Red Lion DRRJ11T6 Model itms - intelligent temperature to modbus conditioner w/ alarm Datasheet

Bulletin No. ITMS-B
Drawing No. LP0494
Released 1/07
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL ITMS - INTELLIGENT TEMPERATURE TO MODBUS CONDITIONER W/ ALARMS
O
TEMPERATURE TO MODBUS CONVERSION
O
ACCEPTS THERMOCOUPLE, RTD, mV OR RESISTANCE
SIGNALS
O
PROCESSOR BASED SCALING
O
PC CONFIGURATION SOFTWARE
O
DUAL SETPOINT RELAY ALARMS
O
FOUR WAY SIGNAL ISOLATION
UL Recognized Component,
File # E179259
GENERAL DESCRIPTION
SAFETY SUMMARY
The ITMS4037 Intelligent Temperature to MODBUS™ Conditioner with
Alarms accepts a wide range of temperature sensors (thermocouple and RTD
elements), and converts the signal into a register format that can be read using
either ASCII or RTU MODBUS protocol.
The ITMS allows a choice of either Fahrenheit or Celsius readout with 0.1 or
1 degree of resolution. An offset value can be programmed to scale the input
signal to meet most process requirements. Additionally, two setpoint values can
be entered for dual relay process monitoring alarms.
The ITMS is programmed with Windows™ based SFIMS software. The
software allows configuration, calibration, and storage of ITMS program files.
Additionally, all setup parameters can be interrogated and modified through
MODBUS register and coil commands.
The RS485 port allows the ITMS to be multidropped, with Baud rates up to
38400. The CBPRO007 programming cable converts the RS232 port of a PC to
RS485, and is terminated with an RJ-11 connector. The bidirectional capability
of the CBPRO007 allows it to be used as a permanent interface cable as well as
a programming cable.
The ITMS’s two relay alarms can be configured independently for absolute
high or low acting with balanced or unbalanced hysteresis. Alarm 2 can also be
configured for deviation and band alarms. In these modes, Setpoint 2 tracks
Setpoint 1. Adjustable alarm trip delays can be used for delaying output
response. The alarms can be programmed for Automatic or Latching. Latched
alarms can be reset with a serial command or a user input. A standby feature
suppresses the alarm during power-up until the temperature stabilizes outside
the alarm region. Standby eliminates power-up tripping for low acting alarms.
A user input can be used to set and reset non-latching alarms. The output relays
can also be manually controlled with register commands.
The module’s high density packaging and DIN rail mounting saves time and
panel space. The module is equipped with a universal mounting foot for
attachment to standard DIN rails, including top hat (T) profile or G profile rail.
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
DIMENSIONS In inches (mm)
ORDERING INFORMATION
MODEL
ITMS
DESCRIPTION
Temperature to MODBUS Conditioner w/Alarms
SFIMS
PC Configuration Software for Windows
CBPRO
Programming Interface Cable
CBJ
PART NUMBER
ITMS4037
SFIMS
CBPRO007
Cable RJ11 to Unterminated 7 foot length
CBJ11A07
Cable RJ11 to RJ11 6 inch jumper
CBJ11BD5
RJ Connector to Terminal Adapter
DRRJ11T6
CAUTION: Risk of electric shock.
1
SPECIFICATIONS
11. MEMORY: Nonvolatile E2PROM retains all programmable parameters.
12. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -20 to +65 °C
Storage Temperature Range: -40 to +85 °C
Operating and Storage Humidity: 85% max. relative humidity (noncondensing) from -20 to +65 °C
Altitude: Up to 2000 meters
13. CERTIFICATIONS AND COMPLIANCE:
SAFETY
UL Recognized Component, File # E179259, UL3101-1, CSA 22.2 No. 1010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
IECEE CB Scheme Test Certificate # US/5141A/UL,
CB Scheme Test Report # 01ME11540-0702001
Issued by Underwriters Laboratories, Inc.
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
ELECTROMAGNETIC COMPATIBILITY
Immunity to EN 50082-2
Electrostatic discharge
EN 61000-4-2 Level 2; 4 KV contact
Level 3; 8 KV air1
Electromagnetic RF fields
EN 61000-4-3 Level3; 10 V/M
80 MHz - 1 GHz
Fast transients (burst)
EN 61000-4-4 Level 4; 2 KV I/O
Level 3; 2 KV power
RF conducted interference
EN 61000-4-6 Level 3; 10 V/rms
150 KHz - 80 MHz
Simulation of cordless telephone ENV 50204 Level 3; 10 V/m
900 MHz ± 5 MHz
200 Hz, 50% duty cycle
Emissions to EN 55011
RF interference
EN 55011
Enclosure class A
Power mains class A
1. POWER: 18-36 VDC, 3.0 W max. or 24 VAC, ±10%, 50/60 Hz, 4 VA max.
2. INPUT:
Sample Rate: 67 msec. (15 Hz)
Failed Sensor Response: Open or shorted (RTD only) sensor coils indication,
error code returned in Process Value
Common Mode Rejection: 50/60 Hz, 110 dB min.
Overvoltage: 30 VDC
Response Time: 150 msec. max.
3. THERMOCOUPLE INPUTS:
Types: T, E, J, K, R, S, B, N, C, linear mV
Input Impedance: 20 MΩ
Lead Resistance Effect: 0.22 µV/Ω
Resolution: 1° or 0.1° for all types
TC TYPE
T
E
J
K
R
S
B
N
C
W5/W26
mV
DISPLAY RANGE
-200 to +400°C
-328 to +752°F
-200 to +750°C
-328 to +1382°F
-200 to +760°C
-328 to +1400°F
-200 to +1372°C
-328 to +2502°F
0 to +1768°C
+32 to +3214°F
0 to +1768°C
+32 to +3214°F
+200 to +1820°C
+392 to +3308°F
-200 to +1300°C
-328 to +2372°F
0 to +2315°C
+32 to +4199°F
-10 mV to 65 mV
WIRE COLOR
ANSI
BS 1843
(+) blue
(-) red
(+) violet
(-) red
(+) white
(-) red
(+) yellow
(-) red
No Standard
(+) white
(-) blue
(+) brown
(-) blue
(+) yellow
(-) blue
(+) brown
(-) blue
(+) white
(-) blue
(+) white
(-) blue
No Standard
No Standard
(+) orange
(-) red
(+) orange
(-) blue
No Standard
No Standard
NA
NA
No Standard
Notes:
1. This device was designed for installation in an enclosure. To avoid
electrostatic discharge to the unit in environments with static levels above
6 KV, precautions should be taken when the device is mounted outside an
enclosure. When working in an enclosure (ex. making connections, etc.),
typical anti-static precautions should be observed before touching the module.
Refer to the EMC Installation Guidelines section of this bulletin for
additional information.
14. CONSTRUCTION: Case body is black high impact plastic. Installation
Category II, Pollution Degree 2.
15. CONNECTIONS: Wire clamping screw terminals.
16. MOUNTING: Universal mounting foot for attachment to standard DIN
style mounting rails, including top hat (T) profile rail according to EN50022
- 35 x 7.5 and -35 x 15, and G profile rail according to EN50035 - G32.
17. WEIGHT: 4.5 oz. (127.57 g)
4. RTD INPUTS:
Type: 2 or 3 wire
Excitation: 150 µA
Lead Resistance: 10 Ω max.
Resolution: 1° or 0.1° for all types
RTD TYPE
385
392
672
Ohms
INPUT TYPE
100 Ω platinum,
Alpha=.00385
100 Ω platinum,
Alpha=.003919
120 Ω nickel,
Alpha=.00672
Linear Resistance
RANGE
-200 to +800°C
-328 to +1472°F
-200 to +800°C
-328 to +1472°F
-80 to +260°C
-112 to +500°F
0 to 440 Ω
5. INDICATION ACCURACY: ±(0.3% of span, +1°C), includes NIST
conformity, cold junction effect, A/D conversion errors, tempco and
linearization conformity at 23°C after 20 minute warm-up.
Span Drift (max) : 0.01% /°C
6. USER INPUT: Internally pulled up to +5 VDC. VIL = 0.78 V max.,
VIH = 1.8 V min. IOFF = 9 µA max. 30 V max. over voltage continuously.
7. ISOLATION LEVEL: 1.5 KV @ 50/60 Hz, 1 minute (150 V working)
between input, RS485 and power supply. 2300 Vrms, 1 minute (300 V
working) to relay contacts.
8. SERIAL COMMUNICATIONS:
Type: RS485; RTU and ASCII MODBUS modes
Baud: 300, 600, 1200, 2400, 4800, 9600, 19200, and 38400
Format: 7/8 bit, odd, even and no parity
Transmit Delay: Programmable. (See Transmit Delay explanation in Step 6)
Transmit Enable (TXEN): (primarily for 20 mA loop converter) open
collector VOH = 10 VDC max. VOL = 0.5 VDC @ 5 mA max. current limit
9. A/D CONVERTER: 16 bit resolution
10. RELAY OUTPUTS:
Type: 1 Form A N.O. contacts, 1 Form C DPDT
Rating: 5A @ 30 VDC or 250 VAC max. (resistive)
1/10 HP @ 120 VAC (inductive)
Response Time: 155 msec. max. to close including step response, 153 msec.
max. to open.
Output On Delay Time: Programmable from 0 to 32000 sec ±0.01% - 1 sec. max.
BLOCK DIAGRAM
2
MODULE ISOLATION
LED FUNCTIONALITY
The ITMS features “4-way” signal isolation. The 4-way isolation is a
combination of optical, transformer and relay barriers, providing common mode
voltage (CMV) isolation to 1.5 KV for 1 minute between input, RS485, and
power supply. Isolation between relay contacts and all other inputs is 2300 Vrms
for 1 minute.
CONDITION
Power Applied
Communication Received
Respective Alarm
Checksum error
Calibration
EMC INSTALLATION GUIDELINES
GREEN LED
2 RED LEDS
On
———
Flashing
———
On
On
Flashing
Flashing
Off
On
3. Signal or Control cables within an enclosure should be routed as far away as
possible from contactors, control relays, transformers, and other noisy
components.
4. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional
protection. Install line filters on the power input cable to the unit to suppress
power line interference. Install them near the power entry point of the
enclosure. The following EMI suppression devices (or equivalent) are
recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC # FCOR0000)
TDK # ZCAT3035-1330A
Steward # 28B209-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC # LFIL0000)
Schaffner # FN670-1.8/07
Corcom # 1 VR3
Note: Reference manufacturer’s instructions when installing a line filter.
5. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
Although this module is designed with a high degree of immunity to ElectroMagnetic Interference (EMI), proper installation and wiring methods must be
followed to ensure compatibility in each application. The type of the electrical
noise, source or coupling method into the unit may be different for various
installations. Cable length, routing, and shield termination are very important
and can mean the difference between a successful or troublesome installation.
Listed below are some EMC guidelines for successful installation in an
industrial environment.
1. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the rail where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
c. Connect the shield to common of the unit and leave the other end of the
shield unconnected and insulated from earth ground.
2. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
3
STEP 1 WIRING THE MODULE
WIRING CONNECTIONS
RELAY OUTPUT CONNECTIONS
All conductors should meet voltage and current ratings for each terminal.
Also, cabling should conform to appropriate standards of good installation, local
codes and regulations. When wiring the module, use the numbers on the label to
identify the position number with the proper function. Strip the wire, leaving
approximately 1/4" (6 mm) of bare wire exposed. Insert the wire into the
terminal, and tighten the screw until the wire is clamped tightly. (Pull wire to
verify tightness.) Each terminal can accept up to one #14 AWG (2.55 mm), two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm) wires.
Relay 1
Relay 1 is a Form A output relay. Wiring is connected between terminal 9
(COMM.) common and terminal 8 (N.O.) the normally open contact.
Relay 2
Relay 2 is a Form C output relay. Wiring is connected between terminal 4
(COMM.) common and either terminal 5 (N.O.), the normally open contact, or
terminal 3 (N.C.), the normally closed contact.
To prolong contact life and suppress electrical noise interference due to the
switching of inductive loads, it is good installation practice to install a snubber
across the contacts. Follow the manufacturer’s instructions for installation.
Note: Snubber leakage current can cause some high impedance loads to be held ON.
MODULE POWER CONNECTIONS
AC module power is connected to terminals 1 and 2. DC module power is
connected with (+) to terminal 1 and (-) to terminal 2. For best results, the power
should be relatively “clean” and within the specified limits. Drawing power
from heavily loaded circuits or from circuits that also power loads that cycle on
and off should be avoided. It is recommended that power supplied to the module
be protected by a fuse or circuit breaker.
DEFAULT SERIAL SETTING CONNECTION
If the ITMS settings are unknown, or forgotten, they can be reset to the
factory defaults by connecting the Serial Default terminal 7 to Input Comm.
terminal 12 with a jumper, and then cycling power.
INPUT CONNECTIONS
Defaults:
Thermocouple Input
Thermocouple leads are connected to terminals 11 (+) and 12 (-).
RTD Input
Protocol:
RTU
Data Bits: 8
Address:
247
Parity:
none
Baud Rate: 9600
For 3-wire RTD elements, connect the sense leads to terminals 11 and 12. The
excitation lead is connected to terminal 10 (EXC).
For 2-wire RTD elements, connect the sense leads to terminals 11 and 12.
Install a copper sense lead of the same gauge and length as the RTD leads.
Attach one end of the wire at the probe and the other end to terminal 10.
Complete lead wire compensation is obtained. This is the preferred method. If a
sense wire is not used, then Terminal 11 should be shorted to terminal 10. A
temperature offset error will exist. The error may be compensated by
programming a temperature offset.
USER INPUT CONNECTION
The user input is activated when terminal 6 is pulled low (connected to Input
Comm. terminal 12).
RS485 SERIAL CONNECTIONS
There are two RJ-11 connectors located on the bottom for paralleling
communications. For single device communications, either connector can be
used. When used in conjunction with Red Lion Control Paradigm HMI products,
reverse A+ and B- wiring.
RJ11
1
ITMS
Not used
2
B-
3
A+
4
COMM
5
TXEN
6
Not used
2 3 4 5
ITMS CONNECTOR
STEP 2 INSTALLING SFIMS (Software for Intelligent Modules)
Insert the SFIMS diskette into the A: or B: drive. Then Run A:\SETUP
(or B:\SETUP) to install RLCPro onto the hard drive. An icon labeled
RLCPro will be created under the group RLCPro.
4
STEP 3 PROGRAMMING - Getting Started
You will be prompted to
select the proper device,
Run RLCPro by double-clicking the icon, or use the start menu.
Use the FILE pull-down menu
to select a NEW file.
and then the model.
STEP 4 PROGRAMMING THE INPUT
The ITMS receives a temperature sensor input, converts it to a raw digital value, and stores this number in the ADC Value (register 40001). This number
is scaled into degrees, and a programmable Offset Value (register 40012), that can be used for sensor correction, is applied. The result is stored as the
Temperature Value (register 40002). It is also stored in the IEEE 754 Standard 32-bit floating decimal format (register 40003 and 40004). The non-scaled
ADC, the scaled Process Temperature Value, or the Floating Point Value may be accessed for the purpose of monitoring the input level.
IEEE STANDARD 754
FLOATING DECIMAL POINT
LO Order Byte Register 40003
HI Order Byte Register 40004
INPUT
SIGNAL
ADC READING
OFFSET
INTERNAL
MATH
Register
40012
Register 40001
PROCESS
TEMPERATURE
VALUE
Register 40002
Input Type: Select the proper input type from the pull down menu.
Scale: Select Fahrenheit or Celsius. In linear millivolt or resistance modes, this has no
effect.
Resolution: For thermocouple, RTD, or linear resistance modes, low resolution selects
whole degrees or ohms. In these same modes, high resolution selects tenth of degrees
or ohms. In linear mV mode, low selects hundredths of mV, and high selects
thousandths of mV.
Offset: The Offset value can be used as a sensor correction value.
Filter Response: The Filter Response is a time constant, in tenth of second increments,
that is used to stabilize an erratic input. The Process Value stabilizes to 99% of the final
value within approximately 5 time constants. A value of ‘0’ disables digital filtering.
Filter Band: Filter Band is a value expressed in Temperature (degrees or tenths) units.
When a fluctuating signal remains within the band value, the Digital Filter is active,
and therefore stabilizes the Process Temperature Value. When a fluctuating signal
exceeds the Filter Band value, the Digital Filter is momentarily disabled to allow for
quick response to valid process changes. Once the signal variation is less than the Filter
Band value, the Digital Filter is reactivated.
5
STEP 5 PROGRAMMING THE ALARMS
Action: Alarm 1 can be programmed for 5 modes of operation, Alarm 2 has 9 possible modes. See
Setpoint Alarm figures for illustration.
Manual: In Manual mode, the Alarms are forced on and off by writing ‘0’ or ‘1’ to the appropriate
MODBUS register (Alarm 1 state = 40027, Alarm 2 state = 40028). The alarms are
configured for this action from the factory. In this mode, the alarms will not respond to their
setpoint or hysteresis values.
Absolute HI: (with balanced or unbalanced hysteresis) The Alarm energizes when the Temperature
Value exceeds the Setpoint Limit Value.
Absolute LO: (with balanced or unbalanced hysteresis) The Alarm energizes when the Temperature
Value falls below the Setpoint Limit Value.
Deviation HI, Deviation LO, Band Inside or Outside: In these modes, Alarm 2 “tracks”
Alarm/Setpoint 1.
Setpoint: The alarm Setpoint value, entered in degrees. If the ITMS is programmed for mV or resistance modes, then the Setpoint is in mV or Ohms,
respectively.
Hysteresis: Hysteresis is used to eliminate output chatter. The Hysteresis Amount is the difference between the points where an Alarm will turn on
and turn off. In Unbalanced modes, the alarm turns on at the Setpoint, and turns off at Setpoint minus hysteresis for HI alarms, and Setpoint plus
hysteresis for LO alarms. In Balanced modes, the hysteresis is evenly divided above and below the Setpoint value. (See the Setpoint Alarm
Figures.)
Note: The Setpoint, along with the Hysteresis, MUST NOT produce a “trigger point” higher than 32,000, or less than -32,000. (See the Setpoint
Alarm Figures.)
Trigger Points: Trigger Points are the Process Values where the alarm state changes. Their values cannot be entered directly, but are shown as a
reference in the SFIMS software. The Setpoint Value, Hysteresis Value, and Setpoint Alarm Type determine the trigger points. With Deviation or
Band modes, Setpoint 1 and Setpoint 2 are combined to determine the trigger points. Trigger Points cannot be greater than +32000 or less than 32000. If these limits are exceeded, the alarm is disabled and an alarm threshold over range error is set. The Trigger Points can be outside the
Temperature Value range for a given sensor type without receiving an error, but the alarm will not change state for that trigger point.
Reset: The alarms can be programmed for Automatic or Latched. In Automatic mode, an energized alarm turns off by itself once the Process Value
leaves the alarm region. In Latched mode, an energized alarm requires a reset from the User input, or a serial reset command. This is done by
writing a ‘0’ to the appropriate MODBUS register. (Alarm 1 state = 40027, Alarm 2 state = 40028)
On Delay: The time, in whole second increments, that the alarm will take to energize when the Process Value enters into an alarm region.
Enable Standby Delay: Standby prevents nuisance (typically low level) alarms after a power up. After powering up the unit, the temperature must
leave the alarm region. Once this has occurred, the standby is disabled, and the alarm responds normally until the next module power up.
User Input Action: The User Input can be programmed to Reset, or Set, either Alarm 1, Alarm 2, or both. The User Input is activated when terminal
6 is pulled low. (Connected to the Common terminal 12.)
User Input Activation: The User Input can be programmed to respond as a Level (maintained) or Edge (momentary) input. See the User Input Mode
Operation Table below.
Sensor Failure Action: This setting allows different alarm responses when the temperature sensor fails. The ITMS can be programmed to turn one
or both alarms on or off.
USER INPUT MODE OPERATION
INPUT
ACTION
INPUT
ACTIVATION
AUTOMATIC ALARM
IN ALARM REGION
LATCHED ALARM
OUTSIDE ALARM REGION
IN ALARM REGION
OUTSIDE ALARM REGION
No action
Resets and puts the alarm in
Standby mode; resets alarm if in
Hysteresis band
Resets alarm if on
Reset
Edge
Resets and puts the alarm in
Standby mode; resets alarm if in
Hysteresis band
Set
Edge
No action
No action
No action
Sets alarm latched
Reset
Level
Resets alarm while input is active,
resumes normal operation when
input is inactive; resets alarm if in
Hysteresis band
No action
Resets alarm while input is active,
resumes normal operation when
input is inactive; resets alarm if in
Hysteresis band
Resets alarm if on
Set
Level
No action
Sets alarm while input active,
resumes normal operation when
input is inactive
No action
Sets alarm latched
6
SETPOINT ALARM FIGURES
STEP 6 PROGRAMMING THE ITMS COMMS PORT
MODBUS Protocol: RTU or ASCII
Unit Address: 1-247
Baud Rate: 300, 600, 1200, 2400, 4800, 9600, 19200, or 38400
Data Bits: 7 or 8
Parity: odd, even, or none
Transmit Delay: Programmable from 1-255 milliseconds. The Transmit
Delay is the time the ITMS waits to respond to a serial command,
UNLESS the values in the table are larger.
BAUD
RTU
ASCII
38400
19200
9600
4800
2400
1200
600
300
2 msec.
3 msec.
5 msec.
9 msec.
17 msec.
33 msec.
65 msec.
129 msec.
2 msec.
2 msec.
2.3 msec.
4.6 msec.
9.2 msec.
18.4 msec.
36.7 msec.
73.4 msec.
Note: If the communication settings are changed and then a download is
performed, the module will now respond to the new settings. Any further attempts to communicate to the module
must target the new address, with the new settings. If you do not know or cannot recall the ITMS settings, they
can be reset to factory defaults. Connect the Serial Default terminal to Common, and cycle power. The Defaults
button in the SFIMS software will update the category display to these settings.
Communications Diagnostics: The Communications Diagnostics function can be used to troubleshoot systems that are
experiencing communication errors. Press the Read button to retrieve the diagnostics information. The Commands
Received and the Commands Processed values are automatically reset when the values are read, and at each unit power-up.
Commands Received: The number of messages received that started with the units own address.
Commands Processed: The number of “good” messages received. A “good” message is considered one that contained the
correct unit address, parity, and checksum (CRC or LRC).
7
STEP 7 PC PORT CONFIGURATION
Go to the SETTINGS pull-down menu, and select PC PORT SETTINGS.
The Communications Settings window allows you to set up the software properly to perform a download.
Connection: Select the computer port (COMM 1-4) that the ITMS is connected to.
Note: The following settings must match the ITMS. If you do not know or cannot recall the ITMS settings, they can
be reset back to factory defaults. Simply jumper the Serial Default terminal to Common, and cycle power. The
serial settings will default to RTU mode, 9600 baud, 8 data bits, No parity, with an address of 247.
Protocol: RTU or ASCII
Unit Address: 1-247
Baud Rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400
Data Bits: 7 or 8
Parity: odd, even, or none
Connect the ITMS to the computer with the CBPRO007 interface cable (or any suitable RS232/RS485 converter).
Apply 18-36 VDC to the supply terminals of the ITMS.
Note: The CBPRO007 download cable DOES NOT
typically require power. In most cases it will derive
its power from the PC. If communications can not be
established, follow the troubleshooting guide. If it is
determined that the converter requires power, attach
a 12 VDC power supply to the VDC and common
terminals of the cable.
STEP 8 DOWNLOADING
Go to the FILE pull-down menu, and select DOWNLOAD.
The following screen prompts you to
ensure that the proper file is downloaded
to the correct module. Click “OK” to
continue.
8
STEP 9 SCRATCH PAD MEMORY
The Scratch Pad category can be used to read or write to the Scratch Pad memory locations (4110141116). The Scratch Pad locations can be used to store user information.
Data Format: Allows registers to be viewed in decimal or hexadecimal format.
Upload: The Upload button causes SFIMS software to read the Scratch Pad registers from the module.
Download: The Download button causes SFIMS software to write to the Scratch Pad registers in the
module.
Note: Downloading new values to the module Scratch Pad locations overwrites the information that is
currently stored in those registers.
STEP 10 VIEW REGISTERS
The View Registers category can be used as a method of diagnostics. Use the ITMS Register Table
as a reference of register assignments and data.
First Register: This specifies the first, or only, register to be read in a block.
# of Registers: This is the length of the block to be read. The module supports block read and write
commands up to 16 registers in length.
Data Format: Allows registers to be viewed in decimal or hexadecimal format.
Read: Clicking the Read button causes SFIMS software to read the selected register from the module.
Write: Clicking the Write button causes SFIMS software to write the selected registers to the module.
Note: The Write button overwrites the existing register values, and may change the module setup and
operation.
STEP 11 CALIBRATION
The ITMS is fully calibrated from the factory. Recalibration is recommended every two years. Each
range has its own internal references that are recalled when the range is selected. This allows
independent calibration for each range. All calibration settings are stored in the E2PROM. Calibration
may be performed by using SFIMS software or MODBUS commands.
RTD and CJ calibrations are dependent on the millivolt calibration and, therefore, must be performed
after a millivolt calibration has been completed. RTD or CJ calibration may be performed independently
of the millivolt calibration.
Calibration Type: This specifies the type of calibration to be performed.
Cold Junction Calibration:
TC Type: This selects the type of TC that is being used to calibrate the cold junction.
Scale: This selects the scale in which the Thermometer temperature is entered and the Module
temperature is displayed.
Thermometer: Enter the reference thermometer temperature here.
Module: This displays the ITMS process temperature value after a cold junction calibration is
completed to verify the accuracy.
Calibrate: The Calibrate button initiates the calibration process after the appropriate settings are
selected.
Note: Millivolt calibration requires a precision voltage source with an accuracy of 0.025% or better.
Allow the ITMS to warm up for 30 minutes minimum and follow the manufacturer’s warm-up
recommendations for the calibration source. RTD calibration requires a 0.1% precision 300 ohm
resistor. CJ calibration should be performed with a TC of known accuracy of types T, E, J, K, C or N
only. When using SFIMS for calibration, select the type of calibration to be performed, and press the
Calibrate button. Follow the calibration procedures in the software.
9
TROUBLESHOOTING
PROBLEM
CAUSE
REMEDIES
Green LED will not light
Module power
Check module power connections and voltage level
Process Value not changing
Input signal
Check input signal connections and signal level
Process Value not changing or incorrect
Incorrect scaling
Check input setup, scaling values, and re-download
Alarms disabled
Alarm threshold over range*; checksum
error; Input over/under range; open or
shorted probe*; calculated results over
+32000 or -32000; in Calibration Mode
Input over or under range* due to:
Wrong TC, or RTD
Incorrect input type
Adjust alarm Setpoint and Hysteresis to ensure trigger
point is within -32000 to +32000 (See Alarm setup). For
other possible causes, see the remaining remedies
Process Value stays at 32002
Open TC or RTD:*
Check input signal connections and probe
Process Value stays at -32002
Shorted RTD:*
Check input signal connections and probe
Process Value stays at +32003 or -32003
Calculated Temp. value over +32000 or
-32000
Check offset value, Register 40012
Process Value stays at 32100, Flashing
LEDs, alarms disabled
Parameter checksum*, loss of
parameter settings
Calibration checksum*
Re-download SFIMS file (reconfigures each parameter)
Will not communicate
(Green LED not flashing)
Incorrect serial settings (ITMS port)
Incorrect serial settings (computer port)
Incorrect wiring
Process Value stays at 32001 or -32001
Check input level
Check input type, and re-download
Perform calibration procedure
Verify ITMS communications setup
Go to pull down menu SETTINGS, PC PORT SETTINGS
Try switching A+ and B- lines
Provide a common connection
NOTE: The ITMS’ serial settings must match the device that it is communicating with. If you do not know or
cannot recall the ITMS settings, they can be reset back to factory defaults. Simply jumper the Serial Default
terminal to Common, and cycle power. The serial settings will default to RTU mode, 9600 baud, 8 data bits, no
parity, with an address of 247.
* Can be monitored by accessing coils 9-16, or register 40025.
For further technical assistance, contact technical support.
INSTALLATION
The unit is equipped with a universal mounting foot for attachment to standard DIN style mounting rails, including G profile rail
according to EN50035 - G32 , and top hat (T) profile rail according to EN50022 - 35 x 7.5 and 35 x 15. The unit should be installed in a
location that does not exceed the maximum operating temperature and provides good air circulation. Placing the unit near devices that
generate excessive heat should be avoided.
G Rail Installation
To install the ITMS on a “G”
style DIN rail, angle the module
so that the upper groove of the
“foot” catches under the lip of the
top rail. Push the module toward
the rail until it snaps into place.
To remove a module from the
rail, push up on the bottom of the
module while pulling out and
away from the rail.
T Rail Installation
To install the ITMS on a “T”
style rail, angle the module so
that the top groove of the “foot”
is located over the lip of the top
rail. Push the module toward the
rail until it snaps into place. To
remove a module from the rail,
insert a screwdriver into the slot
on the bottom of the “foot”, and
pry upwards on the module until
it releases from the rail.
APPLICATION
A chemical company wanted to remotely monitor the
temperature of several holding tanks. Using the ITMS, the
customer was able to receive, interpret, and store the
temperature readings via standard thermocouples. To provide a
remote display, the customer chose a Red Lion Paradigm HMI
(Human Machine Interface). The HMI communicates with the
ITMS modules and displays the information graphically,
providing an intuitive interface. As an added benefit, the ITMS
alarm setpoints can be adjusted from the HMI, while providing
reliable local alarm outputs.
10
MODBUS INFORMATION
The remaining sections of this bulletin list ITMS Register Format information and MODBUS conformity.
MODBUS SUPPORTED FUNCTION CODES
03: Illegal Data Value
Issued when an attempt is made to read or write more registers or coils than
the unit can handle in one request.
FC01: Read Coils
1. Valid coil addresses are 1-16.
2. Only 16 coils can be requested at one time.
3. Block starting point can not exceed coil 16.
07: Negative Acknowledge
Issued when a write to coil or register is attempted with an invalid string
length.
FC05: Force Single Coil
1. Valid write (force) coil addresses are 1-10.
2. <8001>HEX is echoed back that the coil did not change during the request to
write to a read only coil.
CHECKSUM ERRORS
1. Calibration checksum covers the E2 PROM that contains calibration values
for all ranges. When a calibration checksum error occurs, coil 10 becomes a
1. (See Coils Table)
2. Parameter checksum covers the E2 PROM that contains the stored Holding
register settings. When a parameter checksum error occurs, coil 9 becomes a
1. (See Coils Table)
3. All of the LEDs will flash as long as either error occurs.
4. The alarms are disabled as long as either error occurs.
5. Either error can be cleared or activated manually by writing to the appropriate
coil. (This does not correct the reason for the error. It may be necessary to
reconfigure or calibrate.)
6. Both checksums are verified at power up.
FC15: Force Multiple Coils
1. Valid write (force) coil addresses are 1-10.
2. Block starting point can not exceed coil 10.
3. If a multiple write includes read only coils, then only the write coils will change.
FC03: Read Holding Registers
1. Valid addresses are 40001-40029, 41001-41010, 41101-41116.
2. Only 16 registers can be requested at one time.
3. Block starting point can not exceed the register boundaries.
4. <8000>HEX is returned in registers beyond the boundaries.
5. Holding registers are a mirror of Input registers.
CALIBRATION
FC06: Preset Single Register
1. Valid write (preset) addresses are 40006-40029, 41101-41116.
2. <8001>HEX is echoed back that the register did not change during the
request to write to a read only register.
3. If the write value exceeds the register limit (see Register Table), then that
register value changes to its exceeded high or low limit. It is also returned in
the response.
Calibration may be performed by using SFIMS software, or MODBUS
commands. Review Calibration explanation in Step 11, before performing these
steps.
mV Calibration
1. Connect the signal source to proper ITMS terminals.
2. To set Input Type, enter 9 into register 40008.
3. To start calibration, enter <7777> HEX into register 40029.
4. To start ADC calibration, enter <0001> HEX into register 40029.
5. Apply the appropriate voltage and enter the corresponding <>HEX value into
register 40029 for each range to be calibrated.
0 mV <0002>, 14 mV <0003>, 28 mV <0004>, 42 mV <0005>, 56 mV <0006>
6. To save the values and end calibration, enter <0000> HEX into register 40029.
FC16: Preset Multiple Registers
1. Valid write (force) register addresses are 40006-40029, 41101-41116.
2. No response is given with an attempt to write to more than 16 registers at a time.
3. Block starting point can not exceed the read and write boundaries.
4. If a multiple write includes read only registers, then only the write registers
will change.
5. If the write value exceeds the register limit (see Register Table), then that
register value changes to its exceeded high or low limit.
CJ Calibration
Note: In this procedure, write functions are performed in HEX and a write to a
register is monitored by a read in a different register.
1. Connect the thermocouple probe source to the proper ITMS terminals. (Types
T, E, J, K, N and C only).
2. To set Input Type, enter connected TC type into register 40008.
3. To set Scale, enter 1 for °C or 0 for °F into register 40006.
4. To set High Resolution, enter 1 into register 40009.
5. Place an external reference thermometer probe at the end of the ITMS probe.
The two probes should be shielded from air movement and allow sufficient
time to equalize in temperature. (As an alternative, the ITMS probe may be
placed in a calibration bath of known temperature.)
6. To start calibration, enter <7777> HEX into register 40029.
7. To start CJ calibration, enter <0010> HEX into register 40029.
8. Read the Process Temperature Value register 40002 (Read as an Integer).
9. Subtract the external reference reading from the Process Temperature Value
register 40002 reading. Adjust the results to hundredths position, drop
decimal point, and maintain the results sign. (If the difference is -2.0 degrees,
then adjust to -2.00 and remove decimal point yielding a value of -200.)
10. Enter <0011> HEX into register 40029.
11. Add the value from step 9 (maintain the sign) to the value existing in register
40007 (Read as an Integer).
12. If necessary, continue to adjust register 40007 value until the Process
Temperature Value register 40002 matches the external reference reading.
13. To save the values and end calibration, enter <0000> HEX into register
40029.
FC04: Read Input Registers
1. Valid addresses are 30001-30029, 31001-31010, 31101-31116.
2. Only 16 registers can be requested at one time.
3. Block starting point can not exceed register boundaries.
4. <8000>HEX is returned in registers beyond the boundaries.
5. Input registers are a mirror of Holding registers.
FC08: Diagnostics
The following is sent upon FC08 request:
Unit Address, 08 (FC code), 04 (byte count), “Total Comms” 2 byte count,
“Total Good Comms” 2 byte count, checksum of the string.
“Total Comms” is the total number of messages received that were addressed to
the ITMS. “Total Good Comms” is the total messages received by the ITMS
with good address, parity and checksum. Both counters are reset to 0 upon
response to FC08.
FC17: Report Slave ID
The following is sent upon FC17 request:
Unit Address, 17 (FC code), RLC-ITMS4037, 0100 (for code version 1.00), 16
(number of read supported registers), 16 (number of writes supported
registers), 16 (number of registers available for GUID/ Scratch pad memory),
checksum of the string.
The following is the HEX of the above (with unit address of 247):
<F7><11><14><52><4C><43><2D><49><54><4D><53><34><30><33>
<37><01><00><00><10><00><10><00><10><8D><9F>
RTD Calibration
SUPPORTED EXCEPTION CODES
1. Connect precision 300 ohm resistor to terminals 11 & 12. Short terminals 10 & 11.
2. To set Input Type, enter 13 (Integer) or <000D> HEX into register 40008.
3. To start calibration, enter <7777> HEX into register 40029.
4. To start 0 ohm RTD calibration, enter <0015> HEX into register 40029.
5. Apply 0 ohms by shorting terminals 11 & 12 for 10 seconds.
6. To start 300 ohm RTD calibration, enter <0016> HEX into register 40029.
7. Apply 300 ohms by removing short from terminal 11 for 10 seconds.
8. To save the values and end calibration, enter <0000> HEX into register 40029.
01: Illegal Function
Issued whenever the requested function is not implemented in the unit.
02: Illegal Data Address
Issued whenever an attempt is made to access a single register or coil that
does not exist (outside the implemented space) or to access a block of registers
or coils that falls completely outside the implemented space.
11
REGISTER TABLE
The below limits are shown as Integers or HEX < > values. Read and write functions can be performed in either Integers or HEX as long as the conversion was
done correctly. Negative numbers are represented by two’s complement.
REGISTER
ADDRESS *
LOW LIMIT† HIGH LIMIT†
REGISTER NAME
ACCESS
COMMENTS
40001
ADC reading
N/A
N/A
Read Only
ADC (Analog to Digital Converter) reading of present input level.
40002
Process Temperature Value
N/A
N/A
Read Only
Process Value (with scale and offset) of present input level.
40003
Floating Point LO
N/A
N/A
Read Only
40004
Floating Point HI
N/A
N/A
Read Only
40005
User Input Pin State
N/A
N/A
Read Only
0 = Active, 1 = Inactive.
40006
Temperature Scale
40007
CJ Temp
40008
IEEE Standard 754 Floating Decimal Point, low order of Temperature Value.
(Allows 32 bit accuracy for external monitoring.)
IEEE Standard 754 Floating Decimal Point, high order of Temperature Value.
(Allows 32 bit accuracy for external monitoring.)
0
1
Read/Write
0 = °F, 1= °C.
-32000
32000
Read/Write
Cold Junction calibration temp (1 = 0.01°C).
Input Type
0
13
Read/Write
See Input Type Register Table.
40009
High Resolution
0
1
Read/Write
0 = 1 degree, 1 = 0.1 degree.
40010
Filter Band
0
32000
Read/Write
See Filter Band explanation.
40011
Filter Response Time
0
1000
Read/Write
See Filter Response Time explanation (1 = 0.1 second).
40012
Offset Value
-32000
32000
Read/Write
See Offset explanation.
40013
User Input Action
<0000>
<0015>
Read/Write
See User Input Action Register Table.
40014
Alarm 2 Action
<0000>
<0038>
Read/Write
See Alarm 1 & 2 Action Register Table.
40015
Setpoint 2 Value
-32000
32000
Read/Write
Alarm 2 setpoint value based on Process Value.
40016
Alarm 2 Hysteresis
1
32000
Read/Write
Alarm 2 hysteresis value based on Process Value.
40017
Alarm 2 Delay
0
32000
Read/Write
Alarm 2 delay trip on time (1 = 1 second).
40018
Alarm 1 Action
<0000>
<0034>
Read/Write
See Alarm 1 & 2 Action Register Table.
40019
Setpoint 1 Value
-32000
32000
Read/Write
Alarm 1 setpoint value based on Process Value.
40020
Alarm 1 Hysteresis
1
32000
Read/Write
Alarm 1 hysteresis value based on Process Value.
40021
Alarm 1 Delay
0
32000
Read/Write
Alarm 1 delay trip on time (1 = 1 second).
40022
Sensor Failure Action
0
3
Read/Write
See Sensor Failure Action For Alarm State Table.
40023
Transmit Delay
1
255
Read/Write
Delay before serial transmission (1 = 1 msec). See Transmit Delay Explanation.
40024
Node (Unit) Address
1
247
Read/Write
Node serial ITMS address.
40025
Error Coils
<0000>
<0003>
Read/Write
Mirror of Coils 9-16. See Coil Table.
40026
Comm. Coils
<0020>
<00FF>
Read/Write
Mirror of Coils 1-8. See Coil Table and Communications Table.
40027
Alarm 1 State
0
1
Read/Write
Alarm 1 state (1 = on).
40028
Alarm 2 State
0
1
Read/Write
Alarm 2 state (1 = on).
40029
Factory Calibration
<0000>
<7777>
Read/Write
See MODBUS Calibration explanation.
41001- 41010 Slave ID
41101- 41116 GUID/Scratch
See FC17. See FC17.
<0000>
<FFFF>
Read Only
Read/Write
ITMS-4037, 0100 (ver. 1.00), 16 reads, 16 writes, 16 scratch. The version value
could be higher.
This area is for the user to store any related information.
This register area does not affect ITMS operations.
* For Input Registers, replace the 4xxxx with a 3xxxx in the above register address. The 3xxxx are a mirror of the 4xxxx Holding Registers.
† An attempt to exceed a limit will set the register to its high or low limit value.
COILS TABLE (COMMUNICATION AND ERRORS)
COIL ADDRESS
COIL NAME
ACCESS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Baud B0
Baud B1
Baud B2
Parity B3
Parity B4
Data Bits B5
Mode B6
Change B7
P. Checksum Error
C. Checksum Error
AL 1 Over Range
AL 2 Over Range
Open Input
Over Range
Under Range
Shorted RTD
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
COMMENTS
See Communication Register and Coils Table.
See Communication Register and Coils Table.
See Communication Register and Coils Table.
See Communication Register and Coils Table.
See Communication Register and Coils Table.
See Communication Register and Coils Table.
See Communication Register and Coils Table.
“1” = Change ITMS communications to above settings.
“1” = Parameter checksum error, disables alarms, causes flashing LEDs.
“1” = Calibration checksum error, disables alarms, causes flashing LEDs.
“1” = Alarm 1 Threshold over range, disables alarms, causes no LED indication.
“1” = Alarm 2 Threshold over range, disables alarms, causes no LED indication.
“1” = Open RTD or TC, causes Process Temp. Value to be 32002, disables alarms, causes no LED indication.
“1” = Over Range, causes Process Temp. Value to be 32001, disables alarms, causes no LED indication.
“1” = Under Range, causes Process Temp. Value to be -32001, disables alarms, causes no LED indication.
“1” = Shorted RTD, causes Process Temp. Value to be -32002, disables alarms, causes no LED indication.
Coils 1-7 mirror register 40026 and Coils 9-16 mirror register 40025.
12
INPUT TYPE REGISTER (40008) TABLE
USER INPUT ACTION REGISTER (40013) TABLE
MODE
TYPE
MODE
TYPE
MODE
TYPE
MODE
0
Tc - T
5
Tc - S
10
RTD - 385
<0000>
Reset
1
Tc - E
6
Tc - B
11
RTD - 392
<0001>
2
Tc - J
7
Tc - N
12
RTD - 672
<0002>
3
Tc - K
8
Tc - C
13
LIN Ohms
4
Tc - R
9
LIN mV
SENSOR FAILURE ACTION REGISTER (40022) TABLE
FOR ALARM STATE CONDITION
MODE
ALARM 1
0
ALARM 2
Off
1
Off
On
On
2
Off
On
3
On
Off
ACTION
ALARM
INPUT ACTIVATION
1
Level (Maintained)
Reset
2
Level (Maintained)
Reset
1&2
Level (Maintained)
<0003>
Set
1
Level (Maintained)
<0004>
Set
2
Level (Maintained)
<0005
Set
1&2
Level (Maintained)
<0010>
Reset
1
Edge (Momentary)
<0011>
Reset
2
Edge (Momentary)
<0012>
Reset
1&2
Edge (Momentary)
<0013>
Set
1
Edge (Momentary)
<0014>
Set
2
Edge (Momentary)
<0015>
Set
1&2
Edge (Momentary)
ALARM 1 (40018) & 2 (40014) ACTION REGISTER TABLE
Latched
Stand By Off=Auto
off
off
on
on
off
on
off
on
B7
B6
B5
B4
2nd Nibble
HEX
0
0
0
0
<0 >
0
0
0
0
0
0
0
1
1
1
0
1
ACTION
MODE
ALARMS
B3
B2
B1
B0
1st Nibble
HEX
Manual
0
1
2
0
0
0
0
< 0>
<1 >
Absolute Hi, balanced
1
1
2
0
0
0
1
< 1>
<2 >
Absolute Lo, balanced
2
1
2
0
0
1
0
< 2>
<3 >
Absolute Hi, unbalanced
3
1
2
0
0
1
1
< 3>
Absolute Lo, unbalanced
4
1
2
0
1
0
0
< 4>
Deviation Hi
5
2
0
1
0
1
< 5>
Deviation Lo
6
2
0
1
1
0
< 6>
Band Outside
7
2
0
1
1
1
< 7>
Band Inside
8
2
1
0
0
0
< 8>
Examples:
Alarm 1 (40018):
Stand-by off, Latch on = 0 0 0 1 <1 >
Absolute Lo, Balanced = 0 0 1 0 < 2>
<1 2>
Alarm 2 (40014):
Stand-by on, Latch off = 0 0 1 0 <2 >
Band Outside
= 0 1 1 1 < 7>
<27>
See Setpoint Alarm Figures, Page 5, for illustrations of alarm operation.
COMMUNICATIONS REGISTER (40026) AND COILS 1-8 TABLE
Mode
Parity
Baud
Coil 8
B7*
Coil 7
B6
Coil 6
B5
Coil 5
B4
Coil 4
B3
Coil 3
B2
Coil 2
B1
Coil 1
B0
Coil 8 =0
HEX
Coil 8 =1
HEX
RTU
8N1,2
300
0/1
0
1
0
0
0
0
0
<20>
<A0>
RTU
8N1,2
600
0/1
0
1
0
0
0
0
1
<21>
<A1>
RTU
8N1,2
1200
0/1
0
1
0
0
0
1
0
<22>
<A2>
RTU
8N1,2
2400
0/1
0
1
0
0
0
1
1
<23>
<A3>
RTU
8N1,2
4800
0/1
0
1
0
0
1
0
0
<24>
<A4>
RTU
8N1,2
9600
0/1
0
1
0
0
1
0
1
<25>
<A5>
RTU
8N1,2
19200
0/1
0
1
0
0
1
1
0
<26>
<A6>
RTU
8N1,2
38400
0/1
0
1
0
0
1
1
1
<27>
<A7>
RTU
8E1
300
0/1
0
1
0
1
0
0
0
<28>
<A8>
RTU
8E1
600
0/1
0
1
0
1
0
0
1
<29>
<A9>
RTU
8E1
1200
0/1
0
1
0
1
0
1
0
<2A>
<AA>
RTU
8E1
2400
0/1
0
1
0
1
0
1
1
<2B>
<AB>
RTU
8E1
4800
0/1
0
1
0
1
1
0
0
<2C>
<AC>
RTU
8E1
9600
0/1
0
1
0
1
1
0
1
<2D>
<AD>
RTU
8E1
19200
0/1
0
1
0
1
1
1
0
<2E>
<AE>
RTU
8E1
38400
0/1
0
1
0
1
1
1
1
<2F>
<AF>
RTU
8O1
300
0/1
0
1
1
1
0
0
0
<38>
<B8>
RTU
8O1
600
0/1
0
1
1
1
0
0
1
<39>
<B9>
RTU
8O1
1200
0/1
0
1
1
1
0
1
0
<3A>
<BA>
RTU
8O1
2400
0/1
0
1
1
1
0
1
1
<3B>
<BB>
RTU
8O1
4800
0/1
0
1
1
1
1
0
0
<3C>
<BC>
RTU
8O1
9600
0/1
0
1
1
1
1
0
1
<3D>
<BD>
RTU
8O1
19200
0/1
0
1
1
1
1
1
0
<3E>
<BE>
RTU
8O1
38400
0/1
0
1
1
1
1
1
1
<3F>
<BF>
* When reading register 40026, B7 will be a 0. When writing (changing ITMS communications to the new setting), change B7 to a 1.
13
COMMUNICATIONS REGISTER (40026) AND COILS 1-8 TABLE (continued)
Mode
Parity
Baud
Coil 8
B7 *
Coil 7
B6
Coil 6
B5
Coil 5
B4
Coil 4
B3
Coil 3
B2
Coil 2
B1
Coil 1
B0
Coil 8 =0
HEX
Coil 8 =1
HEX
ASCII
7N2
300
0/1
1
0
0
0
0
0
0
<40>
<C0>
ASCII
7N2
600
0/1
1
0
0
0
0
0
1
<41>
<C1>
ASCII
7N2
1200
0/1
1
0
0
0
0
1
0
<42>
<C2>
ASCII
7N2
2400
0/1
1
0
0
0
0
1
1
<43>
<C3>
ASCII
7N2
4800
0/1
1
0
0
0
1
0
0
<44>
<C4>
ASCII
7N2
9600
0/1
1
0
0
0
1
0
1
<45>
<C5>
ASCII
7N2
19200
0/1
1
0
0
0
1
1
0
<46>
<C6>
ASCII
7N2
38400
0/1
1
0
0
0
1
1
1
<47>
<C7>
ASCII
7E1
300
0/1
1
0
0
1
0
0
0
<48>
<C8>
ASCII
7E1
600
0/1
1
0
0
1
0
0
1
<49>
<C9>
ASCII
7E1
1200
0/1
1
0
0
1
0
1
0
<4A>
<CA>
ASCII
7E1
2400
0/1
1
0
0
1
0
1
1
<4B>
<CB>
ASCII
7E1
4800
0/1
1
0
0
1
1
0
0
<4C>
<CC>
ASCII
7E1
9600
0/1
1
0
0
1
1
0
1
<4D>
<CD>
ASCII
7E1
19200
0/1
1
0
0
1
1
1
0
<4E>
<CE>
ASCII
7E1
38400
0/1
1
0
0
1
1
1
1
<4F>
<CF>
ASCII
7O1
300
0/1
1
0
1
1
0
0
0
<58>
<D8>
ASCII
7O1
600
0/1
1
0
1
1
0
0
1
<59>
<D9>
ASCII
7O1
1200
0/1
1
0
1
1
0
1
0
<5A>
<DA>
ASCII
7O1
2400
0/1
1
0
1
1
0
1
1
<5B>
<DB>
ASCII
7O1
4800
0/1
1
0
1
1
1
0
0
<5C>
<DC>
ASCII
7O1
9600
0/1
1
0
1
1
1
0
1
<5D>
<DD>
ASCII
7O1
19200
0/1
1
0
1
1
1
1
0
<5E>
<DE>
ASCII
7O1
38400
0/1
1
0
1
1
1
1
1
<5F>
<DF>
ASCII
8N1
300
0/1
1
1
0
0
0
0
0
<60>
<E0>
ASCII
8N1
600
0/1
1
1
0
0
0
0
1
<61>
<E1>
ASCII
8N1
1200
0/1
1
1
0
0
0
1
0
<62>
<E2>
ASCII
8N1
2400
0/1
1
1
0
0
0
1
1
<63>
<E3>
ASCII
8N1
4800
0/1
1
1
0
0
1
0
0
<64>
<E4>
ASCII
8N1
9600
0/1
1
1
0
0
1
0
1
<65>
<E5>
ASCII
8N1
19200
0/1
1
1
0
0
1
1
0
<66>
<E6>
ASCII
8N1
38400
0/1
1
1
0
0
1
1
1
<67>
<E7>
ASCII
8E1
300
0/1
1
1
0
1
0
0
0
<68>
<E8>
ASCII
8E1
600
0/1
1
1
0
1
0
0
1
<69>
<E9>
ASCII
8E1
1200
0/1
1
1
0
1
0
1
0
<6A>
<EA>
ASCII
8E1
2400
0/1
1
1
0
1
0
1
1
<6B>
<EB>
ASCII
8E1
4800
0/1
1
1
0
1
1
0
0
<6C>
<EC>
ASCII
8E1
9600
0/1
1
1
0
1
1
0
1
<6D>
<ED>
ASCII
8E1
19200
0/1
1
1
0
1
1
1
0
<6E>
<EE>
ASCII
8E1
38400
0/1
1
1
0
1
1
1
1
<6F>
<EF>
ASCII
8O1
300
0/1
1
1
1
1
0
0
0
<78>
<F8>
ASCII
8O1
600
0/1
1
1
1
1
0
0
1
<79>
<F9>
ASCII
8O1
1200
0/1
1
1
1
1
0
1
0
<7A>
<FA>
ASCII
8O1
2400
0/1
1
1
1
1
0
1
1
<7B>
<FB>
ASCII
8O1
4800
0/1
1
1
1
1
1
0
0
<7C>
<FC>
ASCII
8O1
9600
0/1
1
1
1
1
1
0
1
<7D>
<FD>
ASCII
8O1
19200
0/1
1
1
1
1
1
1
0
<7E>
<FE>
ASCII
8O1
38400
0/1
1
1
1
1
1
1
1
<7F>
<FF>
* When reading register 40026, B7 will be a 0. When writing (changing ITMS communications to the new setting), change B7 to a 1.
14
This page intentionally left blank
15
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship
for a period limited to two years from the date of shipment, provided the products have been stored,
handled, installed, and used under proper conditions. The Company’s liability under this limited
warranty shall extend only to the repair or replacement of a defective product, at The Company’s
option. The Company disclaims all liability for any affirmation, promise or representation with
respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
damages, claims, and expenses arising out of subsequent sales of RLC products or products
containing components manufactured by RLC and based upon personal injuries, deaths, property
damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be
to any extent liable, including without limitation penalties imposed by the Consumer Product Safety
Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty
Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those
expressly contained herein. The Customer acknowledges the disclaimers and limitations contained
herein and relies on no other warranties or affirmations.
Red Lion Controls AP
Red Lion Controls
20 Willow Springs Circle
Red Lion Controls BV
Basicweg 11b
31, Kaki Bukit Road 3,
#06-04/05 TechLink
York PA 17406
NL - 3821 BR Amersfoort
Singapore 417818
Tel +1 (717) 767-6511
Tel +31 (0) 334 723 225
Tel +65 6744-6613
Fax +1 (717) 764-0839
Fax +31 (0) 334 893 793
Fax +65 6743-3360
Similar pages