FC SERIES SETTER (CONTINUOUS OUTPUT TYPE) DATA SHEET PNF3 The FC series setter is used for remote setting of a controller or variable constant setting of various types of computing elements. This instrument uses a solid state indicator and a pushbutton operation system to provide reliable monitoring and operating functions. FEATURES 1. High reliability This instrument is designed with few mechanical parts. It is mainly composed of electronic parts such as a solid state indicator which was formerly consisted of mechanical parts. 2. International standards This instrument is compact in size, conforming to international standards IEC. It operates on 24V DC power to deliver 1 to 5V DC signals as recommended by IEC standards. 100 and 200V AC power are also available for convenience of operation. 3. Front panel operation Process values and set points can be read accurately with digital indications on panel front. Various parameter settings and setting operations are also possible from the front panel of the instrument. FUNCTIONAL DIAGRAM PV Linearize Square-root extraction SV Local mode output (LS) Remote request (R-REQ) Filter Compensated process value signal (KPV) Process value input (PV) External set point input (CAS or PI) (1 to 5V DC, pulse width, or pulse number) Remote acknowledge signal (R-ACK) Limiter H Set point output signal (SV) R L L KPV FAULT FLT output ALM High alarm output (H) Low alarm output (L) EDS11-115g Date Aug. 15, 1996 PNF3 SPECIFICATIONS 1. Input signal (1) Process value input signal: 1 input selectable from the following. Voltage input signal current input signal I+ I0 I– 1 to 5V DC Input resistance, 1MΩ or more 4 to 20mA DC 24V DC power supAllow. error ± 0.2%/FS plied to transmitter only when AC power is used Allow. error ± 0.2%/FS* Note: * FS: Full scale (2) Analog input signal: 1 point External set point CAS input signal 1 to 5V DC Input resistance, 1MΩ or more Allow. error ± 0.2%/FS (3) Digital input signal: 1 point Remote acknowledge signal R-ACK Contact input (photo-coupler insulation) ON 0V, OFF 24V ( input current, approx. 11mA/24V DC) Contents of indication: Process value (industrial value), set point (industrial value), high/low alarm, etc. Indication contents are selectable by F/S , keys on front panel. , Setting method: By using F/S , , , , ST keys on front panel. (4) Setting functions Fixed value setting method: By using of , pushbuttons on front panel. Setting speed, approx. 40 sec/FS Remote setting method: By use of external set point signal (voltage or pulse width input) Tracking speed setting range; 0 to 900 sec/FS (5) Operation mode changeover By using of R/L pushbutton on front panel R R (4) Pulse width or pulse number input signal: 1 set (either one) Pulse width input signal Pulse number input signal PI+ PI– Contact input (photo-coupler insulation) ON 0V, OFF 24V (input current, approx. 11mA/24 DC) ON 0V, OFF 24V (approx. 11mA/24V DC) max. input frequency 500Hz 2. Output signal (1) Analog output signal: 2 points Compensated process KPV value signal 1 to 5V DC Set point output signal MV Output resistance, 1Ω or less Allow. error ± 0 2%/FS (2) Digital output signal: 5 points Fault output FLT Open-collector LS Remote request signal R-REQ output (photocoupler insulaHigh alarm output H tion) Low alarm output L Local mode output Rated output, 30V x 0.1A DC, max. 3. Indication, setting, operating functions (1) Bargraph indication L changeover Balanceless bumpless Voltage signal* Balance bumpless Pulse width signal Balanceless bumpless Note: * Balanceless bumpless by setting tracking speed (6) Alarm functions High/low alarm settable in industrial values for process value input signal. 4. Power failure processing functions Power failure detection: Setting output held at power failure detection. During power failure: Data backed up by capacitor up to 5 minutes. Initial value of set point stored in non-volatile memory (10 years expected at ambient temperature of 50°C or less). Power failure recovery: Initial or continuous start mode can be set within 5 minutes of power failure. Recovery from power failure lasting longer than 5 minutes is initial. ** Note: ** Operation mode set at initial can be registered L: Local mode or R: Remote mode 5. Self-diagnosis functions PV indicator SV indicator Indication method LED (red) LED (green) No. of segments 101 + 2 101 + 2 Range 0 to 100%, linear 0 to 100%, linear Resolution 1 %/FS 1%/FS Scale length 100mm 100mm Indicating mode 0 to 100% bargraph indication, 0 to 100% reverse bargraph indication, dot indication, –50 to +50% deviation indication (2) Operation mode indication Indicating method: LED (green) Green: L(local), R(remote) (3) Numerical value indication, setting Indication method: LED (red), name in 3 digits + numerical value in 5 digits (negative code included) 2 L changeover Input signal abnormality: FLT lamp lights, FLT output contact "ON" Indication of abnormal contents: Cause of abnormality indicated in numerical values on front panel. 6. Transmission functions (1) Transmission items Supervisory items: PNF Host Process variable, set point, operation mode, alarm information, fault information, various limiter values, constants, etc. Setting operation items: Host PNF Set point, operation mode, various limiter values, constants, etc. (2) Transmission setting inhibit: Parameter setting enable/inhibit can be designated by transmission from the host. Designation is done by keys on the front panel key. (3) Communication interface (a) T-link: Private interface Transmission speed: 500Kbps No. of units connectable: 32 max. Transmission distance: 1km max. Transmission form: Multi-drop Control method: I/O transmission and message (b) RS-422A/485: Universal interface Transmission speed: 2400, 4800, 9600 or 19200bps configurable No. of units connectable: 31 max. Transmission distance: 1km max. Transmission form: Multi-drop Control method: Polling/selecting 7. Other functions Data protective function by pass code CODE SYMBOLS 1 2 3 4 5 6 7 8 PNF 3 B 9 10 Description 5 - 0 Process value input signal 1 to 5V DC 4 to 20mA DC with 24V DC power supply A B Auxiliary analog input None B Power supply 24V DC (20 to 30V DC) 100V AC (85 to 132V/47 to 63Hz AC) 200V AC (187 to 264V/47 to 63Hz AC) 1 2 3 Y T R S Transmission functions None T-link RS-422A RS-485 8. Operating conditions Power supply: Select from 3 types 24V DC (20 to 30V DC) 100V AC (85 to 132V/47 to 63Hz AC) 200V AC (187 to 264V/47 to 63Hz AC) Power consumption: Approx. 11W (DC) Approx. 20VA (AC) Dielectric strength: 1500V AC, 1 min. Insulation resistance: 500V DC, 100MΩ or more Ambient temperature: 0 to 50°C Ambient humidity: 90% RH or less Enclosure: Steel case Rating plate (Name plate): 100 (H) x 70 (W) mm, white acryl Dimensions: 144 (H) x 72 (W) x 407 (D) mm, IEC (DIN) standard Mass {weight}: Approx. 2.9kg Mounting method: Flush indoor mounting; vertical mounting. Mountable on tilted surface angle "α" α=0° to 90° Finish color: Munsell N 1.5 for both front panel and case Scope of delivery: Setter and mounting bracket 3 PNF3 OUTLINE DIAGRAM (Unit:mm) Panel thickness 8mm or less 16 144 Terminals Supporting bracket 355 52 Mounting bracket 200 72 Panel cutout When mounting "n" units +1 0 250min. 68 4 +0.7 0 138 138 +1 0 200min. When mounting 1 unit (72.2n – 4) +1 0 No. of units n 2 CONNECTION DIAGRAM Compression Terminal AI (External set point) — 01 CAS I+ 31 — Io 32 — — 03 I– 33 — — 04 KPV 34 — — 05 SV 35 — — 02 Not use 36 — AO (Compensated PV signal) AO (Set point output signal) Not use SC 37 — Al, AO Common bus SC 38 — — 06 AI, AO Common bus Not use — 07 SC — 08 SC — 09 39 — — 10 40 — — 11 41 — — 12 42 — — 13 DI (Pulse input) DO (High-limit alarm output) DO (Low limit alarm output) DO (FLT output) 24VDC power for DI, DO 24VDC power for DI, DO Instrument power (24VDC) PI+ — 15 PI– RACK 45 — — 16 H RREQ 46 — L LS 47 — — – — – — – — Not use 43 — — 14 — 17 Process value input 44 — 18 FLT 19 PCD VPD 20 PCD VPD 21 PC* VP* G AC AC 71 72 48 — + 49 — + 50 — + 51 — DI (Remote acknowledge) DO (Remote request) DO (Local status) Not use 24VDC power for DI, DO Instrument power (24V DC) Note: * Symbols for AC instrument power are VPO, PCO. Output:Approx. 24V DC (0.1A max.) 73 Ground Instrument power (AC) Instrument power (AC) Connection for process value input terminals 1 to 5V DC 4 to 20mA DC The 5th digit of code symbols B 4 to 20mA DC with inner DC power supply of CC-S The 5th digit of code symbols B + 31 – 33 + 31 – 33 + 31 – 33 32 The 5th digit of code symbols A + 32 – + – 32 PC 21 5 PNF3 COMMUNICATION CONNECTOR 1 SIG GND 6 2 SHLD(SD) 7 8 RXD + 9 RXD – 3 INH 4 TXD+(T1) 1 SIG GND 6 2 SHLD(SD) Black 7 White 8 RXD + 9 RXD – 5 TXD–(T2) Green 3 INH 4 TXD+(T1) 5 TXD–(T2) Yellow Note:Symbol in ( ): T-link terminal symbol Brown Red 6 7 8 RXD + 9 RXD – 1 SIG GND 1 SIG GND 6 2 SHLD(SD) 7 3 INH 8 RXD + 4 TXD+(T1) 9 RXD – 5 TXD–(T2) LINE TERMINATION RESISTOR 2 SHLD(SD) Black 3 INH White 4 TXD+(T1) 5 TXD–(T2) Green Yellow Red Brown Termianl station HOST MASTER CONTROLLER First station Host Termination Resistor Transmission cable PNF3 PNF3 PNF3 PNF3 The product conforms to the requirements of the Electromagnetic compatibility Directive 89/336/EEC as detailed within the technical construction file number TN510402. The applicable standards used to demonstrate compliance are :- EN 55011 : 1991 CLASS A Conducted and Radiated emissions EN 50082-1 :-1992 Radiated immunity, ESD and FBT Caution on Safety *Before using this product, be sure to read its instruction manual in advance. Head Office 6-17, Sanbancho, Chiyoda-ku, Tokyo 102-0075, Japan http://www.fesys.co.jp/eng Sales Div. International Sales Dept. No.1, Fuji-machi, Hino-city, Tokyo, 191-8502 Japan Phone: 81-42-585-6201, 6202 Fax: 81-42-585-6187 http: //www.fic-net.jp/eng Information in this catalog is subject to change without notice. Printed in Japan