up table’s hysteresis register is at Address 0x3A. A
hysteresis value of between 0°C and 15°C can be programmed
with a resolution of 1°C and applied to all the temperature
thresholds. Table 31 gives examples of values for programming.
Code
0000 0000
0000 0001
0000 0010
0000 0101
0000 1000
0000 1111
Table 31. Programming the Hysteresis
Hysteresis Value
0°C
1°C
2°C
5°C = Default
8°C
15°C
XOR TREE TEST MODE
PROGRAMMING THE THERM LIMIT FOR
EACH TEMPERATURE CHANNEL
THERM is the absolute maximum temperature allowed on a
temperature channel. Above this temperature, a component
such as the CPU or VRM may be operating beyond its safe
operating limit. When the temperature measured exceeds
THERM, all fans are driven at full speed to provide critical
system cooling. The fans remain running at full speed until the
temperature drops below THERM – Hysteresis. The hysteresis
value is programmable; its default is 5°C. If the Boost Disable bit
(Bit 1) is set in Configuration Register 2, the fans do not run to
full speed.
The THERM limit is considered the maximum worst-case
operating temperature of the system. Exceeding any THERM
limit runs all fans at full speed, a condition with very negative
acoustic effects. This limit should be set up as a fail-safe and not
exceeded under normal system operating conditions.
The THERM temperature limit registers are listed in Table 32.
Table 32. THERM Hysteresis Registers
Address
0x0D
0x10
0x13
Description
Local THERM Limit
Remote 1 THERM Limit
Remote 2 THERM Limit
Default
0x95 (85°C)
0x95 (85°C)
0x95 (85°C)
The THERM hysteresis register is at Address 0x1A. A hysteresis
value is programmed and applied to all three temperature
channels—Local, Remote 1, and Remote 2. A THERM hysteresis
value of between 0°C and 15°C can be programmed with a
resolution of 1°C. Table 33 gives some examples.
The ADM1034 includes an XOR tree test mode. This is useful
for in-circuit test equipment at board-level testing. By applying
stimulus to the pins included in the XOR test, it is possible to
detect opens or shorts on the system board. Figure 44 shows the
signals that are exercised in the XOR tree test mode. The XOR
tree test is enabled by setting the XOR bit (Bit 3) in Configuration 4 Register (0x04).
TACH1
DRIVE2
THERM
FAN_FAULT/REF
LOCATION
ALERT
DRIVE1
04918-0-042
Code
0000 0000
0000 0001
0000 0010
0000 0101
0000 1000
0000 1111
Hysteresis Value
0°C
1°C
2°C
5°C = Default
8°C
15°C
Figure 44. XOR Tree Test
LOCK BIT
Setting the Lock bit (Bit 6) of Configuration Register 1
(Address 0x01) makes all the lockable registers read-only. These
registers remain read-only until the ADM1034 is powered down
and back up again. For more information on which registers are
lockable, see Table 34.
SW RESET
Setting the Software Reset bit (Bit 0) of Configuration Register 1
(Address 0x01) resets all software-resettable bits to their default
value. For more information on resetting registers and their
default values, see Table 34 to Table 74.
Rev. 0 | Page 30 of 40
ADM1034
Table 34. ADM1034 Registers
Address
0x00/80
0x01/81
0x02/82
0x03/83
0x04/84
0x05/85
0x06/86
0x07/87
0x08/88
0x09/89
0x0A/8A
0x0B/8B
0x0C/8C
0x0D/8D
0x0E/8E
0x0F/8F
0x10/90
0x11/91
0x12/92
0x13/93
0x16/96
0x17/97
0x18/98
0x19/99
0x1A/9A
0x22/A2
0x23/A3
0x24/A4
0x25/A5
0x26/A6
0x27/A7
0x28/A8
0x29/A9
0x2A/AA
0x2B/AB
0x2C/AC
0x2D/AD
0x2E/AE
0x2F/AF
0x30/B0
0x31/B1
0x32/B2
0x33/B3
0x34/B4
0x35/B5
0x36/B6
0x37/B7
0x38/B8
0x39/B9
0x3A/BA
0x3C/BC
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Description
#Bytes/Block Read
Configuration 1
Configuration 2
Configuration 3
Configuration 4
Conversion Rate
Fault Queue
Fan Behavior
Mask 1
Mask 2
Mask 3
Local High Limit
Local Low Limit
Local THERM Limit
Remote 1 High Limit
Remote 1 Low Limit
Remote 1 THERM Limit
Remote 2 High Limit
Remote 2 Low Limit
Remote 2 THERM Limit
Local Offset
Remote 1 Offset
Remote 2 Offset
THERM % Limit
THERM Hysteresis
Look-Up Table T1
Look-Up Table T2
Look-Up Table T3
Look-Up Table T4
Look-Up Table T5
Look-Up Table T6
Look-Up Table T7
Look-Up Table T8
Look-Up Table, FS1
Look-Up Table, FS1
Look-Up Table, FS2
Look-Up Table, FS2
Look-Up Table, FS3
Look-Up Table, FS3
Look-Up Table, FS4
Look-Up Table, FS4
Look-Up Table, FS5
Look-Up Table, FS5
Look-Up Table, FS6
Look-Up Table, FS6
Look-Up Table, FS7
Look-Up Table, FS7
Look-Up Table, FS8
Look-Up Table, FS8
Look-Up Table Hysteresis
Fan Response
Bit 7
7
Table/SW
RR
#FP2
FF/ REF
RES
RES
F2 Off
LH
RES
F1S
7
7
7
7
7
7
7
7
7
7
7
7
7
RES
7
7
7
7
7
7
7
7
7
15
7
15
7
15
7
15
7
15
7
15
7
15
7
15
RES
RES
Bit 6
6
Lock
RES
#FP2
%T
RES
RES
F1 Off
LL
RES
FA
6
6
6
6
6
6
6
6
6
6
6
6
6
RES
6
6
6
6
6
6
6
6
6
14
6
14
6
14
6
14
6
14
6
14
6
14
6
14
RES
F2
Bit 5
5
SDA
CS
#FP2
%T
RES
RES
RES
R1H
RES
F2S
5
5
5
5
5
5
5
5
5
5
5
5
5
RES
5
5
5
5
5
5
5
5
5
13
5
13
5
13
5
13
5
13
5
13
5
13
5
13
RES
F2
Bit 4
4
SCL
CS
#FP2
%T
RES
RES
RES
R1L
%T
RES
4
4
4
4
4
4
4
4
4
4
4
4
4
RES
4
4
4
4
4
4
4
4
4
12
4
12
4
12
4
12
4
12
4
12
4
12
4
12
RES
F2
Rev. 0 | Page 31 of 40
Bit 3
3
ALERT
LUT
#FP1
XOR
Conv
FQ
D2B
R1D
TA
RES
3
3
3
3
3
3
3
3
3
3
3
3
3
Hys
3
3
3
3
3
3
3
3
3
11
3
11
3
11
3
11
3
11
3
11
3
11
3
11
Hys
RES
Bit 2
2
TIMER
D/L
#FP1
R2TM
Conv
FQ
D2B
R2H
TS
RES
2
2
2
2
2
2
2
2
2
2
2
2
2
Hys
2
2
2
2
2
2
2
2
2
10
2
10
2
10
2
10
2
10
2
10
2
10
2
10
Hys
F1
Bit 1
1
Avg
BD
#FP1
R1TM
Conv
FQ
D1B
R2L
RES
RES
1
1
1
1
1
1
1
1
1
1
1
1
1
Hys
1
1
1
1
1
1
1
1
1
9
1
9
1
9
1
9
1
9
1
9
1
9
1
9
Hys
F1
Bit 0
0
Mon
Reset
#FP1
LTM
Conv
FQ
D1B
R2D
RES
RES
0
0
0
0
0
0
0
0
0
0
0
0
0
Hys
0
0
0
0
0
0
0
0
0
8
0
8
0
8
0
8
0
8
0
8
0
8
0
8
Hys
F1
Default
0x20
0x01
0x84
0x44
0x00
0x07
0x01
0x09
0x52
0x10
0x00
0x8B
0x54
0x95
0x8B
0x54
0x95
0x8B
0x54
0x95
0x00
0x00
0x00
0xFF
0x05
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0x05
0x11
Lockable?
Y
Y
Y
Y
Y
Y
Y
Y
N
N
N
N
N
Y
N
N
Y
N
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
ADM1034
Address
0x3D/BD
0x3E/BE
0x3F/BF
0x40/C0
0x41/C1
0x42/C2
0x43/C3
0x44/C4
0x45/C5
0x4A/CA
0x4B/CB
0x4C/CC
0x4D/CD
0x4E/CE
0x4F/CF
0x50/D0
0x51/D1
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Description
Device ID
Company ID
Revision Register
Local Temperature
Local Temperature
Remote 1 Temperature
Remote 1 Temperature
Remote 2 Temperature
Remote 2 Temperature
TACH1 Period
TACH1 Period
TACH2 Period
TACH2 Period
THERM % Ontime
Status 1
Status 2
Status 3
Bit 7
7
7
7
4
12
4
12
4
12
7
15
7
15
7
LH
LT
F1S
Bit 6
6
6
6
3
11
3
11
3
11
6
14
6
14
6
LL
R1T
FA
Bit 5
5
5
5
2
10
2
10
2
10
5
13
5
13
5
R1H
R2T
F2S
Bit 4
4
4
4
1
9
1
9
1
9
4
12
4
12
4
R1L
%T
RES
Bit 3
3
3
3
0
8
0
8
0
8
3
11
3
11
3
R1D
TA
RES
Bit 2
2
2
2
RES
7
RES
7
RES
7
2
10
2
10
2
R2H
TS
RES
Bit 1
1
1
1
RES
6
RES
6
RES
6
1
9
1
9
1
R2L
RES
RES
Bit 0
0
0
0
RES
5
RES
5
RES
5
0
8
0
8
0
R2D
RES
ALERT
Default
0x34
0x41
0x02
0x00
0x00
0x00
0x00
0x00
0x00
0xFF
0xFF
0xFF
0xFF
0x00
0x00
0x00
0x00
Lockable?
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
Table 35. Register 0x00, # Bytes/Block Read, POR = 0x20, Lock = Y, S/W Reset =Y
Bit
<7:0>
Name
# Bytes Block Read
R/W
R/W
Description
Block reads are # bytes/block read long. The maximum is 32 bytes, the SMBus transaction limit.
Table 36. Register 0x01, Configuration Register 1, Power-On Default 0x01, Lock = Y, SW Reset = Y
Bit
7
Name
Table/SW Con
R/W
R/W
6
Lock Bit
R/W
5
4
3
2
1
SDA Timeout
SCL Timeout
ALERT Configuration
Enable THERM Timer
Averaging Off
R/W
R/W
R/W
R/W
R/W
0
Monitor/STBY
R/W
Description
Set this bit to 1 to place the fan speed under the control of the look-up table. When this bit is 0, the
ADM1034 is in software/manual control mode. Default = 0.
Set this bit to 1 to prevent the user from writing to the ADM1034 registers. 1 = ADM1034 registers
locked. 0 = ADM1034 registers unlocked. Default = 0.
1 = SDA timeout enabled. 0 = SDA timeout disabled. Default = 0.
1 = SCL timeout enabled. 0 = SDL timeout disabled. Default = 0.
0 = SMBusALERT. Default = 0. 1 = ALERT_COMP mode.
1 = timer enabled, 0 = timer disabled. This bit enables THERM as an input. Default = 0.
This bit is used to disable averaging at the slower conversion rates (8 Hz and slower). Averaging is
automatically disabled at the higher (16, 32, and 64 Hz ) conversion rates. Default = averaging on =
0.
Set bit to 1 to enable temperature monitoring. Set bit to 0 to disable it. Power-On Default = 1
Table 37. Register 0x02, Configuration Register 2, Power-On Default 0x84, Lock = Y, SW Reset = Y
Bit
7
Name
Round Robin
R/W
R/W
6
<5:4>
Reserved
Channel Selector
R/W
R/W
3
4:8 Look-Up Table
R/W
2
Discrete/Linear
R/W
Description
This bit enables the round-robin mode. Set this bit to 0 to put the ADM1034 in single-channel
mode. The ADC converts on one channel only, which is determined by the channel selector bits.
Default = Round Robin = 1.
Reserved.
This bit determines the channel on which the ADC converts.
00 = Local Channel Only
01 = Remote 1 Channel Only
10 = Remote 2 Channel Only
11 = Reserved
This bit determines how many table points are used to control each fan.
0 = 4 table points for each fan
1 = all 8 points on one table; this table is used to control both fans
This bit determines whether the fans run at discrete speeds or at speeds that increase with
Rev. 0 | Page 32 of 40
ADM1034
Bit
1
Name
Speed
Boost Disable
R/W
R/W
0
SW Reset
R/W
Description
temperature between the two thresholds. Default = 1 = Linear.
Set bit to 1 to prevent the fans from being boosted if either THERM temperature or THERM timer
limits are exceeded. Under these conditions, the fan runs at the previously calculated speed. Default
= 0.
Set this bit to 1 to reset the ADM1034 registers to their default values, excluding the limit registers,
offset registers, and look-up table registers. This bit self-clears. Default = 0.
Table 38. Register 0x03, Configuration Register 3, Power-On Default= 0x44, Lock = Y, SW Reset = Y
Bit
<7:4>
Name
#Poles Fan 2
R/W
R/W
<3:0>
#Poles Fan 1 1
R/W
Description
Write the number of poles on Fan 2 to this register. power-on default = 4 poles = 100. This should
always be an even number, because there cannot be an odd number of poles in a fan.
Write the number of poles in Fan 1 to this register. power-on default = 4 poles = 100. This should
always be an even number, because there cannot be an odd number of poles in a fan.
Table 39. Register 0x04, Configuration Register 4, Power-On Default = 0x00, Lock = Y, SW Reset = Y
Bit
7
Name
FAN_FAULT/REF
R/W
R/W
<6:4>
THERM % Time Window
R/W
3
2
XOR Test
Enable Remote 2 THERM Events
R/W
R/W
1
Enable Remote 1 THERM Events
R/W
0
Enable Local THERM Events
R/W
Description
This bit sets the function for Pin 8. 0 = Default = FAN_FAULT output (THERM input
is CMOS). 1 = Reference input for THERM.
These bits set the time window over which THERM % is calculated.
000 = 0.25 second
001 = 0.5 second
010 = 1 second
011 = 2 seconds
100 = 4 seconds
101 = 8 seconds
110 = 8 seconds
111 = 8 seconds
Set this bit to 1 to enable the XOR connectivity test.
This bit enables THERM assertions as an output. Functions when the THERM timer
is enabled and the Remote 2 temperature exceeeds its THERM limit.
This bit enables THERM assertions as an output. Functions when the THERM timer
is enabled and the Remote 1 temperature exceeeds its THERM limit.
This bit enables THERM assertions as an output. Functions when the THERM timer
is enabled and the local temperature exceeeds its THERM limit.
Table 40. Register 0x05, Conversion Rate Register, Power-On Default = 0x07, Lock = Y, SW Reset = Y
Bit
7
<6:4>
<3:0>
Name
Res
Res
Conversion Rate
R/W
R
R
R/W
Description
This bit is reserved for future use. Do not write to this bit.
Reserved.
These four bits set the conversion rate of the ADM1034. Changing these bits does not update the
conversion rate until the start of the next round robin.
0000 = 0.0625 conversions/second
0001 = 0.125 conversions/second
0010 = 0.25 conversions/second
0011 = 0.5 conversions/second
0100 = 1 conversion/second
0101 = 2 conversions/second
0110 = 4 conversions/second
0111 = 8 conversions/second = default
1000 = 16 conversions/second
1001 = 32 conversions/second
1010 = 64 conversions/second
Rev. 0 | Page 33 of 40
ADM1034
Table 41. Register 0x06, Fault Queue, Power-On Default = 0x01, Lock = Y, SW Reset = Y
Bit
<7:4>
<3:0>
Name
Unused
Fault Queue Length
R/W
R
R/W
Description
Reserved.
These four bits set the fault queue (the number of out-of-limit measurements made before an
ALERT is generated).
000x = 1
001x = 2
01xx = 3
1xxx = 4
Table 42. Register 0x07, Fan Behavior Register, Power-On Default = 0x09, Lock = Y, SW Reset = Y
Bit
7
6
5
4
<3:2>
Name
Fan2 Off
Fan1 Off
Res
Res
DRIVE2 BHVR
R/W
R/W
R
R
R
R/W
<1:0>
DRIVE1 BHVR
R/W
Description
Set this bit to 1 to switch off Fan 2.
Set this bit to 1 to switch off Fan 1.
Reserved.
Reserved.
These bits determine which temperature source controls the DRIVE2 output.
00 = Local temperature controls DRIVE2.
01 = Remote 1 temperature controls DRIVE2.
10 = Remote 2 temperature controls DRIVE2.
11 = DRIVE2 full speed.
These bits determine which temperature source controls the DRIVE1 output.
00 = Local temperature controls DRIVE1.
01 = Remote 1 temperature controls DRIVE1.
10 = Remote 2 temperature controls DRIVE1.
11 = DRIVE1 full speed.
Table 43. Register 0x08, Mask Register 1, Power-On Default = 0x52, Lock = N, SW Reset = Y
Bit
7
Name
Local High
R/W
R/W
6
Local Low
R/W
5
Remote 1 High
R/W
4
Remote 1 Low
R/W
3
Remote 1 Diode Error
R/W
2
Remote 2 High
R/W
1
Remote 2 Low
R/W
0
Remote 2 Diode Error
R/W
Description
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set.
The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set.
The status bit is not affected. Default = 1.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set.
The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set.
The status bit is not affected. Default = 1.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set.
The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set.
The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set.
The status bit is not affected. Default = 1.
A 1 disables the corresponding interrupt status bit from causing the interrupt output to be set.
The status bit is not affected. Default = 0.
Rev. 0 | Page 34 of 40
ADM1034
Table 44. Register 0x09, Mask Register 2, Power-On Default = 0x10, Lock = N, SW Reset = Y
Bit
<7:5>
4
Name
Unused
THERM %
R/W
R
R/W
3
THERM Assert
R/W
2
THERM_State
R/W
<1:0>
Unused
R
Description
Unused.
A 1 disables the corresponding interrupt status bit, preventing it from causing the interrupt output.
The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit, preventing it from causing the interrupt output.
The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit, preventing it from causing the interrupt output.
The status bit is not affected. Default = 0. This bit has no effect in ALERT comparator mode, because
the corresponding status bit does not generate an ALERT in that mode.
Unused.
Table 45. Register 0x0A, Mask Register 3, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
7
Name
Fan 1 Stalled
R/W
R/W
6
Fan Alarm Speed
R/W
5
Fan 2 Stalled
R/W
4
3
2
1
0
Reserved
Reserved
Reserved
Reserved
Reserved
R
R
R
R
R
Description
A 1 disables the corresponding interrupt status bit, preventing it from causing the interrupt output.
The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit, preventing it from causing the interrupt output.
The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit, preventing it from causing the interrupt output.
The status bit is not affected. Default = 0.
Reserved. Default = 0.
Reserved. Default = 0.
Reserved. Default = 0.
Reserved. Default = 0.
Reserved. Default = 0.
Table 46. Register 0x0B, Local High Limit, Power-On Default = 0x8B, Lock = N, SW Reset = N
Bit
<7:0>
Name
Local High Limit
R/W
R/W
Description
When the local temperature exceeds this temperature, the corresponding interrupt status bit is set.
Table 47. Register 0x0C ,Local Low Limit, Power-On Default = 0x54, Lock = N, SW Reset = N
Bit
<7:0>
Name
Local Low Limit
R/W
R/W
Description
When the local temperature falls below this temperature, the corresponding interrupt status bit is
set.
Table 48. Register 0x0D, Local THERM Limit, Power-On Default = 0x95, Lock = Y, SW Reset = N
Bit
<7:0>
Name
Local THERM Limit
R/W
R/W
Description
When the local temperature exceeds this temperature, the corresponding status bit is set and the
THERM output is activated.
Table 49. Register 0x0E, Remote 1 High Limit, Power-On Default = 0x8B, Lock = N, SW Reset = N
Bit
<7:0>
Name
Remote 1 High Limit
R/W
R/W
Description
When the Remote 1 temperature exceeds this temperature, the corresponding interrupt status bit
is set.
Table 50. Register 0x0F, Remote 1 Low Limit, Power-On Default = 0x54, Lock = N, SW Reset = N
Bit
<7:0>
Name
Remote 1 Low Limit
R/W
R/W
Description
When the Remote 1 temperature falls below this temperature, the corresponding interrupt status
bit is set.
Rev. 0 | Page 35 of 40
ADM1034
Table 51. Register 0x10, Remote 1 THERM Limit, Power-On Default = 0x95, Lock = Y, SW Reset = N
Bit
<7:0>
Name
Remote 1 THERM Limit
R/W
R/W
Description
When the Remote 1 temperature exceeds this temperature, the corresponding status bit is set
and the THERM output is activated.
Table 52. Register 0x11, Remote 2 High Limit, Power-On Default = 0x8B, Lock = N, SW Reset = N
Bit
<7:0>
Name
Remote 2 High Limit
R/W
R/W
Description
When the Remote 2 temperature exceeds this temperature, the corresponding interrupt status
bit is set.
Table 53. Register 0x12, Remote 2 Low Limit, Power-On Default = 0x54, Lock = N, SW Reset = N
Bit
<7:0>
Name
Remote 2 Low Limit
R/W
R/W
Description
When the Remote 2 temperature falls below this temperature, the corresponding interrupt
status bit is set.
Table 54. Register 0x13, Remote 2 THERM Limit, Power-On Default = 0x95, Lock = Y, SW Reset = N
Bit
<7:0>
Name
Remote 2 THERM Limit
R/W
R/W
Description
When the Remote 2 temperature exceeds this temperature, the corresponding status bit is set
and the THERM output is activated.
Table 55. Register 0x16, Local Offset Register, Power-On Default = 0x00, Lock = Y, SW Reset = N
Bit
<7:0>
Name
Local Offset
R/W
R/W
Description
Allows a twos compliment offset to be automatically added to or subtracted from the local
temperature measurement. Resolution = 0.125°C. Maximum offset from −16°C to +15.875°C.
Default = 0.
Table 56. Register 0x17, Remote 1 Offset Register, Power-On Default = 0x00, Lock = Y, SW Reset = N
Bit
<7:0>
Name
Remote 1 Offset
R/W
R/W
Description
Allows a twos compliment offset to be automatically added to or subtracted from the Remote
1 temperature measurement. Resolution = 0.125°C. Maximum offset from −16°C to +15.875°C.
Default = 0.
Table 57. Register 0x18, Remote 2 Offset Register, Power-On Default = 0x00, Lock = Y, SW Reset = N
Bit
<7:0>
Name
Remote 2 Offset
R/W
R/W
Description
Allows a twos compliment offset to be automatically added to or subtracted from the Remote
2 temperature measurement. Resolution = 0.125°C. Maximum offset from −16°C to +15.875°C.
Default = 0.
Table 58. Register 0x19, THERM Timer % Limit, Power-On Default = 0xFF, Lock = Y, SW Reset = N
Bit
<7:0>
Name
THERM Timer on%
Limit
R/W
R/W
Description
If the THERM is asserted for greater than this limit on the time window, the corresponding
status bit is set.
Table 59. Register 0x1A, THERM Hysteresis, Power-On Default = 0x05, Lock = Y, SW Reset = N
Bit
<7:4>
<3:0>
Name
Reserved
THERM Hysteresis
R/W
R
R/W
Description
Reserved.
An unsigned THERM hysteresis value, LSB = 1°C. Once THERM has been activated on a
temperature channel, the THERM limit – hysteresis is deactivated if the temperature drops
below THERM.
Rev. 0 | Page 36 of 40
ADM1034
Table 60. Look-Up Table Registers, Lock = Y, SW Reset = Y
Register Address
0x22
0x23
0x24
0x25
0x26
0x27
0x28
0x29
0x2A
0x2B
0x2C
0x2D
0x2E
0x2F
0x30
0x31
0x32
0x33
0x34
0x35
0x36
0x37
0x38
0x39
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Description
Look-Up Table, T1
Look-Up Table, T2
Look-Up Table, T3
Look-Up Table, T4
Look-Up Table, T5
Look-Up Table, T6
Look-Up Table, T7
Look-Up Table, T8
Look-Up Table, FS1, LSB
Look-Up Table, FS1, MSB
Look-Up Table, FS2, LSB
Look-Up Table, FS2, MSB
Look-Up Table, FS3, LSB
Look-Up Table, FS3, MSB
Look-Up Table, FS4, LSB
Look-Up Table, FS4, MSB
Look-Up Table, FS5, LSB
Look-Up Table, FS5, MSB
Look-Up Table, FS6, LSB
Look-Up Table, FS6, MSB
Look-Up Table, FS7, LSB
Look-Up Table, FS7, MSB
Look-Up Table, FS8, LSB
Look-Up Table, FS8, MSB
Power-On Default
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
Table 61. Register 0x3A, Look-Up Table Hysteresis, Power-On Default = 0x05 Lock = Y, SW Reset = Y
Bit
<7:4>
<3:0>
Name
Reserved
Look-up Table Hysteresis
R/W
R
R/W
Description
Reserved.
These bits determine the hysteresis applied to the temperature thresholds in the look-up
table. LSB size = 1°C.
Table 62. Register 0x3C, Fan Response Register, Power-On Default = 0x11, Lock = Y, SW Reset = Y
Bit
7
<6:4>
Name
Res
Fan 2 Response
R/W
R
R/W
3
<2:0>
Res
Fan 1 Response
R
R/W
Description
Reserved.
These bits set the fan’s response in the fan speed control mode.
000 = 1.25 updates/second
001 = 2.5 updates/second = Default
010 = 5 updates/second
011 = 10 updates/second
100 = 20 updates/second
101 = 40 updates/second
110 = 80 updates/second
111 = 160 updates/second
Reserved.
These bits set the fan’s response in the fan speed control mode.
000 = 1.25 updates/second
001 = 2.5 updates/second = Default
010 = 5 updates/second
011 = 10 updates/second
100 = 20 updates/second
101 = 40 updates/second
110 = 80 updates/second
111 = 160 updates/second
Rev. 0 | Page 37 of 40
ADM1034
Table 63. Register 0x3D, Device ID, Power-On Default = 0x34, Lock = N, SW Reset = N
Bit
<7:0>
Name
Device ID
R/W
R
Description
This read-only value contains the device ID, which is 0x34.
Table 64. Register 0x3E, Company ID, Power-On Default = 0x41, Lock = N, SW Reset = N
Bit
<7:0>
Name
Company ID
R/W
R
Description
This read-only value contains the company ID, which is 0x41.
Table 65. Register 0x3F, Revision Register, Power-On Default = 0x02, Lock = N, SW Reset = N
Bit
<7:0>
Name
Revision ID
R/W
R
Description
This read-only value contains the revision ID.
Table 66. Register 0x40/41, Local Temp Registers, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
<4:0>
<12:5>
Name
Local Temperature
LSB
Local Temperature
MSB
R/W
R
R
Description
This register contains the LSBs of the last measured local temperature value.
Resolution = 0.03125°C.
This register contains the MSBs of the last measured local temperature value.
Resolution = 1°C.
Table 67. Register 0x42/43, Remote 1 Temp Registers, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
<4:0>
<12:5>
Name
Remote 1 Temperature
LSB
Remote 1 Temperature
MSB
R/W
R
R
Description
This register contains the LSBs of the last measured Remote 1 temperature value. Resolution =
0.03125°C.
This register contains the LSBs of the last measured Remote 1 temperature value. Resolution =
1°C.
Table 68. Register 0x44/45, Remote 2 Temp Registers, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
<4:0>
<12:5>
Name
Remote 2 Temperature
LSB
Remote 2 Temperature
MSB
R/W
R
R
Description
This register contains the LSBs of the last measured Remote 2 temperature value. Resolution =
0.03125°C.
This register contains the MSBs of the last measured Remote 2 temperature value. Resolution =
1°C.
Table 69. Register 0x4A/4B, TACH1 Period, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
<7:0>
<15:8>
Name
Fan 1 Period Count, LSB
Fan 1 Period Count, MSB
R/W
R
R
Description
This register contains the LSBs of the last measured Fan 1 revolution count.
This register contains the MSBs of the last measured Fan 1 revolution count.
Table 70. Register 0x4C/4D, TACH2 Period, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
<7:0>
<15:8>
Name
Fan 2 Period Count, LSB
Fan 2 Period Count, MSB
R/W
R
R
Description
This register contains the LSBs of the last measured Fan 2 revolution count.
This register contains the MSBs of the last measured Fan 2 revolution count.
Table 71. Register 0x4E, THERM % On-Time, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
<7:0>
Name
THERM % On-Time
R/W
R
Description
Represents the % time of THERM activity within the time window set by the configuration bits.
Rev. 0 | Page 38 of 40
ADM1034
Table 72. Register 0x4F, Status 1, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
7
6
5
4
3
Name
Local Temp High
Local Temp Low
Remote 1 Temp High
Remote 1 Temp Low
Remote 1 Diode Error
R/W
R
R
R
R
R
2
1
0
Remote 2 Temp High
Remote 2 Temp Low
Remote 2 Diode Error
R
R
R
Description
A 1 indicates that the local high limit has been tripped.
A 1 indicates that the local low limit has been tripped.
A 1 indicates that the Remote 1 high limit has been tripped.
A 1 indicates that the Remote 1 low limit has been tripped.
A 1 indicates that a short or an open has been detected on the Remote 1 temperature channel.
This test is completed once on each conversion.
A 1 indicates that the Remote 2 high limit has been tripped.
A 1 indicates that the Remote 2 low limit has been tripped.
A 1 indicates that a short or an open has been detected on the Remote 2 temperature channel.
This test is completed once on each conversion.
Table 73. Register 0x50, Status 2, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
7
6
5
4
Name
Local THERM
Remote 1 THERM
Remote 2 THERM
THERM % Exceeded
R/W
R
R
R
R
3
2
1
0
THERM Asserted
THERM_State
Reserved
Reserved
R
R
R
R
Description
A 1 indicates that the local THERM limit has been tripped.
A 1 indicates that the Remote 1 THERM limit has been tripped.
A 1 indicates that the Remote 2 THERM limit has been tripped.
A 1 indicates that the THERM signal has been asserted for longer than the programmed limit.
Clear on Read. If THERM % Limit = 0x00 and THERM is asserted, it is reasserted immediately.
A 1 indicates that the THERM signal has been asserted low as an input only.
A 1 indicates that the THERM pin has been asserted low as an output.
Reserved.
Reserved.
Table 74. Register 0x51, Status Register 3, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
7
6
Name
Fan 1 Stalled
Fan Alarm Speed
R/W
R
R
5
4
3
2
1
0
Fan 2 Stalled
Reserved
Reserved
Reserved
Reserved
ALERT Low
R
R
R
R
R
R
Description
A 1 indicates that Fan 1 has stalled.
A 1 indicates that the fans are running at full speed due to an alarm condition, for instance, when
a THERM temperature limit is exceeded.
A 1 indicates that Fan 2 has stalled.
Reserved.
Reserved.
Reserved.
Reserved.
A 1 indicates that the ADM1034 has pulled the ALERT output pin low. This allows polling of a
single status register to determine if an ALERT condition in any of the status registers has
occurred.
Rev. 0 | Page 39 of 40
ADM1034
OUTLINE DIMENSIONS
0.193
BSC
9
16
0.154
BSC
1
0.236
BSC
8
PIN 1
0.069
0.053
0.065
0.049
0.010
0.025
0.004
BSC
COPLANARITY
0.004
0.012
0.008
SEATING
PLANE
0.010
0.006
8°
0°
0.050
0.016
COMPLIANT TO JEDEC STANDARDS MO-137AB
Figure 45. 16-Lead Shrink Small Outline Package [QSOP]
(RQ-16)
Dimensions shown in inches
ORDERING GUIDE
Model
ADM1034ARQ
ADM1034ARQ-REEL
ADM1034ARQ-REEL7
ADM1034ARQZ1
ADM1034ARQZ-REEL1
ADM1034ARQZ-REEL71
1
Temperature Range
−40°C to +125°C
−40°C to +125°C
−40°C to +125°C
Package Description
16-Lead QSOP
16-Lead QSOP
16-Lead QSOP
Package Option
RQ-16
RQ-16
RQ-16
−40°C to +125°C
−40°C to +125°C
−40°C to +125°C
16-Lead QSOP
16-Lead QSOP
16-Lead QSOP
RQ-16
RQ-16
RQ-16
Z = Pb-free part.
© 2004 Analog Devices, Inc. All rights reserved. Trademarks and
registered trademarks are the property of their respective owners.
D04918–0–8/04(0)
Rev. 0 | Page 40 of 40