Mean Well DR-75 75w single output industrial din rail power supply Datasheet

75W Single Output Industrial DIN Rail Power Supply
DR-75
series
Features :
Universal AC input / Full range
Protections:Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fix switching frequency at 50KHz
3 years warranty
SPECIFICATION
MODEL
DR-75-12
DR-75-24
DR-75-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
6.3A
3.2A
1.6A
CURRENT RANGE
0 ~ 6.3A
0 ~ 3.2A
0 ~ 1.6A
RATED POWER
76W
76.8W
76.8W
RIPPLE & NOISE (max.) Note.2 100mVp-p
OUTPUT
150mVp-p
240mVp-p
12 ~ 14V
24 ~ 28V
48 ~ 53V
VOLTAGE TOLERANCE Note.3
2.0%
1.0%
1.0%
LINE REGULATION
0.5%
0.5%
0.5%
LOAD REGULATION
1.0%
1.0%
1.0%
VOLTAGE ADJ. RANGE
SETUP, RISE TIME
INPUT
HOLD UP TIME (Typ.)
60ms/230VAC
VOLTAGE RANGE
85 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
76%
1.6A/115V
0.96A/230V
COLD START 20A/115VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
15 ~ 16.5V
29 ~ 34V
58 ~ 65V
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
(Note 4)
EMS IMMUNITY
MTBF
DIMENSION
PACKING
NOTE
80%
81%
40A/230VAC
Protection type : Shut down o/p voltage, re-power on to recover
85
5
(TSW1) detect on heat sink of power transistor
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-10 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATION Compliance to EN55011,EN55022 (CISPR22) Class B
HARMONIC CURRENT
OTHERS
12ms/115VAC at full load
120 ~ 370VDC
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
OVER TEMPERATURE
EMC
1800ms, 60ms/115VAC at full load
EFFICIENCY (Typ.)
PROTECTION OVER VOLTAGE
SAFETY &
1000ms, 60ms/230VAC
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
123.1K hrs min. MIL-HDBK-217F (25
55.5*125.2*100mm (W*H*D)
0.6Kg; 20pcs/13Kg/1.29CUFT
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:DR-75-SPEC 2008-04-07
DR-75
75W Single Output Industrial DIN Rail Power Supply
Mechanical Specification
Unit:mm
100
Case No. 923
series
+V ADJ.
125.2
TB2
TB1
1
2
3
4
55.5
1
2
3
LED
Terminal Pin No. Assignment (TB1)
35
Pin No.
1
2
3
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Assignment
FG
AC/N(DC+)
AC/L(DC-)
Terminal Pin No. Assignment (TB2)
Pin No.
1,2
3,4
Assignment
DC OUTPUT +V
DC OUTPUT -V
Block Diagram
fosc : 50KHz
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
DETECTION
CIRCUIT
FG
O.L.P.
O.T.P.
Output Derating
PWM
CONTROL
O.V.P.
Output Derating Vs Input Voltage
100
100
24V,48V
90
80
12V
80
70
LOAD (%)
LOAD (%)
60
40
20
-10
60
50
40
0
10
20
30
45
50
AMBIENT TEMPERATURE ( )
60 (VERTICAL)
85
90
105
125
145
165
185
205
225
245 265
INPUT VOLTAGE (V) 60Hz
File Name:DR-75-SPEC 2008-04-07