Mean Well DR-30-12 30w single output industrial din rail power supply Datasheet

30W Single Output Industrial DIN Rail Power Supply
DR-30
series
Features :
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
Isolation class
LED indicator for power on
100% full load burn-in test
3 years warranty
SPECIFICATION
MODEL
DR-30-5
DR-30-12
DR-30-15
DR-30-24
DC VOLTAGE
5V
12V
15V
24V
RATED CURRENT
3A
2A
2A
1.5A
CURRENT RANGE
0 ~ 3A
0 ~ 2A
0 ~ 2A
0 ~ 1.5A
RATED POWER
15W
RIPPLE & NOISE (max.) Note.2 80mVp-p
OUTPUT
INPUT
VOLTAGE ADJ. RANGE
21.6 ~ 26.4V
1.0%
LINE REGULATION
1.0%
1.0%
1.0%
1.0%
LOAD REGULATION
1.0%
1.0%
1.0%
1.0%
SETUP, RISE TIME
100ms, 30ms/230VAC
HOLD UP TIME (Typ.)
100ms/230VAC
VOLTAGE RANGE
85 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
100ms, 30ms/115VAC at full load
21ms/115VAC at full load
120 ~ 370VDC
EFFICIENCY (Typ.)
74%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
0.88A/115VAC
0.48A/230VAC
COLD START 15A/115VAC
30A/230VAC
OVERLOAD
105 ~ 160% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
5.75 ~ 6.75V
13.8 ~ 16.2V
17.25 ~ 20.25V
27.6 ~ 32.4V
81%
82%
83%
Protection type : Shut down o/p voltage, re-power on to recover
-20 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL60950-1, TUV EN60950-1 approved, Design refer to EN50178
I/P-O/P:3KVAC
ISOLATION RESISTANCE
I/P-O/P:100M Ohms/500VDC
EMI CONDUCTION & RADIATION Compliance to EN55011,EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
HARMONIC CURRENT
EMS IMMUNITY
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
MTBF
441.5K hrs min. MIL-HDBK-217F (25
78*93*56mm (W*H*D)
0.27Kg; 48pcs/14Kg/1.02CUFT
DIMENSION
PACKING
NOTE
13.5 ~ 16.5V
1.0%
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
OTHERS
10.8 ~ 13.2V
1.0%
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
(Note 4)
36W
150mVp-p
2.0%
OVER VOLTAGE
EMC
30W
120mVp-p
VOLTAGE TOLERANCE Note.3
PROTECTION
SAFETY &
4.75 ~ 5.5V
24W
120mVp-p
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:DR-30-SPEC 2008-04-07
DR-30
30W Single Output Industrial DIN Rail Power Supply
Mechanical Specification
series
Case No. 918B Unit:mm
68
45
47
56
27.4
Terminal Pin No. Assignment
Pin No.
5,6
7
8
Assignment
AC/N
AC/L
+V
Assignment
-V
LED
+V ADJ.
3
Pin No.
1
2
3,4
46.5
46.5
93
12.2 5 5 5
8
6
5
4
3
7
37.75
78
35
2
1
5
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Block Diagram
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
POWER
SWITCHING
RECTIFIERS
&
FILTER
+V
-V
DETECTION
CIRCUIT
O.L.P.
CONTROL
O.V.P.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
100
90
80
80
70
LOAD (%)
LOAD (%)
60
40
20
-20
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70 (VERTICAL)
60
50
40
85
95
100
115
120
140
160
180
200
220
240
264
INPUT VOLTAGE (VAC) 60Hz
File Name:DR-30-SPEC 2008-04-07