Cooper LP-CC-12 Low-peakâ ¢ lp-cc class cc 600vac/300vdc, 1â 2-30a time-delay fus Datasheet

Technical Data 1023
Effective February 2016
Supersedes August 2015
Low-Peak™ LP-CC Class CC 600Vac/300Vdc, 1⁄230A time-delay fuses
Catalog numbers (amps)
LP-CC-1⁄2
LP-CC-1-1⁄2
LP-CC-3
LP-CC-6
LP-CC-12
LP-CC-6⁄10
LP-CC-1-6⁄10
LP-CC-3-2⁄10
LP-CC-6-1⁄4
LP-CC-15
LP-CC-8⁄10
LP-CC-1-8⁄10
LP-CC-3-1⁄2
LP-CC-7
LP-CC-20
LP-CC-1
LP-CC-2
LP-CC-4
LP-CC-7-1⁄2
LP-CC-25
LP-CC-30
LP-CC-1-1⁄8
LP-CC-2-1⁄4
LP-CC-4-1⁄2
LP-CC-8
LP-CC-1-1⁄4
LP-CC-2-1⁄2
LP-CC-5
LP-CC-9
LP-CC-1-4⁄10
LP-CC-2-8⁄10
LP-CC-5-6⁄10
LP-CC-10
Carton quantity:
Catalog symbol:
•
Amp rating
Carton qty.
1⁄4-30
10
Dimensions - in (mm)
1.5" (± 0.031)
(38.1mm)
LP-CC-(amp)
0.41" (± 0.005)
(10.3mm)
Description:
Ultimate protection Class CC current-limiting, timedelay fuses. Time-delay – 12 seconds (minimum)
at 200% of rated current.
Specifications:
Features:
•
200kA interrupting rating complies with
NEC® Section 110.9 for today’s large capacity
systems.
•
Fast short-circuit protection and dual-element,
time-delay performance provide ultimate
protection.
•
Reduces existing fuse inventory by up to 33%
when upgrading to Low-Peak fuses.
•
Consistent 2:1 ampacity ratios for all Low-Peak
fuses make selective coordination easy.
•
Time-delay characteristic avoids unwanted
fuse openings from surge currents while fast
response speed under short-circuit conditions
provides a high degree of current limitation.
•
Current-limitation protects downstream
components against damaging thermal and
magnetic effects of short-circuit currents.
•
A superior, all-purpose, space-saving branch
circuit fuse that meets most protection
requirements up to 30A.
•
Very compact, with a physical size only 13⁄32” x
1 1⁄2” (10.3 x 38.1mm) with rejction tip.
•
Proper sizing can provide “no damage” Type 2
coordinated protection for NEMA and IEC motor
controllers.
•
Can be used where either a time-delay or a
fast-acting fuse is needed, making selection
easier and reducing spare fuse inventories for
substantial cost reduction.
•
Superior protection for small horsepower motor
circuits.
Ratings
•
Volts
• 600Vac,
•
300Vdc (1⁄2-2-8⁄10A, 20-30A)
•
150Vdc (3-15A)
•
Amps 1⁄2-30A
•
IR
•
200kA Vac RMS Sym.
•
20kA Vdc
Agency information
•
UL® Listed Class CC, Std. 248-4,
Guide JDDZ, File E4273
•
CSA® Certified; Class 1422-02, File 53787
•
CE
•
RoHS compliant (20-30A)
Low-Peak™ LP-CC Class CC 600Vac/300Vdc, 1⁄2-30A time-delay fuses
Technical Data 1023
Effective February 2016
Recommended fuse blocks and holders:
Fuse amps
1-Pole
2-Pole
3-Pole
Modular open blocks
0-30
BCM603-1_
BCM603-2_
BCM603-3_
CHCC1D_
CHCC2D_
CHCC3D_
—
—
OPM-NG-_
—
—
OPM-1038_
—
—
OPM-1038_SW
HPS
—
—
HPF
—
—
—
HEY
—
HEZ
—
—
DIN-Rail holders
0-30
Panel mount holders
0-30
In-line holders
0-30
For additional information on Class CC fuse blocks and holders, see
data sheets:
• Modular open blocks # 10241 (BCM)
•
DIN-Rail holders No. 3185 (CHCC), No. 1109 (OPM), No. 1102
(OPM-1038), No. 1103 (OPM-1038_SW)
•
Panel mount holders No. 2113 (HPS), No. 2114 (HPF)
•
In-line holders No. 2126 (HEY), No. 2130 (HEZ)
2
Eaton.com/bussmannseries
Low-Peak™ LP-CC Class CC 600Vac/300Vdc, 1⁄2-30A time-delay fuses
Technical Data 1023
Effective February 2016
3
3-1/2
4
4-1/2
6
8
10
12
15
20
25
30
200
6/10
8/10
1
1-1/4
1/2
Time-current curves - average melt:
AMP RATING
100
TIME IN SECONDS
10
1
1000
CURRENT IN AMPS
100
10
1
0.01
0.4
0.1
Eaton.com/bussmannseries
3
Low-Peak™ LP-CC Class CC 600Vac/300Vdc, 1⁄2-30A time-delay fuses
Technical Data 1023
Effective February 2016
Current-limiting effects:
B
30
25
20
15
2-8/10
1-1/4
Amp Rating
INSTANTANEOUS PEAK-LET-THROUGH CURRENT IN AMPS
Current-limitation curves:
A
RMS SYMMETRICAL CURRENT IN AMPS
A-B = ASYMMETRICAL AVAILABLE PEAK (2.3 X SYM RMS AMPS)
Let-through current
Prospective (apparent RMS symmetrical vs. fuse rating)
S.C.C. 1-1⁄4A 2-8⁄10A
15A
20A
25A
30A
1000
100
135
240
305
380
435
3000
140
210
350
440
575
580
5000
165
255
420
570
690
710
10,000
210
340
540
700
870
1000
20,000
260
435
680
870
1090
1305
30,000
290
525
800
1030
1300
1520
40,000
315
610
870
1150
1390
1700
50,000
340
650
915
1215
1520
1820
60,000
350
735
1050
1300
1650
1980
80,000
390
785
1130
1500
1780
2180
100,000
420
830
1210
1600
2000
2400
200,000
525
1100
1600
2000
2520
3050
NOTE: To calculate Ip (Ipeak) multiply IRMS value by 2.3.
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document
are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help
the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or
limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin.
Once a product has been selected, it should be tested by the user in all possible applications.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2016 Eaton
All Rights Reserved
Printed in USA
Publication No. 1023 — BU-SB13732
February 2016
Eaton, Bussmann and Low-Peak are valuable
trademarks of Eaton in the US and other
countries. You are not permitted to use
the Eaton trademarks without prior written
consent of Eaton.
UL is a registered trademark of the
Underwriters Laboratories, Inc.
CSA is a registered trademark of the Canadian
Standards Group.
NEC is a registered trademark of the National
Fire Protection Association, Inc.
Follow us on social media to get the
latest product and support information.